AnF Enclosures
REV. 8-29-18 Page 13
Step 5
After the entire AnF is assembled, install the Vent-Kit-6x12. These vents are designed to be used
with the AnF Series as well as universal vents for many other types of fi re pit enclosures. Look at the
contents provided to ensure you have received everything correctly.
Install the vents on opposite sides of
the enclosure to ensure cross fl ow
ventilation. Cross fl ow ventilation is
necessary to provide free fl owing air to
assist in keeping the enclosure dry and
cool during operation of a fi re pit.
Cut an rectangular opening 9.75”w x
3.75”h into on opposite sides of the
enclosure. Center the vent over the cut
out area ensuring the vent slots are
clear of any obstruction. Mark the holes
with a pencil or marker. Drill six 1⁄4”
pilot holes, position the vent centered
over the opening, insert a screw into
the vent and enclosure at the same
time and secure with washer and nut
on the inside. Repeat the process until
all six screws are securing each vent
into place on both sides of the AnF
enclosure (See Fig. 31).
9.750”
3.750”
CUT OUT DETAIL
Fig. 31
Vent Cut Out Dimensions
(2) Vents
(12) Phillips Black
Pan Head Screw
(12) Stainless Steel
Nut
(2) Stainless Steel
Flat Washer
NOTE:
Before cutting the rectangular
opening for your vents, be sure that
you are not hitting one of the metal
studs inside the AnF. The vents must be
directly across from each other.