I
NSTALLATION
(C
ONTINUED
)
P
AGE
15
be used. Follow the manufacturer's instructions for the use of flashing and an adjustable storm collar
at the roof line to prevent water from entering the house. Manufacturers require that chimneys
extending beyond a certain height above the roof (frequently above 5') must also be braced.
Using Offsets
•
30° Elbows may be used to offset the chimney (to
align the chimney or gain clearance to combustibles
•
A maximum four 30° elbows may be used
•
Each elbow must be used in conjunction with a
return elbow (so the chimney returns to a vertical
direction)
•
If using a single offset (two 30° elbows) a
maximum of 8' of inclined chimney may be used
between elbows.
•
If using two offsets (four 30° elbows) a maximum
of 4' of inclined chimney may be used between
each set of elbows.
•
For every 6' of inclined chimney a flue support is
required
•
Elbows may be used directly off the top of the
fireplace (maintain a 5" clearance to combustibles
on the back wall, 4 1/2" minimum on the front wall
and header, and 18" minimum to the side walls)
•
The table below details the amount of offset ("X")
and rise ("R") gained from various chimney
lengths when used with 30° elbows. Make sure to
add the amounts for both elbows. Two sections
may be added together to form a combined length.
For example, 12" and 18" Temco chimney sections
give an offset of 17-5/8" (3-7/8" + 5-3/8" + 8-3/8"
= 17-5/8"). The rise ("R") equals 38-1/8" (14-3/8"
+ 9-1/4" + 14-1/2" = 38-1/8").
X
R
Max. of 30
degrees
4' Max.
Chimney must be totally
enclosed when passing
through living space with a
minimum 2" clearance to
combustibles.
Firestop
Firestop
2"
Min.
Cooling Vents
Temco 82 Series
Superior TF8
FMI 8DM
Marco 8D
M E A S U R E D
OFFSET
RISE
OFFSET
RISE
OFFSET
RISE
OFFSET
RISE
IN INCHES
"X"
"R"
"X"
"R"
"X"
"R"
"X"
"R"
2 Elbows
3 7/8
14 3/8
4
15
4 3/8
16 3/8
5 1/4
19 1/4
12" Section
5 3/8
9 1/4
5 1/4
9
5 3/8
9 1/8
5 1/4
9
18" Section
8 3/8
14 1/2
8 1/4
14 1/4
8 3/8
14 3/8
8 1/4
14 1/2
24" Section
11 3/8
19 5/8
---
---
---
---
---
---
36" Section
17 3/8
30
17 1/4
30
17 3/8
29 7/8
17 1/4
30 1/4
48" Section
23 3/8
40 3/8
23 1/4
40 1/4
23 3/8
40 1/4
23 1/4
40 1/2
Flue Support
1 1/2
2 3/8
1 1/2
2 1/2
6 3/4
11 3/4
5 1/4
9 1/4