SETTINGS
OPTION SETTINGS
NOTE:
The list of available options and the settings associated with them will vary with each controller. Below are the
most common user de
fi
ned settings that may appear.
1
AUDIBLE
Use arrows to enable or disable the audible alarm for selected option. Press to con
fi
rm.
1
COMMON ALARM
Use arrows to enable or disable the common alarm output for selected option.
Press to con
fi
rm.
1
DELAY
Use arrows to set the “on” delay time for selected option. Press to con
fi
rm.
EVENT LOG
The Event Log is a record of events (pressure recording, alarms, starts, etc...) that are stored in the memory of the
Mark II
XG
. The last 3000 events are kept in this memory. The events are stored in the order that they occur, with the
most recent being “
fi
rst” (the last event that occurred will be event #1). The following keys are used to browse through
the event log:
Move forward through the events one at a time (1 - 2 - 3....etc)
Move backward through the events one at a time (55 - 54 - 53....etc)
Move forward through the events ten at a time (60 - 70 - 80....etc)
Move backward through the events ten at a time (91 - 81 - 71....etc)
Pressing and holding of the arrow keys will allow the scrolling to move faster.
DATA HISTORY
The Data History is a record of important data and events that are kept throughout the life of the controller.
Use arrows to scroll through the information stored in the Data History log. The available information is:
Numbers of calls to start • Number of actual starts • Pump total run time • Pump last run time • Total controller
power on time • Last pump start time/date • Minimum system pressure • Maximum system pressure • Last phase
failure • Last phase reversal • Last locked rotor trip • Last locked rotor currents • Frequency minimum • Frequency
maximum • Maximum starting currents • Maximum run currents • Minimum voltage/phase while idle (not running)
• Maximum voltage/phase while idle (not running) • Minimum voltage/phase during start • Minimum voltage/phase
during run • Maximum voltage/phase during run
1
NOW IN WEEK
Use arrows to choose current time frame in reference to the Weekly Test schedule. Press to con
fi
rm.
(Example: If test is programmed for every 2 weeks on Sunday and today were Friday then - If testing is desired to start
this week, then every other week thereafter, we would now be in week 2 of 2 - If testing is desired to start on the fol-
lowing Sunday, not the coming Sunday, then we would now be in week 1 of 2).
Option Settings
Event Log
Data History
USB
USB
1
SAVE TO USB
Use arrows to enable or disable the Save to USB function. Press to con
fi
rm.
The following is saved to the USB
fl
ash drive: Event Log, Data History, Controller Information and all user de
fi
ned
settings (pressure settings, timer settings, alarm settings....etc.). The saved
fi
le is a text
fi
le named the same as the
controller serial number (87654321.txt) and can be viewed using most word processing software.
Note: Use of a
fl
ash drive larger than 1GB may result in excessively long read/write operations. If a
fl
ash drive larger
than 1GB must be used, create a 1GB or less partition on that drive.
18