2.5 Component Module Descriptions

FireClass Fire detection system FireClass Panels

12

Product Information and Design Application

 

Doc. version 1.0

2.4.6

PMM800 Power Monitoring 
Module

Input
– The 230

 

V AC mains supply is connected to the 

input of the power supply unit (BAQ60T24). The 
28.6

 

VDC output from the power supply unit is fed to 

the input of the PMM800.

Output

Table

 

7 shows the 3 DC output rails voltage ranges:

The PMM800 provides four 24

 

V outputs. Each output is 

fitted with fuse. These are F1AL 250VAC 20x5mm fast 
blow glass fuses.
There is a battery fuse fitted. This is a T8AH 250VAC 
20x5

 

mm ceramic anti-surge fuse.

2.4.7

Siting Considerations

The fastenings are not included in the kit, so they will need 
to be externally sourced. When specifying the fastenings 

(such as the screw size), take into account the type of wall 
and the weight of the assembled housing. The size of the 
batteries will have a large bearing on the weight of the units 
(see 2.4 “Collected Specifications” on page

 11).

The control panel is designed for wall mounting. Typically 
screws and rawlplugs in drilled holes will be used. The 
screw hole positions are shown in Fig. 1: “Overall and Fixing 
Dimensions – FireClass Lite” on page

 7 

.

2.4.8

Environmental Stipulations

The control panel is not weatherproof. Check that the loca-
tion is indoors, dry and free from excessive dust. Also check 
that location fulfils the temperature and humidity stipula-
tions shown in Table 8: “Temperature and Humidity Stipu-
lations”.

2.4.9

EMC

Product family standard EN50130-4 in respect of Con-
ducted Disturbances, Radiated Immunity, Electrostatic Dis-
charge, Fast Transients and Slow High Energy
EN 61000-6-3 for Emissions.

2.5

Component Module 
Descriptions

The following sections detail the standard modules fitted to 
an FireClass Lite control panel or repeater.

2.5.1

Central Processing Unit

The Central Processing Unit (CPU800 board) contains the 
main processor and memory. It is mounted to the FIM801 
Lite board.

2.5.2

Field Interface Module (FIM)

The FIM801 Lite provides all the inputs and outputs of the 
control panel. Refer to Fig

 

4 for FIM Board connections.

Rail

Voltage Range

28

 

V

Vout(max)=28.6

 

V (Tamb=—10C, Iout=0).

Vout(min)=20

 V(Tamb=50

 C), 

Iout=2.5

 A 

(BAQ60T24).

Output ripple: 150

 

mV p-p maximum at maxi-

mum load
BAQ60T24: 0-2.5

 A, 

Imaxb=2.5

 A, 

Imaxa=1.9

 

A (12A-h Battery charging at C/20 

rate)
Maximum current available on the 28

 V 

rail 

(I(28)) in either condition, may be calculated from 
the following formula:-
I(28)=I(max)-0.211*I(5)-1.568*I(40)
Where:
I(max)=Imaxa or Imaxb i.e. whichever is being 
considered
I(5)=Current drawn from 5

 V 

rail

I(40)=Current drawn from 40

 V 

rail

5

  V

Output voltage: 4.85

 V-5.25

 

V @ 50m

 A 

to 

1.5

 

A. Minimum load=50

 mA.

Output ripple: 150

 

mV p-p maximum.

40

 

V

Output voltage: 39.75

 V-40.2

 

V @ 0 to 1.25

 A.

Output ripple: <40

 

mV p-p 1-10

 KHz 

acceptable 

level increasing 6

 

dB/octave either side.

Table 7: PMM800 Output Rail Voltage Ranges

Parameter

Value

Operating Temperature

-5°C to +40°C

Storage Temperature

-20°C to +70°C

Operating and storage 
maximum Relative  
Humidity

95% RH non-condensing

Table 8: Temperature and Humidity Stipulations

 

Содержание Lite 1.0

Страница 1: ...Product Information and Design Application 120 515 093 Doc version 1 0 25 April 2012 FireClass Lite FireClass Addressable Fire Alarm Control Panels version 1 0...

Страница 2: ...re reserved in particular but not limited to the rights of copying distribution and translation No portion of this documentation including the online help may be reproduced edited copied or distribute...

Страница 3: ...iption Panel and Repeater 6 2 2 FireClass Lite Express 6 2 2 1 FIM Connection Details 10 2 3 Summary 11 2 4 Collected Specifications 11 2 4 1 Shock Vibration 11 2 4 2 Dimensions 11 2 4 3 Colour 11 2 4...

Страница 4: ...Contents FireClassFiredetectionsystemFireClassPanels 4 Product Information and Design Application Doc version 1 0...

Страница 5: ...aining on FireClass based systems is recom mended 1 5 Reference Documents For further information see the following documents that comprise the FireClass main user documentation set Installation and C...

Страница 6: ...s Product Information and Design Application guide A 2 5 A power supply unit is fitted as standard It supports 7 Repeaters It has a 32 zone LED display The Autoconfiguration feature restricts the numb...

Страница 7: ...ss Product Information and Design Application Doc version 1 0 7 Fig 1 Overall and Fixing Dimensions FireClass Lite 1 Knockouts 20 mm 26x 2 Knockout 25 mm 3 Knockout 20 mm 4 Knockouts 5 Mounting hole 5...

Страница 8: ...e Fire Alarm Control Panel FIELD SUPPLY 24V ALARM RELAY FAULT RELAY SOUNDER CIRCUIT 1 SOUNDER CIRCUIT 2 MAINS IN 24 V BATTERY FCNET REMOTE BUS REPEATER SERIAL PORT 1 PRINTER SERIAL AR AR DET DET DET I...

Страница 9: ...H RL1 RL2 RL4 RL3 T N O R F R E V OV V C N O R F FA FA A CE FB2 RV1 R R RV2 R R FB3 RL13 IC C C C C 1 C1 C C C 1 1 4 4 X3 IC22 X2 IC21 RL11 B P O O L M A R G O R P A P O O L M A R G O R P IC6 4 B F S1...

Страница 10: ...ard connections All terminals accept solid stranded conductors from 0 5 to 2 5 mm2 Fig 4 FIM801 Lite board connection the labels match those on the FIM board 1 Shown in the no alarm position 2 Shown i...

Страница 11: ...ircuits loops Points per loop Points per CIE Zones per loop Zones per panel Zone LEDs Batteries FireClass Lite 1 125 125 32 240 32 240 32 2 x 12 Ah Table 2 Numbers of loops zones and points Points can...

Страница 12: ...and Humidity Stipu lations 2 4 9 EMC Product family standard EN50130 4 in respect of Con ducted Disturbances Radiated Immunity Electrostatic Dis charge Fast Transients and Slow High Energy EN 61000 6...

Страница 13: ...be done IC field repair of the RS232 is not possible Some of the front cover connectors are not present in the FIM801 Lite board Loop expansion is not possible Network connection is not possible The...

Страница 14: ...he Internet at www fireclass co uk United Kingdom FIRECLASS Hillcrest Business Park Cinder Bank Dudley West Midlands DY2 9AP United Kingdom FireclassSales tycoint com www fireclass co uk 120 515 093_F...

Отзывы: