Man-1556 Rev.02
FPC-2V2 Fire Extinguishant Controller Operation and Installation Manual
Page 16 of 18
6. Specifications
Mains supply
24V DC +10% - 15%
Maximum current
1.6 Amps
Fuse rating
1.6 Amps (Quick Blow)
Operating voltage
19-30VDC
Output voltage
19-30VDC +/- 2%
Standby current
18 milliamps
Extinguishant release output
19-30VDC, Fused at 1.6 Amp
Extinguishant release
Immediate – Max 4 FirePro
Condensed
Aerosol Generators
Extinguishant release duration Latched - Continuous
Detection Type
Conventional Smoke or Heat Detectors – Max of
2 Detectors, can be mixed.
Linear Heat Detection Cable - Latching Type NO
– LHD Cable Max 30m.
Detection Circuit End of Line
6K8 5% ½ Watt resistor
Fault monitoring
Detection and actuator circuits (open circuit
monitored only)
Fault relay contact rating
30VDC 1A Amp max
Fire relay contact rating
30VDC 1A Amp max
Cable entries
8 X 21mm knockouts
Terminal capacity
0.52mm to 2.52mm solid or stranded wire
Overall size
190mm x 136.5mm x 43mm
Construction
1/2mm sheet steel
Finish
Epoxy powder coat
Colour
BS OO A 05 light grey textured
Panel environmental class
Class A and is designed for indoor use only
Operating temperatures
-5oC (+/- 3) and +40oC (+/- 2)
Maximum relative humidity
95%