Man-1556 Rev.02
FPC-2V2 Fire Extinguishant Controller Operation and Installation Manual
Page 7 of 18
Figure 4- Connection to linear heat detection cable
Figure 5- Connection to smoke detectors
3.3
FirePro Condensed Aerosol Generators connection terminals
These terminals (“FIREPRO GEN1” to “FIREPRO GEN4”) are for the connection of
FirePro
Condensed Aerosol Generators. Test lamps are provided in the terminals to allow testing
of the system before connecting the
FirePro
Condensed Aerosol Generators
. These test
lamps should be removed from the terminals if a
FirePro
Condensed
Aerosol Generator is
to be fitted.
Any
FirePro
generator outputs that are not being used should be left with test lamps
fitted.