Ademco Contact ID Format Event Code Descriptions
Ademco Contact ID Format Event Code Descriptions
DACT-UD PN 51899:B1 1/25/05
47
APPENDIX B
Ademco Contact ID Format
Event Code Descriptions
This appendix describes the various Event Codes and their messages which are available for the
Ademco Contact ID Format.
The reporting structure for the Ademco Contact ID Format is as follows:
SSS 18 QXYZ GG CCC
where
SSSS = Four digit Subscriber ID Account Code
18
= Identifies transmission as Contact ID to the receiver at the Central Station
Q
= Event Qualifier where 1 = New Event and 3 = New Restore
XYZ
= Event code (shown in Table 3.4 )
GG
= Group number
CCC
= Zone number
Notes:
1. GG Group Number is fixed at '00' and cannot be changed.
2. CCC for Zone or Point Number :
Zone Number is transmitted as '001' for zone 1 up to '099' for zone 99
Point Number is transmitted as ‘001’ for point 1 to ‘636’ for point 636
Ademco Contact ID Reporting Structure
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble
reports in the Ademco Contact ID Reporting Structure follows:
Notes:
1.
18
, which is used in the reporting structure to identify the transmission as Contact ID, is not
printed out in the alarm and trouble report.
2.
Q
, which is the Event Qualifier for the reporting structure, is printed out in the report as an E
for New Event or R for New Restore.
Time
Date
Rcvr/Line ID
SSSS
QXYZ
GG
CCCC
11:28
03/25
11
7777
E110
00
C001 - general fire alarm on zone one
11:28
03/25
11
7777
E111
00
C002 - smoke detector alarm on zone two
11:28
03/25
11
7777
E380
00
C003 - fault on zone three
11:28
03/25
11
7777
E570
00
C009 - Zone nine disabled
11:28
03/25
11
7777
R110
00
C001 - Zone one alarm restored
11:28
03/25
11
7777
R111
00
C002 - smoke detector zone two restored
11:28
03/25
11
7777
R380
00
C003 - zone three fault restored
11:28
03/25
11
7777
R570
00
C009 - zone nine reenabled
11:28
03/25
11
7777
E158
00
C006 - high temperature, zone six
11:28
03/25
11
7777
E151
00
C007 - gas detected, zone seven