FireClass Fire detection system FireClass Panels
2.3 Summary
Product Information and Design Application
Doc. version 1.0
11
2.3
Summary
The FireClass Lite panel details are summarized as below:
2.4
Collected Specifications
2.4.1
Shock/Vibration
The shock vibration resistance meets EN54-2.
2.4.2
Dimensions
Table
3 shows the following dimensions for the FireClass
Lite panel.
2.4.3
Colour
For FireClass Lite panel, the colours are as follows:
Housing colour is RAL7035.
Control facia colour is Pantone Grey 431C.
2.4.4
Battery Details
The backup batteries are pairs of12
V SLA (sealed lead
acid) from Power Sonic.
The maximum internal resistance of the battery and its
associated circuitry is 0.35
Ohms.
Table
5 shows the maximum PSE loads.
2.4.5
PSU
Table
6 shows the mains requirements.
Values are shown as default/maximum
Panel
Number of
addressable
circuits
(loops)
Points *
per loop
Points
per CIE
Zones per
loop
Zones per
panel
Zone
LEDs
Batteries
FireClass Lite
1
125
125
32/240
32/240
32
2 x 12
Ah
Table 2: Numbers of loops, zones and points
* Points can be any combination of detectors, call-points, addressable ancillaries and addressable sounders.
Panel
Height (mm)
Width (mm)
Depth (mm)*
Weight (Kg)**
Input Current***
FireClass Lite
370
325
126
7
0.9
A
Table 3: Dimensions
* To the wall add 4_mm – see the dimension drawings
** Excluding batteries
*** With no power supplied to optional ancillaries
Panel
Battery
Code
Capacity
(Ah)
Weight
(Kg)
FireClass Lite
PS-12120
12
3.6
Table 4: Battery Details
Panel
Imaxa: Ipse
Imaxb: Ipse
FireClass Lite
1.9
A
2.5
A
Table 5: Maximum PSE Loads
Item
Unit
Type
Value
Current
FireClass Lite
2.5
A
and
1xPMM800
0.9
A
Voltage
FireClass Lite
2.5
A
and
1xPMM800
230
V
50/60
Hz
Table 6: Mains Power Requirements
Reference Document
For additional details on Addressable loop
Cabling considerations, Wiring configurations
Termination and Loop loading calculations, refer
to FireClass Designer Help file.