Alarm Limits
SETTINGS
ALARM LIMITS
OVERPRESSURE ALARM
Use to adjust the displayed voltage for each phase in the Mark II
XG
. Press to con
fi
rm. Adjustment can
be made in 0.1% increments to more closely match actual voltage. These discrepancies are due to tolerances in the
potential transformers used for the voltage conversions.
ENABLED
1
Use arrows to enable or disable the Overpressure Alarm. Press to con
fi
rm.
LIMIT
1
Use arrows to set the pressure limit for the Overpressure Alarm. Press to con
fi
rm.
1
Use arrows to set the voltage limit for the Undervoltage Alarm. Press to con
fi
rm.
Note: The maximum and default setting is approximately -15% of nominal voltage.
Use arrows to enable or disable the Undervoltage Alarm. Press to con
fi
rm.
Use arrows to set the voltage limit for the Overvoltage Alarm. Press to con
fi
rm.
Note: The maximum and default setting is approxi10% of nominal voltage.
Use arrows to enable or disable the Overvoltage Alarm. Press to con
fi
rm.
Note: This setting only available on high voltage controllers, 2300 - 7200 Volts (FTA2000, FTA2400).
Use arrows to set the frequency limit for the Under frequency Alarm. Press to con
fi
rm.
Use arrows to enable or disable the Under frequency Alarm. Press to con
fi
rm.
Use arrows to set the frequency limit for the Over frequency Alarm. Press to con
fi
rm.
Use arrows to enable or disable the Over frequency Alarm. Press to con
fi
rm.
Use arrows to set the percentage of deviance between phases for the Phase Imbalance alarm.
Press to con
fi
rm.
Use arrows to set the motor amps for the Motor Overload alarm (FLA - 150% FLA).
Press to con
fi
rm.
TX
This is a value representing communications sent to the digital soft starter.
RX
This is a value representing communications received from the digital soft starter.
ERROR
This is a value representing communication errors between the Mark II
XG
and the digital soft starter.
2
SETTINGS
MOTOR & POWER
TRIM VOLTAGE
SETTINGS
ALARM LIMITS
VOLT MIN
ENABLED
1
1
SETTINGS
ALARM LIMITS
VOLT MAX
ENABLED
1
1
SETTINGS
ALARM LIMITS
FREQ MIN
ENABLED
1
1
SETTINGS
ALARM LIMITS
FREQ MAX
ENABLED
1
1
SETTINGS
ALARM LIMITS
IMBALANCE
1
SETTINGS
ALARM LIMITS
OVERLOAD
NO CURRENT AT RUN
This is a read only setting that is transmitted to the digital soft starter.
CT RATIO
This is a read only setting that is transmitted to the digital soft starter.