Forte Flush & Athena Flush AG/RURAL
-
November 2018
4
2. INSTALLATION RESPONSIBILITIES
Warning:
The Fire and Flue system must be installed in accordance with AS/NZS 2918:2001 and the
appropriate requirements of the relevant NZ Building Code or Codes. If the flue system has been
AS/NZS 2918:2001 Appendix F tested by the flue system manufacturer then their specifications for the
installation of the flue system must be adhered to.
Any modification of the Fire that has not been approved in writing by the testing authority is co
n
sidered
to be in breach of the approval granted for compliance with AS/NZS 4013.
Caution
:
Mixing of Fire or flue
-
system components from different sources or modifying the
dimensional specification of components may result in hazardous conditions. Where such action is
considered, the manufacturer should be consulted in the first instance.
Strict adherence to these instructions will meet these standards. Any variation from these installation
instructions or any doubt about them must be checked against the requirements of the standards.
Please leave this manual with the owner when installation is complete.
3. FLOOR PROTECTOR REQUIREMENTS
If the Fire is to be placed on or within 500mm of a heat sensitive floor, an
insulated
floor protector will
be required.
The insulated floor protector needs to extend under the Fire and in front of the door. See dimensions
for floor protector. Similarly a 200mm extension is required on each side of the door opening unless the
insulated floor protector forms an abutment with a wall or heat shield at a lesser distance.
The Fire and floor protector must be fixed to the floor for seismic restraint. Anchor points are provided
in the feet of the Fire.
INSULATED FLOOR PROTECTOR CONSTRUCTION
An
Insulated
Floor Protector shall be a minimum thickness of
40mm
, consisting of 20mm of an
approved
insulation material i.e. 2 sheets of 10mm Micorboard or Supalux, 10mm tile backing board
and 10mm tiles or similar on the top surface. All joints on the upper surface should be sealed to
prevent spilt ash from contacting any heat
-
sensitive material.
Содержание 102107
Страница 8: ...Forte Flush Athena Flush AG RURAL November 2018 8 ZERO CLEARANCE BOX Built in Fire Canopy ...
Страница 9: ...Forte Flush Athena Flush AG RURAL November 2018 9 ZERO CLEARANCE BOX Built in Fire Canopy ...
Страница 10: ...Forte Flush Athena Flush AG RURAL November 2018 10 ZERO CLEARANCE BOX Built in Fire Canopy ...
Страница 11: ...Forte Flush Athena Flush AG RURAL November 2018 11 ZERO CLEARANCE BOX Built in Fire Canopy ...
Страница 12: ...Forte Flush Athena Flush AG RURAL November 2018 12 ZERO CLEARANCE BOX Built in Fire Canopy ...
Страница 13: ...Forte Flush Athena Flush AG RURAL November 2018 13 ZERO CLEARANCE BOX Built in Fire Canopy ...
Страница 14: ...Forte Flush Athena Flush AG RURAL November 2018 14 ZERO CLEARANCE BOX Built in Fire Canopy ...
Страница 15: ...Forte Flush Athena Flush AG RURAL November 2018 15 ZERO CLEARANCE BOX Built in Fire Canopy ...
Страница 18: ...Forte Flush Athena Flush AG RURAL November 2018 18 ...
Страница 19: ...Forte Flush Athena Flush AG RURAL November 2018 19 7 WETBACK ...
Страница 21: ...Forte Flush Athena Flush AG RURAL November 2018 21 ...