DACT-UD Installation
Installation in MS-9600 FACP
16
DACT-UD PN 51899:B1 1/25/05
9. Refer to "Digital Communicator" on page 10, before proceeding with this step.
Connect the premises primary and secondary phone lines to the DACT as
illustrated in Figure 2.5 and test the system for correct operation
1 2 3 4 5 6 7 8
RJ31-X
Jack
1 2 3 4 5 6 7 8
RJ31-X
Jack
J2
J3
PH1
PH2
Figure 2.5 Wiring Phone Jacks
Green Wire
Red Wire
Green Wire
Red Wire
Tip
Ring
Ring
Tip
Ring
Tip
Tip
Ring
To premise phones
To premise phones
Primary Lines
Incoming Telco Phone Lines
Secondary Lines
Incoming Telco Phone Lines
Note: Shorting bars inside RJ31X Jack
removed during male plug insertion
Primary Phone Line PH-1
Secondary Phone Line PH-1
Male Plug
Connectors
Female
Connectors
7 foot cable
(MCBL-7)
order separately
DACT-UD
CAUTION:
It is critical that the DACT-UD
be located as the first device on the incoming
telephone circuit to properly function
MS-92 00UD
Figure 2.6 DACT Installation
Customer Premises Equipment and Wiring
Telephone
Line
MS-9600 with DACT-UD
Network
Service
Provider’s
Facilities
Network
Demarcation
Point
RJ31X
Jack
Unused
RJ-11 Jack
Unused
RJ-11 Jack
Telephone
Telephone
Telephone
Answering
System
Fax Machine
Computer
It is critical that the DACT be located as the first device on the incoming telephone circuit to properly function
.