2 Control Panel and Associated Housing

FireClass Fire detection system FireClass Panels

6

Product Information and Design Application

 

Doc. version 1.0

2

Control Panel and Associated Housing

2.1

Key Functions and Features

2.1.1

General Description-Panel and 
Repeater

The FireClass Lite supports only repeaters on RBUS and 
does not support other RBUS ancillaries. 

The FireClass Lite is limited in firmware to support 125 
addressable devices on 1 loop (Loop expansion is not 
supported).

The FireClass Lite control panel dimensions and screw-
hole positions are as shown in Fig.

 1.

The Field Interface Board use in the panel is the FIM801 
Lite which is a partially populated version of the 
FIM801 used in other FireClass addressable fire alarm 
panels. (See Fig.

 3).

Investigate Delay and Day/Night mode LED functions 
are available. 
For additional details, refer to ‘Operator Functions’ in 
the FireClass Addressable Panels Product Information 
and Design Application guide.

A 2.5

 

A power supply unit is fitted as standard.

It supports 7 Repeaters.

It has a 32 zone, LED display.

The Autoconfiguration feature restricts the number of 
addressable devices on the loop to 125.

It is a stand-alone (non-networkable) version only.

2.2

FireClass Lite Express

It is a new template to support FireClass Lite. It is included 
in the FireClass Express installer. The FireClass Lite Express 
displays the below features:

The FireClass Lite Express supports 32 zones.

The FireClass Lite Express provides access to all 250 
loop addresses, but only 125 may be used. This may 
not include 125 devices if multiple addresses are used 
per device.

It has a maximum power supply unit of 2.5

 A.

It does not have any network support.

It has the same cause and effect mappings between the 
input and output states as applicable to other panels.

FireClass Lite Express 

FireClass Lite panels support only the Lite tem-
plate. Attempting to download any other tem-
plate will result in download failure and the mes-
sage is displayed as 

Incompatible Con-

figuration

.

Содержание Lite 1.0

Страница 1: ...Product Information and Design Application 120 515 093 Doc version 1 0 25 April 2012 FireClass Lite FireClass Addressable Fire Alarm Control Panels version 1 0...

Страница 2: ...re reserved in particular but not limited to the rights of copying distribution and translation No portion of this documentation including the online help may be reproduced edited copied or distribute...

Страница 3: ...iption Panel and Repeater 6 2 2 FireClass Lite Express 6 2 2 1 FIM Connection Details 10 2 3 Summary 11 2 4 Collected Specifications 11 2 4 1 Shock Vibration 11 2 4 2 Dimensions 11 2 4 3 Colour 11 2 4...

Страница 4: ...Contents FireClassFiredetectionsystemFireClassPanels 4 Product Information and Design Application Doc version 1 0...

Страница 5: ...aining on FireClass based systems is recom mended 1 5 Reference Documents For further information see the following documents that comprise the FireClass main user documentation set Installation and C...

Страница 6: ...s Product Information and Design Application guide A 2 5 A power supply unit is fitted as standard It supports 7 Repeaters It has a 32 zone LED display The Autoconfiguration feature restricts the numb...

Страница 7: ...ss Product Information and Design Application Doc version 1 0 7 Fig 1 Overall and Fixing Dimensions FireClass Lite 1 Knockouts 20 mm 26x 2 Knockout 25 mm 3 Knockout 20 mm 4 Knockouts 5 Mounting hole 5...

Страница 8: ...e Fire Alarm Control Panel FIELD SUPPLY 24V ALARM RELAY FAULT RELAY SOUNDER CIRCUIT 1 SOUNDER CIRCUIT 2 MAINS IN 24 V BATTERY FCNET REMOTE BUS REPEATER SERIAL PORT 1 PRINTER SERIAL AR AR DET DET DET I...

Страница 9: ...H RL1 RL2 RL4 RL3 T N O R F R E V OV V C N O R F FA FA A CE FB2 RV1 R R RV2 R R FB3 RL13 IC C C C C 1 C1 C C C 1 1 4 4 X3 IC22 X2 IC21 RL11 B P O O L M A R G O R P A P O O L M A R G O R P IC6 4 B F S1...

Страница 10: ...ard connections All terminals accept solid stranded conductors from 0 5 to 2 5 mm2 Fig 4 FIM801 Lite board connection the labels match those on the FIM board 1 Shown in the no alarm position 2 Shown i...

Страница 11: ...ircuits loops Points per loop Points per CIE Zones per loop Zones per panel Zone LEDs Batteries FireClass Lite 1 125 125 32 240 32 240 32 2 x 12 Ah Table 2 Numbers of loops zones and points Points can...

Страница 12: ...and Humidity Stipu lations 2 4 9 EMC Product family standard EN50130 4 in respect of Con ducted Disturbances Radiated Immunity Electrostatic Dis charge Fast Transients and Slow High Energy EN 61000 6...

Страница 13: ...be done IC field repair of the RS232 is not possible Some of the front cover connectors are not present in the FIM801 Lite board Loop expansion is not possible Network connection is not possible The...

Страница 14: ...he Internet at www fireclass co uk United Kingdom FIRECLASS Hillcrest Business Park Cinder Bank Dudley West Midlands DY2 9AP United Kingdom FireclassSales tycoint com www fireclass co uk 120 515 093_F...

Отзывы: