Document # 50079 Rev. D 05/23/97
Page
6
•
Wire size: minimum #14 AWG with 600V insulation
Control Input Circuit
•
Trigger Input Voltage - 9 to 32 VDC
•
Input Current Draw in Alarm Polarity
16 - 32V 2.0mA per input
9 - 16V 1.0mA per input
Trouble Contact Rating
•
5 amps at 24VDC
Output Circuits (19.1 - 26.4 VDC, filtered)
•
3.0 amps maximum for any one circuit
•
4.0 amps maximum total continuous current for all outputs
•
6.0 amps maximum total short term (one hour maximum) current for all
outputs
Auxiliary Power Output
•
Specific Application Power - 45 mA Short Circuit.
Secondary Power (Battery) Charging Circuit
•
Supports lead acid batteries only.
•
Float Charge Voltage: 27.6V
•
Maximum Charge Current: 250 mA
•
Maximum Battery Capacity: 7.0 AH
1.6 Installation Standards and Codes
The FCPS complies with the following standards:
NFPA 72-1993 National Fire Alarm Code
Underwriters Laboratories:
•
UL 864 Standard for Control Units for Fire Alarm Systems
•
UL 1481 Power Supplies for Fire Alarm Systems
In addition, the installer should be familiar with the following stan-
dards:
•
NEC Article 300 Wiring Methods
•
NEC Article 760 Fire Protective Signaling Systems
•
Applicable Local and State Building Codes
•
Requirements of the Local Authority Having Jurisdiction
Other documents supporting Fire•Lite Alarms products referenced in this
manual are listed below.
• Device Compatibility Document 15384
• The MS-9200 Instruction Manual, Document 15668
• The Sensiscan 2000 Installation Manual, Document 15017