108
Audio Command Center Series Manual —
P/N 51889:E1 6/8/2010
Programmed Activation by FACP
MS-9600, MS-9200UDLS and MS-9200UD
D.1.4 ACC-25/50ZS and ACC-25/50ZST Switch Settings
ACC-ZPMK DIP Switch S1
•
Switches 1, 2, and 3 are used to configure the ACC-25/50ZS and ACC-25/50ZST for operation
with a specific FACP as shown in the following table:
•
Switch 4 - future use
•
Switches 5, 6, 7, and 8 - used to set the number of ACC-25/50DAZS panels installed.
ACC-ZPMK Rotary Address Switches S2 and S3
ACS Protocol:
The address switches must be set to ACS address
01
to communicate with the FACP. Any other
ACS devices which are set to address 01 should be in Receive Mode only.
•
S2=1
•
S3=0
ANN-BUS Protocol:
The address switches can be set to any address between 01 through 08 to communicate with the
FACP. Any other ANN-BUS devices must be set to a different address.
•
S2=1-8
•
S3=0
ACC-ZSM Zone Splitter Module Switch Settings
See “ACC-ZSM Zone Splitter Module (ACC-25/50ZS & ACC-25/50ZST)” on page 41 for infor-
mation on setting these switches.
ACC-FFT Fire Fighter Module Switch Setting (ACC-25/50ZST only)
See Section “SW1 - Remote Microphone Installed Switch on ACC-FFT” on page 39 for additional
information.
SWITCH
1
SWITCH
2
SWITCH
3
CONFIGURED FOR OPERATION WITH FOLLOWING FIRE ALARM
CONTROL PANEL
OFF
OFF
OFF
MS-9200UD version 1
OFF
ON
ON
ACS Protocol: MS-9600 version 1
ON
OFF
OFF
ACS Protocol: MS-9600 version 2 or higher
ON
OFF
ON
ACS Protocol: MS-9200UDLS or MS-9200UD version 2 or higher
ON
ON
OFF
ANN-BUS Protocol:
MS-9600LS Version 4 or higher
MS-9200UDLS Version 4 or higher
Table D.2 FACP Configuration
S1 DIP Switch
ON
OFF
5
not used (must be set to OFF)
6
This switch works in conjunction with switches 7 & 8 to set the number of ACC-25/50DAZS panels connected
7
This switch works in conjunction with switches 6 & 8 to set the number of ACC-25/50DAZS panels connected
8
6 OFF, 7 OFF, 8 OFF = No ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
6 OFF, 7 OFF, 8 ON = 1 ACC-25/50DAZS Distributed Audio Panel connected to ACC-25/50ZS/T
6 OFF, 7 ON, 8 OFF = 2 ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
6 OFF, 7 ON, 8 ON = 3 ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
6 ON, 7 OFF, 8 OFF = 4 ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
6 ON, 7 OFF, 8 ON = 5 ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
Table D.3 Number of ACC-25/50DAZS Panels Installed
Содержание ACC-25
Страница 62: ...62 Audio Command Center Series Manual P N 51889 E1 6 8 2010 Notes ...
Страница 101: ...Audio Command Center Series Manual P N 51889 E1 6 8 2010 101 Notes ...
Страница 137: ...Audio Command Center Series Manual P N 51889 E1 6 8 2010 137 Notes ...
Страница 144: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...