 MRP-4424     Document  15180     Rev D     03/12/97     15180:D

Transmitter Module (4XTMF)

For Local Energy Municipal Box service (NFPA 72-1993 Auxiliary Fire Alarm System):
Supervisory current: 5.0 mA.
Trip current: 0.35 amps. (Subtracted from Notification Appliance power.)
Coil Voltage: 3.65 VDC.
Coil resistance: 14.6 ohms.
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building.

For Remote Station service (NFPA 72-1993 Remote Station Fire Alarm System):
Maximum load for each circuit:  10 mA.
Reverse polarity output voltage: 24 VDC.
Remote Alarm and Remote Trouble wiring can leave the building.

LED Interface Module (4XLMF)
Maximum voltage/current, each output: 27.6V/8mA.
Note: Outputs are power limited.

Zone Relay Module (4XZMF)
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)

1.4

Remote Annunciator

Notifier Remote Annunciator (RZA-4XF)
The Remote Annunciator mounts on a standard single-gang box, and provides
LED indication of the same functions as the zone relay module. For example,
with DIP 1=ON and DIP 2=OFF:

• One Zone in Alarm (red)
• Two Zones in Alarm (red)
• Releasing Circuit 1 (red)
• Releasing Circuit 2 (red)
• System Trouble (yellow)

A Local Trouble Sounder and Silence Switch are also provided.  All LED wiring
is supervised for open conditions. Any open condition will cause the System
Trouble LED to illuminate.

Note: The Remote Annunciator requires the use of an LED Interface module
(4XLMF).

1.5

Optional Meters

Voltage, Current Meters  (4XMMF)
The Meter Module provides a voltmeter to measure the voltage across the
batteries and an ammeter to measure the charging current to the batteries.
The meters are provided as a assembly that mounts to the lower left-hand
corner of the cabinet.

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Содержание MRP-4424

Страница 1: ...The MRP 4424 Agent Release Control Panel DOCUMENT 15180 ECN96 433 03 12 97 Rev D 12 Clintonville Road Northford CT 06472 Technical Manuals Online http www tech man com firealarmresources com ...

Страница 2: ...p before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the unit Follow the instructions in the installation operating and programming manuals These instructions must be followed to avoid damage to the control panel and associated equipment FACP operation and reliability depend upon proper instal...

Страница 3: ...2 2 Control Switches 12 2 3 Zone Status LEDs 12 2 4 Supervisory 13 2 5 Zone Disable 13 2 6 Last Event Recall 13 3 0 Installation Procedure 14 3 1 General 14 3 2 Initiating Device Circuits 15 3 3 4 Wire Smoke Detector Connections 16 3 4 Output Circuits 17 3 5 Power 18 3 6 Optional Modules 20 3 7 Setting MRP 4424 Mode of Operation 25 Appendix A Battery Calculations 27 Appendix B NFPA Standard Specif...

Страница 4: ...le Local and State Building Codes Requirements of the Local Authority Having Jurisdiction Noti Fire 911A Manual Document 74 06200 005 MS 5012 Manual Document 15465 Fire Lite Device Compatibility Document 15384 ADA Americans with Disabilities Act I NFPA Standards The MRP 4424 complies with the following NFPA standards NFPA 12 CO2 Extinguishing Systems High Pressure Only NFPA 12A Halon 1301 Extingui...

Страница 5: ...all Notification Release Circuits RMS regulated output power 2 25 amps 7 amp hour to 15 amp hour battery options up to 90 hours standby Resettable and non resettable regulated power outputs Extensive transient protection Watchdog timer to supervise microprocessor in cludes MICRO FAIL LED Output circuits protected against false activations Slide in zone identification labels Steel cabinet 14 5 wide...

Страница 6: ...6 MRP 4424 Document 15180 Rev D 03 12 97 15180 D Figure 1 0 1 MRP 4424 Installation Diagram Technical Manuals Online http www tech man com firealarmresources com ...

Страница 7: ...alarm exists Zone Relay Module 4XZMF The Zone Relay module provides Form C contacts for the following As a jumper option the first four relays described below can be made silenceable LED Interface Module 4XLMF The LED Interface Module supports the RZA 4XF Remote Annunciator module Annunciator wiring is supervised for open conditions by this module The Annunciator Driver Module mounts to the main b...

Страница 8: ...istive 0 5 amps 30 VAC resistive 1 4 Remote Annunciator NotifierRemoteAnnunciator RZA 4XF The Remote Annunciator mounts on a standard single gang box and provides LED indication of the same functions as the zone relay module For example with DIP 1 ON and DIP 2 OFF One Zone in Alarm red Two Zones in Alarm red Releasing Circuit 1 red Releasing Circuit 2 red System Trouble yellow A Local Trouble Soun...

Страница 9: ...o Style Y Z NACs two Style Y Releasing Circuits Maximum allowable voltage drop due to wiring 2 VDC Normal Operating Voltage 24 VDC Total current available to all external devices 2 25 amps Maximum signaling current per circuit 1 5 amps End of line resistor 4 7K 1 2 Watt part 71252UL listed Alarm and Trouble Relays Dry Form C contacts rated 2 0 amps 30 VDC resistive 0 5 amps 30 VAC resistive All re...

Страница 10: ... Rev D 03 12 97 15180 D Figure 1 6 1 Cabinet Dimensions Cabinet 5 375 Backbox 4 750 Door 16 125 Backbox 16 Door 14 625 Backbox 14 5 Optional Trim Ring TR 4XRF Technical Manuals Online http www tech man com firealarmresources com ...

Страница 11: ... flashes for any trouble condi tion including those associated with option boards CIRCUITTROUBLE Yellow LED that flashes for trouble conditions on output circuits notification and releasing circuits ALARMSILENCED Yellow LED that illuminates steadily when the ALARM SILENCE switch has been pushed after an alarm POWERTROUBLE YellowLEDthatflashesforlowordisconnected batteries and earth fault condition...

Страница 12: ...ing circuits The ALARM SILENCED LED will illuminate Alarm silence is a latching function and requires a RESET to clear ALARMACTIVATE The ALARM ACTIVATE switch may be used to activate Notification ApplianceCircuits ALARMACTIVATEalsoactivatestheSystemAlarm relay ALARM ACTIVATE is a latching function Pressing ALARM SILENCE silences the notification appliance circuits and System Alarm Relay and lights...

Страница 13: ...switch 2 With the TONE SILENCE switch held in press in sequence the ALARM SILENCE switch the ALARM ACTIVATE switch and then the RESET switch 3 The Zone 1 Alarm LED will flash 4 To disable Zone 1 press the RESET switch The Zone 1 yellow LED will light to show that the zone is disabled Note The RESET switch toggles disable status for the selected zone 5 To select the next zone press the ALARM SILENC...

Страница 14: ...dance with the National and or Local codes for fire alarm systems UL Power Limited Wiring Requirements Power limited and non power limited circuit wiring must remain separated in the cabinet All power limited circuit wiring must remain at least 0 25 away from any non power limited circuit wiring Furthermore all power limited circuit wiring and non power limited circuit wiring must enter and exit t...

Страница 15: ...ual Pull Station HeatDetector Two wire SmokeDetector Abort Switch Manual Release IDC 1 IDC 2 IDC 3 IDC 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 4 7K 1 2 Watt part 71252 UL listed 4 7K 1 2 Watt part 71252 UL listed Notes 1 Observe polarity when connecting polarized devices 2 All circuits are supervised and power limited 3 Leave Dummy Load provided on all unused circuits Style B Initiating Device Ci...

Страница 16: ...elay current RMAX 20 6 VOM N x IS NA x IA IR 3 3 4 Wire Smoke Detector Connections Refer to the Device Compatibility Chart for suitable 4 wire smoke detectors 24 VDC Common IDC IDC Red Black 24 VDC Common IDC IDC UL listed24VDC Four WireSmokeDetectors UL Listed 4 7K 1 2 Watt ELR TB1 1 2 3 4 TB4 1 2 3 4 B A A B 24VR A maximum of 200mA is available from the 24VDC 4 wire smoke detector power circuit ...

Страница 17: ...n of maximum allowable resistance RMAX 20 6V 20 4V IS Where RMAX maximum allowable resistance of wiring IS solenoid current Dummy Load all unused Notifi cationApplianceCircuits 4 7K 1 4 Watt UL ListedEnd of Linedevice 4 7K 1 4 Watt UL listedEnd of Linedevice Dummy Load all unused Releasing Circuits OUT 1 OUT 2 OUT 3 OUT 4 Figure 3 4 1 Notification Appliance Circuits B A A B B A A B B B B Polarized...

Страница 18: ...tedtothispanel Disconnect allsourcesofpowerbeforeservicing Thepanelandassociatedequipmentmaybedamaged by removing and or inserting cards modules or interconnecting cables while this unit is energized This output is not suitable for power ing devices requiring filtered regu lated DC power ThecombinedcurrentdrawsfromtheResettableandNon Resettableoutputscannot exceed 200 mA RMS Regulated Power 24 VDC...

Страница 19: ...ger wire with 600 volt rating Battery Power Observe polarity when connecting battery Connect battery cable to J9 on the main board using the plug in connector provided See Appendix A for calculation of correct battery rating Voltmeter Ammeter To monitor battery voltage and battery charging current a 4XMMF is required To install the power meter module remove the jumper labeled AMP and connect cable...

Страница 20: ...duplicatemodules seenotesbelow Thecorresponding option jumper must be cut before installation of an optional module Notes 1 Optional 4XLMF module for an RZA 4XF Annunciator must be installed on J7 and J8 only 2 4XTMF and 4XZMF modules can be installed in either location Figure 3 6 1 Option Panel Modules Cut for Ring by Zone J4 J7 J8 J5 Technical Manuals Online http www tech man com firealarmresour...

Страница 21: ...gn the pins on the main board with J1 and or J2 on the option board Insert screws provided into the holes on the top of the stand offs Affix the terminal identification labels provided with the option modules as shown below Stand offs Option Board 4XZMF shown Main Board Figure 3 6 2 Installing Option Modules Part 42050 Technical Manuals Online http www tech man com firealarmresources com ...

Страница 22: ...witch down to prevent unwanted activation of the Municipal Box during testing of the control panel The Disconnect LED will remain illuminated while the Municipal Box is disconnected The System Trouble LED will indicate disconnected and or Open Circuit conditions on the Municipal Box Cutting the TBL jumper will allow the alarm reverse polarity circuit to open on trouble if no alarm exists Dummy loa...

Страница 23: ... NC C NO NC C NO NC C Cut jumper for non latching silenceable relay operation powerlimited circuit powerlimited circuit non power limited circuit non power limited circuit Note Refer to the Protected Premises Unit label located on the door of the control panel to indicate if any dry contacts are to be used as non power limited dry contacts 1 Skip a set of dry contacts to maintain the 0 25 required...

Страница 24: ...und Resound 1 2 3 4 5 6 7 8 The wiring of this module must follow the requirements as specified in the General section UL Power Limited Wiring Requirements LED Interface Module 4XLMF Figure 3 6 3 LED Interface Module 4XLMF Note Make wiring connections with system power off Maximum wire impedance is 50 ohm per wiring connection Technical Manuals Online http www tech man com firealarmresources com ...

Страница 25: ... i r e d m o d e o f o p e r a t i o n a n d s e t S W 1 D I P s w i t c h 1 1 2 3 4 5 6 O N D I P S w i t c h e s S w i t c h 1 C R O S S Z O N E S w i t c h 2 S U P E R V I S O R Y T h e T i m e rw i l l s t a r t w h e n e v e r a n a l a r m o c c u r s o n e i t h e r Z o n e 1o r Z o n e 2 T h e T i m e rw i l l s t a r tw h e n a l a r m s o c c u r o n b o t h Z o n e 1 a n d Z o n e 2 O u...

Страница 26: ... S w i t c h e s 3 a n d 4 p l u s 9 0 s e c o n d s T h e t i m e r w i l l n o t s t a r t a s l o n g a s t h eA B O R T s w i t c h i s h e l d S Y S T E M R E S E T r e s t o r e s t i m e r t o o r i g i n a l t i m e s s e l e c t e d v i a D I P S w i t c h e s 3 a n d 4 S u c c e s s i v e A B O R T S w i l l a d d 9 0 s e c o n d s t o s e l e c t e d t i m e r v a l u e O NO N L o c a l...

Страница 27: ... C o n t r o l P a n e l 8 8 m A C o n t r o l p a n e l w i t h A C p o w e r o f f S y s t e m T r o u b l e L E D a n d a u d i b l e t r o u b l e s o u n d e r o n I f u s i n g a 4 X Z M F Z o n e R e l a y M o d u l e1 X 8 m A I f u s i n g a 4 X T M F T r a n s m i t t e r M o d u l e a d d 1 1 m A I f u s i n g t h e R e v e r s e P o l a r i t y A l a r m o u t p u t a d d 5 m A I f u s ...

Страница 28: ... y s t e m d r a w o f 3 a m p s i n a l a r m f o r 5 m i n u t e s 0 2 5 a m p h o u r o r f o r 1 0 m i n u t e s 0 5 a m p h o u r 2 N F P A 7 2 1 9 9 3 C e n t r a l S t a t i o n a n d N F P A 7 2 1 9 9 3 L o c a l a n d P r o p r i e t a r y F i r e A l a r m S y s t e m s r e q u i r e 2 4 h o u r s o f s t a n d b y 3 N F P A 7 2 1 9 9 3 A u x i l i a r y a n d R e m o t e S t a t i o n F...

