4

Fixing instructions Doc. version 2.0 09 February 12

FC410DDM – Universal fire and gas detector module

FireClass

WIRING AND INSTALLATION
How to connect the FC410DDM
1)

If the FC410DDM is to be loop powered, then move the header links on
J2, J3 and J4 to pins 1 and 2.

2)

All conductors to be free of earths.

3)

All wiring must conform to the applicable standards.

4)

See Figs. 3 to 7 for simplified FC410DDM wiring diagrams.

5)

For 4-20 mA gas sensors, connection of the loop and 24 V wiring is
shown in Figs. 6 and 7.
Maximum one sensor may be fitted to each circuit, both sensors must be
of the same type (sinking or sourcing).

6)

When using current sourcing 4-20 mA sensors, the 220 Ohms 1% 0.25
W current sensing resistor must be fitted to the FC410DDM terminals as
shown in Fig. 7.

7)

Verify the correct polarity of all wiring before connecting the FC410DDM
to the addressable loop wiring, 24 V supply and detector circuits.

MOUNTING THE FC410DDM TO AN FC470CV ANCILLARY COVER

+

For pre-mounted options follow the ordering information (see section
“Ordering information”).

How to mount the FC410DDM module to an FC470CV cover
1)

Assemble the FC410DDM to the FC470CV Double Gang cover, using
the four screws and washers provided.

2)

Fit the FC410DDM and terminal identification labels to the protective
cover (see Fig. 2).

3)

Fit the protective cover.

ORDERING INFORMATION

FC410DDM: Universal fire and gas detector module (PCB)
FC470CV:

Double-Gang cover

RECYCLING INFORMATION

Customers are recommended to dispose of their used equipments (panels,
detectors, sirens, and other devices) in an environmentally sound manner.
Potential methods include reuse of parts or whole products and recycling of
products, components, and/or materials.

WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT (WEEE)
DIRECTIVE

In the European Union, this label indicates that this product
should NOT be disposed of with household waste. It should
be deposited at an appropriate facility to enable recovery and
recycling.

The manufacturer reserves the right to change the technical specifications
of this product without prior notice.

Содержание FC410DDM

Страница 1: ...4 V bei 20 mA Bezogen auf 0 V Pegel bei stromliefernden Meldern Bezogen auf 22 V Pegel bei stromsenkenden Meldern FC Ringleitungs Spannung max 40 V DC bei externer oder interner Energieversorgung min...

Страница 2: ...iefernd sein 6 Bei Verwendung der 4 20 mA stromliefernden Melder muss der Endwiderstand 220 Ohm 1 0 25 W an das FC410DDM angeschlossen werden siehe Abbildung 7 7 Pr fen Sie auf richtige Polarit t alle...

Страница 3: ...DC all loop power modes except for only Series 600 detectors 21 V DC external power or on Series 600 detectors on loop power External 24 V PSU Voltage 21 9 V to 29 V Battery Requirements External Pow...

Страница 4: ...M TO AN FC470CV ANCILLARY COVER For pre mounted options follow the ordering information see section Ordering information How to mount the FC410DDM module to an FC470CV cover 1 Assemble the FC410DDM to...

Страница 5: ...rrente Tensione del Loop Fire Class Tensione massima Loop 40 Vcc Tensione minima Loop 28 Vcc per tutti i modi di alimentazionedel loop ad eccezione dei rilevatori serie 600 21 Vcc alimentazione estern...

Страница 6: ...cavi prima di collegare il FC410DDMal loopindirizzabile circuiti rilevatorie alimentazione24 V INSTALLAZIONEDELFC410DDMNELCOPERCHIOACCESSORIOFC470CV Per gli accessori di montaggio seguire le informaz...

Страница 7: ...Clean Contact N O Collegamento di un contatto Allarme N A A A B B 10 11 12 13 Fig 6 Anschluss eines stromsenkenden Melders 4 20 mA nur eine Meldelinie dargestellt Connection of a 4 20 mA current sink...

Страница 8: ...r Brandmelde und Feueralarmanlagen f r Geb ude Short circuit isolator and input output device for use in fire detection and alarm systems Isolatore di corto circuito e modulo Ingresso Uscita per uso...

Отзывы: