  4.  Observe direction of motor rotation.
  5.  If rotation is incorrect, con

fi

 rm that the isolating switch/circuit breaker is in the OFF position, 

open enclosure door and reverse any two of the corresponding motor leads (T1, T2, T3, T6/T12, 
T4/T10, T5/T11) on the load side of both contactors 1M and 2M.  For example, reverse T1 and 
T2 on contactor 1M and T6/T12 and T4/T10 on contactor 2M; or T1 and T3 on contactor 1M and 
T6/T12 and T5/T11 on contactor 2M; or T2 and T3 on contactor 1M and T4/T10 and T5/T11 on 
contactor 2M.

  6.  Retest for proper rotation following steps 1 through 4.

FTA1930 Controllers

  1.  Close enclosure door.

  2.  Momentarily close the isolating switch/circuit breaker handle, i.e. move up to the ON position 

and then back to OFF.

  3.  The pump motor should rotate immediately if system pressure is low.  If system pressure is not low, 

press the manual START push-button and immediately press the manual STOP push-button.

  4.  Observe direction of motor rotation.

  5.  If rotation is incorrect, con

fi

 rm that the isolating switch/circuit breaker is in the OFF position, open 

enclosure door and reverse any two of the motor leads (T1, T2, T3) on the load side of contactor 

1M.  For example, T1 and T2,  T1 and T3 or T2 and T3.

  6.  Retest for proper rotation following steps 1 through 4

FTA900, 975 POWER TRANSFER SWITCH

  1.  Con

fi

 rm motor rotation from the normal power source for the controller as outlined above.

  2.  Open both the controller isolating disconnect switch/circuit breaker and the transfer switch iso-

lating disconnect switch by moving the operating handles to the OFF position.

  3.  Refer to the Automatic Transfer Switch Operator’s Manual.  Manually transfer the switch  to  the 

emergency power source.

  4.  Start the generator set at the generator control panel.

  5.  With the generator running at stable voltage and frequency momentarily close the power transfer 

switch isolating disconnect switch.  The pump motor should rotate immediately if system pres-

sure is low.  If system pressure is not low, press the manual START push-button and immediately 

press the manual STOP push-button.

  6.  Observe motor rotation.  Con

fi

 rm that the isolating switch is in the OFF position.  Shutdown 

generator set.

  7.  If rotation is incorrect, reverse any two of the line leads at the power transfer switch isolating 

disconnect switch (L1, L2, L3).  For example, L1 and L2, or L2 and L3, or L1 and L3.

  8.  Retest for proper rotation following steps 1 through 6.

FTA950, 976 POWER TRANSFER SWITCH

  1.  Con

fi

 rm motor rotation from the normal power source for the controller as outlined above.

  2.  Open both the controller and transfer switch isolating disconnect/circuit breakers by moving the 

operating handles to the OFF position.

  3.  Refer to the Automatic Transfer Switch Operator’s Manual.  Manually transfer the switch  to  the 

emergency power source.

  4.  Momentarily close the power transfer switch isolating disconnect switch/circuit breaker.   

The pump motor should rotate immediately if system pressure is low.  If system pressure is not low, 

press the manual START push-button and immediately press the manual STOP push-button.

  5.  Observe motor rotation.

  6.  If rotation is incorrect, con

fi

 rm that the isolating disconnect switch/circuit breakers are in  

the OFF position.  Request the utility company to disconnect the second utility incoming  

power at the source, then reverse any two of the line leads at the power transfer switch isolating 

disconnect switch (L1, L2, L3).  For example, L1 and L2, L1 and L3, or L2 and L3.

  7. Retest for proper rotation following steps 1 through 5 above.

6

Содержание Emerson Mark IIXG

Страница 1: ...Installation and Operation Instructions Mark IIXG Electric Fire Pump Controllers NS1000 50 A ECN 237793...

Страница 2: ...50 1000 1500 1800 2000 2400 5 FTA1250 5 FTA1300 1350 5 6 FTA1930 6 FTA900 975 Transfer Switch 6 FTA950 976 Transfer Switch 6 INITIAL START UP OPERATION 7 MANUAL START 7 EMERGENCY RUN START 7 ABBREVIAT...

Страница 3: ...Units 14 Start 14 Stop 14 Automatic Shutdown Disabled 14 Overpressure Alarm 14 Recording Delta Hourly 14 Sensor 14 Calibration 14 Reset to Defaults 14 Motor Power System Volts 14 Phase Sequence 15 Fr...

Страница 4: ...ttings Interlock Alarm 17 Low Pressure Audible 17 Low Suction 17 Pump Run Alarm 17 User Input 17 Weekly Test 17 18 Option Settings 18 MAIN MENU EVENT LOG 18 MAIN MENU DATA HISTORY 18 MAIN MENU USB Sav...

Страница 5: ...n 20 Diagnostics Raw Input Analog 20 Raw Input Discrete 20 Raw Input Keys 20 Raw Output Discrete 20 Mark IIXG Starts 20 Lamp Test 20 Audible Test 21 USB Test 21 Phase Fail 21 Phase Reverse 21 Shunt 1...

Страница 6: ...ary Resistance Reduced Voltage Starting Closed Circuit Transition FTA1800 Autotransformer Reduced Voltage Starting Closed Circuit Transition FTA1930 Digital Soft Starting FTA2000 High Voltage Starting...

Страница 7: ...nting 5 Using either the dimension print or by measuring the distance between the center lines of the lower bracket slots transcribe this dimension onto the wall Note The bottom edge of the en closure...

Страница 8: ...e 2 Verify that the controller information is what is required on the project Firetrol catalog number Motor voltage and horsepower Incoming line voltage and frequency Maximum system pressure 3 Project...

Страница 9: ...wnonfieldconnection diagram 4 If a deluge valve is used remove the factory installed jumper from terminals as shown on field connection diagram Connect wires from the normally closed contact on the de...

Страница 10: ...press the manual STOP push button 4 Observe direction of motor rotation 5 Ifrotationisincorrect confirmthattheisolatingswitch circuitbreakerisintheOFFposition open enclosure door and reverse any two o...

Страница 11: ...to the emergency power source 4 Start the generator set at the generator control panel 5 Withthegeneratorrunningatstablevoltageandfrequencymomentarilyclosethepowertransfer switch isolating disconnect...

Страница 12: ...d continue to run It will not stopautomatically Therunningperiodtimerandpressureswitchhavenocontroloverthismanual operation 3 To stop press the STOP push button 4 Starting from a remote START push but...

Страница 13: ...structions 2 MOTOR ACCELERATION timer is factory set for 2 seconds and may be field adjusted if necessary See Mark IIXG Programming for details CAUTION DO NOT EXCEED FOUR 4 SECONDS MAXIMUM 3 Contactor...

Страница 14: ...7 26 Mark IIXG User Interface and Display 1 2 4 3 5 6 Informational Display Control Status and System Pressure Frequency Phase Rotation Phases Line Voltage Phase Motor Current Phase Active Alarms Prim...

Страница 15: ...Interlock Alarm Low Press Aud Low Suction Pump Run User Input Weekly Test Event Log Event History Data History Calls to Start Starts Pump Total Run Time Last Pump Run Time Controller Power On Time La...

Страница 16: ...on These options are indicated by a for enabled or a x for disabled In many cases this can also be interpreted as for yes or a x for no 1 Indicates the level of password required to modify a setting 1...

Страница 17: ...i bar kPa Press to confirm Note Many menu settings feature an enable disable option These options are indicated by a for enabled or a x for disabled 1 Indicates the level of password required to modif...

Страница 18: ...S TIMERS ON DELAY 1 Use arrows to set preferred on delay time Press to confirm Note On Delay also known as sequential start time delays the starting of the motor when an automatic call to start is rec...

Страница 19: ...CALIBRATION SET TO ZERO 2 Use arrows to set zero calibration value Press to confirm SET TO SPAN Use arrows to set span calibration value Press to confirm Note Remove interlock jumper wire when calibra...

Страница 20: ...el at the beginning of the deceleration ramp DECEL PAUSE LEVEL 3 Use to set the Deceleration Pause Level 32 60 FLA Press to confirm The starter will reduce current to set level at the beginning of the...

Страница 21: ...se arrows to set the frequency limit for the Under frequency Alarm Press to confirm Use arrows to enable or disable the Under frequency Alarm Press to confirm Use arrows to set the frequency limit for...

Страница 22: ...to confirm 1 ON DELAY Use arrows to select an on delay time before the alarm is acknowledged 0 99 seconds Press to confirm 1 AUDIBLE Use arrows to select if the user input activates the audible alarm...

Страница 23: ...s to start Number of actual starts Pump total run time Pump last run time Total controller power on time Last pump start time date Minimum system pressure Maximum system pressure Last phase failure La...

Страница 24: ...confirm NOTE This is a factory set parameter and under normal circumstances would never be changed 3 MODEL Use arrows to select required model number Press to confirm NOTE This is a factory set parame...

Страница 25: ...disable the screen saver function Press to confirm NOTE The display screen is designed to automatically dim 5 minutes after returning to the home screen and without any activity The screen will wake...

Страница 26: ...sable the shunt trip 2 test Press to end test Reset the transfer switch circuit breaker SHUNT 1 2 Use arrows to enable the shunt trip 1 test Press to begin test The normal fire pump circuit breaker sh...

Страница 27: ...ABOUT Information is shown for Model Number Serial Number Software Part Number Build Number Date and Boot Code Part Number Version Information and Checksum Information About 22...

Отзывы: