background image

1

REMOVE DRIVE

Use                 arrows to enable or disable the Remove Drive feature.  Press            to con

fi

 rm.

Much like a computer, the Remove Drive feature ensures 

fi

 le closure prior to removing the USB 

fl

 ash drive from the 

Mark II

XG

.  Use of this feature helps prevent 

fi

 le corruption.

NOTE:  The Mark IIXG also features an automatic daily save function.  Every day at midnight (0:00) the events for that 
day are written to a 

fi

 le on the USB 

fl

 ash drive.  This 

fi

 le is also a text 

fi

 le (.txt) and is named for the month, in the current 

year folder under Firetrol (x:\Firetrol\2009\Sept.txt).

19

MOTORSCOPE

MOTORSCOPE

Information is displayed for the following:
Startup Time
Sampling Rate
Voltage Min.
Current Max.

VOLTAGE GRAPH

A graphical display of the controller voltage is shown representing the 

fi

 rst 10 seconds of the last motor start.

CURRENT GRAPH

A graphical display of the motor current is shown representing the 

fi

 rst 10 seconds of the last motor start.

FACTORY

CONFIGURATION

MODEL

3

SERIAL NUMBER

Use                             arrows to enter the controller serial number.  Press            to con

fi

 rm.

NOTE:  This is a factory set parameter and under normal circumstances would never be changed.

3

MODEL

Use                 arrows to select required model number.  Press            to con

fi

 rm.

NOTE:  This is a factory set parameter and under normal circumstances would never be changed.

3

HP (HORSEPOWER)

Use                 arrows to select required motor horsepower.  Press            to con

fi

 rm.

NOTE:  This is a factory set parameter and under normal circumstances would never be changed.

3

VOLTAGE

Use                 arrows to select required voltage.  Press            to con

fi

 rm.

NOTE:  This is a factory set parameter and under normal circumstances would never be changed.

3

FULL LOAD

Use                 arrows to set the full load amps (FLA) of the motor.  Press            to con

fi

 rm.

NOTE:  This is a factory set parameter and under normal circumstances would never be changed.  

3

CT RATIO

Use                 arrows to set required CT ratio for the controller.  Press            to con

fi

 rm.

NOTE:  This is a factory set parameter and under normal circumstances would never be changed.

Configuration - Model

3

FREQUENCY

Use                 arrows to select required frequency (hertz) for the supplied power.  Press            to con

fi

 rm.

NOTE:  This is a factory set parameter and under normal circumstances would never be changed.

1

Use                  to select required phase sequence (1~, abc, cba).  Press            to con

fi

 rm.

PHASE SEQUENCE

Содержание Emerson Mark IIXG

Страница 1: ...Installation and Operation Instructions Mark IIXG Electric Fire Pump Controllers NS1000 50 A ECN 237793...

Страница 2: ...50 1000 1500 1800 2000 2400 5 FTA1250 5 FTA1300 1350 5 6 FTA1930 6 FTA900 975 Transfer Switch 6 FTA950 976 Transfer Switch 6 INITIAL START UP OPERATION 7 MANUAL START 7 EMERGENCY RUN START 7 ABBREVIAT...

Страница 3: ...Units 14 Start 14 Stop 14 Automatic Shutdown Disabled 14 Overpressure Alarm 14 Recording Delta Hourly 14 Sensor 14 Calibration 14 Reset to Defaults 14 Motor Power System Volts 14 Phase Sequence 15 Fr...

Страница 4: ...ttings Interlock Alarm 17 Low Pressure Audible 17 Low Suction 17 Pump Run Alarm 17 User Input 17 Weekly Test 17 18 Option Settings 18 MAIN MENU EVENT LOG 18 MAIN MENU DATA HISTORY 18 MAIN MENU USB Sav...

Страница 5: ...n 20 Diagnostics Raw Input Analog 20 Raw Input Discrete 20 Raw Input Keys 20 Raw Output Discrete 20 Mark IIXG Starts 20 Lamp Test 20 Audible Test 21 USB Test 21 Phase Fail 21 Phase Reverse 21 Shunt 1...

Страница 6: ...ary Resistance Reduced Voltage Starting Closed Circuit Transition FTA1800 Autotransformer Reduced Voltage Starting Closed Circuit Transition FTA1930 Digital Soft Starting FTA2000 High Voltage Starting...

