Audio Command Center Series Manual —
P/N 51889:E1 6/8/2010
111
MS-9600, MS-9200UDLS and MS-9200UD
Programmed Activation by FACP
•
if an addressable device programmed to Zone 35 is activated and no other devices are active,
the message programmed for Zone 35 will be generated over speaker circuit 3 on the ACC-
25/50ZS or ACC-25/50ZST. (Refer to Table D.5 on page 109).
•
if an addressable device (address 09 in example below) programmed to Zone 35 is activated
and a second addressable device (address 15 in example below) programmed to Zone 36 is
activated, the highest priority message programmed to either Zone 35 or Zone 36 (Message 3
in example below) will be generated over speaker circuits 3 and 4. (Table D.5 on page 109). If
an addressable device (address 21 in example below) programmed to Zone 32 is then acti-
vated, the highest priority message programmed to Zone 32, 35, or 36 (Message 1 in example
below) will be generated over all speaker circuits. (Table D.5 on page 109).
Addressable Pull Station
Programmed to
Message 3
Zone 35
activate
Speaker Circuit 3
Addressable Pull Station
(address 21)
Programmed to
Zone 32
Message 4
(lowest priority of the three)
Message 3
(2nd highest priority of the three)
Message 1
(highest priority of the three)
Addressable Pull Station
(address 09)
Zone 35
Programmed to
Zone 36
Programmed to
Addressable Pull Station
(address 15)
activate
activate
activate
Speaker Circuit 1
Speaker Circuit 2
Speaker Circuit 3
Speaker Circuit 4
Speaker Circuit 5
Speaker Circuit 6
Speaker Circuit 7
Speaker Circuit 8
Содержание ACC-25
Страница 62: ...62 Audio Command Center Series Manual P N 51889 E1 6 8 2010 Notes ...
Страница 101: ...Audio Command Center Series Manual P N 51889 E1 6 8 2010 101 Notes ...
Страница 137: ...Audio Command Center Series Manual P N 51889 E1 6 8 2010 137 Notes ...
Страница 144: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...