Installation Instruction
MAGPRO-WSS23 is
а
n addressable Wall Mount Sounder and Strobe (Flash) designed for installing in addressable fire alarm systems supporting
MAGPRO communication protocol. The device is powered on from the panel and can be controlled via the communication protocol.
The device MAGPRO-WSS23 is compatible with fire base MAGPRO-DB
for ceiling or wall mounting and WSB IP65 for wall mounting
.
Attention
:
Power off the loop circuit
before installing the MAGPRO-WSS23 addressable fire base
!
1. Choose the proper place for installation of the device
.
2. Set the device address
using
MAGPRO-PROG
Programmer.
The address must be in the range from
1
to
250.
3. Mount the fire base
on the ceiling or on the wall of the protected premises using fixings
according the mounting surface.
4. Connect the base
to the fire panel using the wiring diagram.
5. Insert the sounder into the base
and rotate clockwise until it drops into place - the short mark on the base fits with that on the sounder body.
Continue to rotate the sounder until its mark coincides with the long mark on the base - a click is heard.
6. Program the device parameters.
Choose in consecutiveness from the control panel:
System - Programming - Devices - Loop.
Find the installed
sounder, as enter address, loop and zone number - the panel automatically will recognize the type of the device. Choose the button
MORE
to enter
in the additional settings menu.
7. Test the sounder and strobe for proper operation.
TECHNICAL SPECIFICATIONS
!
A-weighted sound level diagram
9
1dB
97dB
96dB
89dB
87dB
1m
88dB
15°
45°
75°
105°
135°
165°
EN54-3:2001
EN54-3:2001/A1:2002
EN54-3:2001/A2:2006
EN54-23:2010
Fire alarm devices - Visual alarm device (VAD)
intended for use in and around buildings
Sounder Type: B
Coverage volume: W-2,4-6
Distributor:
Elite Security Products Ltd, Unit 7
Target Park, Shawbank Road
Lakeside,
Redditch B98 8YN, UK
http://www.espuk.com
Manufacturer:
Teletek Electronics JSC
14A Srebarna Str, 1407 Sofia, Bulgaria
http://www.teletek-electronics.com
DoP No: 032
1293-CPR-0461 Rev.1
1293
17
-10°C
÷
+5
0
°C
Installation
~183
g
Indoor*
!
Outdoor**
Essential characteristics
Performance under fire
conditions
Operational reliability
Duration of operation
Provision for external
conductors
Flammability of materials
Enclosure protection
Access
Manufacturer’s adjustments
On-site adjustments of
behavior
Requirements for software
controlled devices
Coverage volume
Variation of light output
Min. and max. light intensity
Light color
Light temporal pattern/
frequency of flashing
Marking and data
Synchronization
Temperature resistance
Humidity resistance
Corrosion resistance
Resistance to ingress
Electrical stability
Shock and vibration
resistance
Durability:
Performance
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
White
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
18020265
; RevB; 01/2018
Visual Alarm Device
(VAD) - EN54-23
Operating Voltage Range . . . . . . . . . . . . . . . . . . 15
-
3
2VDC
(Nom. 27VDC)
Nominal consumption (stand-by) . . . . . . . . . . . .
<500
μ
А@27
VDC
Maximal consumption (main tone type 27)
:
-
low volume level, sound only . . . . . . . . . . . .
<
5m
А
-
low volume level, sound and strobe. . . . . . .
<12
m
А
- high volume level
,
sound only . . . . . . . . . . .
<
16.5m
А
- high volume level
,
sound and strobe . . . . . .
<22
m
А
Maximal consumption (other tone types):
-
low volume level, sound only . . . . . . . . . . . .
<4
m
А
-
low volume level, sound and strobe. . . . . . .
<11
m
А
- high volume level
,
sound only . . . . . . . . . . .
<10
m
А
- high volume level
,
sound and strobe . . . . . .
<16
.
5
m
А
Power volume (main tone type 27)
:
- low volume . . . . . . . . . . . . . . . . . . . . . . . . . . ~ 80dB
(A)
±
6dB @ 1m
- high volume . . . . . . . . . . . . . . . . . . . . . . . . . ~ 92dB
(A)
± 5
dB @ 1m
Power volume (other tone types)
:
-
low volume . . . . . . . . . . . . . . . . . . . . . . . . . . 75-85dB
±
3dB @ 1m
- high volume . . . . . . . . . . . . . . . . . . . . . . . . . 80-95dB
±
3dB @ 1m
Number of tone types . . . . . . . . . . . . . . . . . . . . .
32
Supported communication protocol. . . . . . . . . . . MAGPRO
2
Wire Gauge for terminals . . . . . . . . . . . . . . . . . . 2.5mm
Relative humidity resistance
. . . . . . . . . . . . . . . .
(93
± 3)%
@
40°
C
Color . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . white transparent
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SAN
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116x55mm
MAGPRO-WSS23
Intelligent analogue addressable
fire alarm sounder
and strobe
ATTENTION: Read carefully this installation
Instructions before installing the device!
This manual is subject to change without notice
!
IP43C (ЕN54-3)*
IP65 (EN60529)**
* When used with base MAGPRO-DB
** When used with base WSB IP65