22
MRP-4424 Document 15180 Rev D 03/12/97 15180:D
Transmitter Module -- 4XTMF
Polarities shown in activated positions. The wiring of this module must follow the requirements as
specified in the
"General" section, "UL Power Limited Wiring Requirements."
+
-
+
-
+
-
Remote Alarm
Remote Trouble
1
2
3
4
5
6
7
}
TBL Jumper
Disconnect
LED
Disconnect
Switch
}
}
}
}
Power Limited Circuit
Non-Power Limited Circuit
No Connection
Municipal Box *
Push the disconnect switch down to prevent unwanted activation of the Municipal Box during testing
of the control panel. The Disconnect LED will remain illuminated while the Municipal Box is
disconnected. The System Trouble LED will indicate disconnected and/or Open Circuit conditions on
the Municipal Box.
Cutting the TBL jumper will allow the alarm reverse polarity circuit to open on trouble,
if no alarm exists.
* Dummy load terminals 6 and 7 (4.7K, 1/4 W resis-
tor) if Municipal Box is not connected.
Note:
Remote Alarm, Remote Trouble and Municipal Box wiring can leave the building.