Страница 7: ...nting 5 Using either the dimension print or by measuring the distance between the center lines of the lower bracket slots transcribe this dimension onto the wall Note The bottom edge of the en closure...

Страница 8: ...e 2 Verify that the controller information is what is required on the project Firetrol catalog number Motor voltage and horsepower Incoming line voltage and frequency Maximum system pressure 3 Project...

Страница 9: ...wnonfieldconnection diagram 4 If a deluge valve is used remove the factory installed jumper from terminals as shown on field connection diagram Connect wires from the normally closed contact on the de...

Страница 10: ...press the manual STOP push button 4 Observe direction of motor rotation 5 Ifrotationisincorrect confirmthattheisolatingswitch circuitbreakerisintheOFFposition open enclosure door and reverse any two o...

Страница 11: ...to the emergency power source 4 Start the generator set at the generator control panel 5 Withthegeneratorrunningatstablevoltageandfrequencymomentarilyclosethepowertransfer switch isolating disconnect...

Страница 12: ...d continue to run It will not stopautomatically Therunningperiodtimerandpressureswitchhavenocontroloverthismanual operation 3 To stop press the STOP push button 4 Starting from a remote START push but...

Страница 13: ...structions 2 MOTOR ACCELERATION timer is factory set for 2 seconds and may be field adjusted if necessary See Mark IIXG Programming for details CAUTION DO NOT EXCEED FOUR 4 SECONDS MAXIMUM 3 Contactor...

Страница 14: ...7 26 Mark IIXG User Interface and Display 1 2 4 3 5 6 Informational Display Control Status and System Pressure Frequency Phase Rotation Phases Line Voltage Phase Motor Current Phase Active Alarms Prim...

Страница 15: ...Interlock Alarm Low Press Aud Low Suction Pump Run User Input Weekly Test Event Log Event History Data History Calls to Start Starts Pump Total Run Time Last Pump Run Time Controller Power On Time La...

Страница 16: ...on These options are indicated by a for enabled or a x for disabled In many cases this can also be interpreted as for yes or a x for no 1 Indicates the level of password required to modify a setting 1...

Страница 17: ...i bar kPa Press to confirm Note Many menu settings feature an enable disable option These options are indicated by a for enabled or a x for disabled 1 Indicates the level of password required to modif...

Страница 18: ...S TIMERS ON DELAY 1 Use arrows to set preferred on delay time Press to confirm Note On Delay also known as sequential start time delays the starting of the motor when an automatic call to start is rec...

Страница 19: ...CALIBRATION SET TO ZERO 2 Use arrows to set zero calibration value Press to confirm SET TO SPAN Use arrows to set span calibration value Press to confirm Note Remove interlock jumper wire when calibra...

Страница 20: ...el at the beginning of the deceleration ramp DECEL PAUSE LEVEL 3 Use to set the Deceleration Pause Level 32 60 FLA Press to confirm The starter will reduce current to set level at the beginning of the...

Страница 21: ...se arrows to set the frequency limit for the Under frequency Alarm Press to confirm Use arrows to enable or disable the Under frequency Alarm Press to confirm Use arrows to set the frequency limit for...

Страница 22: ...to confirm 1 ON DELAY Use arrows to select an on delay time before the alarm is acknowledged 0 99 seconds Press to confirm 1 AUDIBLE Use arrows to select if the user input activates the audible alarm...

Страница 23: ...s to start Number of actual starts Pump total run time Pump last run time Total controller power on time Last pump start time date Minimum system pressure Maximum system pressure Last phase failure La...

Страница 24: ...confirm NOTE This is a factory set parameter and under normal circumstances would never be changed 3 MODEL Use arrows to select required model number Press to confirm NOTE This is a factory set parame...

Страница 25: ...disable the screen saver function Press to confirm NOTE The display screen is designed to automatically dim 5 minutes after returning to the home screen and without any activity The screen will wake...

Страница 26: ...sable the shunt trip 2 test Press to end test Reset the transfer switch circuit breaker SHUNT 1 2 Use arrows to enable the shunt trip 1 test Press to begin test The normal fire pump circuit breaker sh...

Страница 27: ...ABOUT Information is shown for Model Number Serial Number Software Part Number Build Number Date and Boot Code Part Number Version Information and Checksum Information About 22...

Отзывы: