Programming the MS-9600 Fire Alarm Control Panel
Programming for DACT-UD
DACT-UD PN 51899:B1 1/25/05
31
PROCMON AR
00
00
MON-USER-DEF-17
00
00
not used
00
00
not used
00
00
POINT_FAULT
F1
D1
POINT_DISABLE
41
51
AC_FAIL
92
93
DRILL
97
98
SLC 1 OPEN FAULT
43
53
SLC 1 SHORT FAULT
44
54
SLC 2 OPEN FAULT
4B
5B
SLC 2 SHORT FAULT
4C
5C
GROUND FAULT
61
A1
LOW BATTERY
62
A2
NO_BATTERY
63
A3
TELCO LINE 1
64
A4
TELCO LINE 2
65
A5
COMM FAULT 1
6A
AA
COMM FAULT 2
6B
AB
TOTAL COMM FLT
00
00
PRINTER FAULT
6C
AC
NAC 1 FAULT
66
A6
NAC 2 FAULT
67
A7
NAC 3 FAULT
68
A8
NAC 4 FAULT
69
A9
not used
00
00
VOICE EVACUATION
00
00
ACS FAULT
6D
AD
LCD_80F FAULT
6E
AE
NAC 1 DISABLE
4B
5B
NAC 2 DISABLE
4C
5C
NAC 3 DISABLE
4D
5D
NAC 4 DISABLE
4E
5E
MEMORY FAULT
46
56
CHARGER FAULT
47
57
OPTION CARD 1 FAULT
48
58
OPTION CARD 2 FAULT
49
59
SLC 2 FAULT
4F
5F
ZONE DISABLE
42
52
NAC_KEY_FLT
4B
5B
NO_DEVICES_INSTLLD
4A
5A
OFF_NORMAL_MESSAGE
6F
AF
24_HOUR_TEST
99
00
24 HOUR ABNORMAL TES
FB
00
UPDOWN REQUEST
71
00
UPLOAD SUCCESS
72
00
DOWNLOAD SUCCESS
73
00
UPDOWN FAILURE
74
00
GENERAL_ALARM
00
00
GENERAL_SUPERVISORY
00
00
Table 3.3 Event Codes (Continued)