Man-1556 Rev.02
FPC-2V2 Fire Extinguishant Controller Operation and Installation Manual
Page 10 of 18
4. Testing and Commissioning
Before applying power to the FPC-2V2 panel,
FirePro
Condensed Aerosol
Generators
must be physically isolated from the system by disconnecting both
wires to it. This will prevent any accidental release of extinguishant.
With all FirePro Condensed Aerosol generators disconnected from the FPC-2V2 panel,
ensure that the test lamps that are supplied with the unit are fitted to terminals FirePro
GEN1, FirePro GEN2, FirePro GEN3 and FirePro GEN4
When power is applied and all connections are correct, only the green “Power On” LED
should be lit. If any fault indicators are lit the wiring to the appropriate input or output
should be checked and all faults have been cleared before proceeding.
Figure 9 – Unit front frame
IMPORTANT
DISCONNECT ALL
FirePro
CONDENSED AEROSOL GENERATORS
BEFORE TESTING.
IMPORTANT
DO NOT LEAVE ANY FirePro CONDENSED AEROSOL
GENERATORS CONNECTED TO THE UNIT WHEN TESTING AS
THESE
FirePro
GENERATORS WILL ACTIVATE.