Страница 29: ...c e w i t h t h e N F P A s t a n d a r d s l i s t e d b e l o w N F P A 7 2 1 9 9 3 S i g n a l i n g S y s t e m s f o r C e n t r a l S t a t i o n S e r v i c e P r o t e c t e d P r e m i s e s U n i t N O T I F I R E 9 1 1 A 9 1 1 A C D A C T o r M S 5 0 1 2 f o r c o n n e c t i o n t o a c o m p a t i b l e l i s t e d C e n t r a l S t a t i o n D A C R o r P r o t e c t e d P r e m i s ...

Страница 30: ... i s n o t F M a p p r o v e d N o t e s 1 T h e M a x i m u m s t a n d b y l o a d s h a l l b e 1 2 5 m A 2 T h e S t a n d b y B a t t e r y R e q u i r e m e n t 2 4 V D C 7 A m p H o u r M a x 3 T h e 9 1 1 A w a s d i s c o n t i n u e dE f f e c t i v e 1 0 9 6 t h i s d i a g r a m i s f o r r e f e r e n c e o n l y S T D D A C T N O T E o n S T D D A C T P l a c e j u m p e r o v e r p ...

Страница 31: ...han 20 in length in the same room This application using the NOTI FIRE 911AC is not FM approved NOTE on STD DACT Place jumper over pins 2 3 marked DACT when employing a DACT This directs the control panel to transmit all trouble conditions except AC LOSS d r a o b r e h t o M C A 1 1 9 m r a l A 1 3 B T 7 d n a 6 y l l a m r o n n e p o s t c a t n o c 3 3 B T 9 d n a 8 e l b u o r T 4 3 B T 0 1 y...

Страница 32: ...utral Ground Black White Green yellow yellow 1 2 TB2 TB3 TB1 RESET SILENCE MODE ALARM AC POWER TROUBLE SUPERVISORY Primary Active Secondary Active Kissoff J2 J3 Modular Cable P N MCBL 6 Secondary Phone Line Primary Phone Line 1 2 3 4 5 6 7 8 9 10 11 12 13 14 TB TB4 TB3 d r a o b r e h t o M 2 1 0 5 S M m r a l A 1 3 B T 2 2 B T 3 3 B T 1 2 B T e l b u o r T 4 3 B T 4 2 B T 6 3 B T 3 2 B T y r o s ...

Страница 33: ...ission of sprinkler supervisory or trouble conditions Note Maximum loop resistance allowed for wiring from control panel to Municipal Box is 3 ohms 4XTMF Transmitter Module activated polarities shown Municipal Box Circuit Gamewell ModelM34 56 Local Energy Municipal Box 6 7 Note Municipal Box wiring can leave the building Technical Manuals Online http www tech man com firealarmresources com ...

Страница 34: ...onnections are power limited and supervised with the exception of the reverse polarity loop Supervision of the loop is the responsibility of the receiver Fire Lite RS82 9 Remote Station Receiver UL listed Remote Trouble Remote Alarm 1 2 3 4 4XTMF Transmitter Module activated polarities shown Note Remote Alarm and Remote Trouble wiring can leave the building Technical Manuals Online http www tech m...

Страница 35: ...er 2 Use transformer model ULT STK NO 1000391 listed Class 2 12 V 10 VA See Potter Electric Signal Company Bulletin 748 3 This control panel transmitter arrangement can be employed for NFPA 72 1993 Proprietary Fire Alarm Systems Notes 1 Form C Alarm contact programmed to activate on General Alarm 2 Form C Trouble contact which will automatically activate on any Trouble condition MRP 4424 Technical...

Страница 36: ...n I d e l l a t s n i f i s e l u d o m l a n o i t p o V 2 1 r o f K 2 2 V 4 2 r o f K 7 4 R L E y m m u d 2 s d a e l y r e t t a b h t o b e v o m e R 3 e h t t a t i u c r i c e n o t c e n n o c s r a e l c e l b u o r t f I m e l b o r p e h t t n i o p n i p o t e m i t 4 t i u c r i c e c a l p e r r a e l c t n s e o d e l b u o r t f I d r a o b M T X 4 n o D E L w o l l e Y n o M T X 4 ...

Страница 37: ...37 MRP 4424 Document 15180 Rev D 03 12 97 15180 D NOTES Technical Manuals Online http www tech man com firealarmresources com ...

Страница 38: ...38 MRP 4424 Document 15180 Rev D 03 12 97 15180 D NOTES Technical Manuals Online http www tech man com firealarmresources com ...

Страница 39: ...39 MRP 4424 Document 15180 Rev D 03 12 97 15180 D NOTES Technical Manuals Online http www tech man com firealarmresources com ...

Страница 40: ...de by Fire Lite with respect to its products Fire Lite does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer acknowledges that Fire Lite is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience transportation damage misuse abuse ac...

Отзывы: