Fire-Lite Alarms FCPS-24F Скачать руководство пользователя страница 2

WARNING:

 This equipment generates, uses, and can radiate radio frequency

energy and if not installed and used in accordance with the instruction manual, may

cause interference to radio communications. It has been tested and found to comply

with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC

Rules, which is designed to provide reasonable protection against such interference

when operated in a commercial environment. Operation of this equipment in a

residential area is likely to cause interference, in which case the user will be required

to correct the interference at his own expense.

Installation Precautions 

 

-   Adherence to the following will aid in problem-free installation with long-term reliability:

WARNING 

Several different sources of power can be connected to the fire alarm

control panel.

  Disconnect all sources of power before servicing.  Control unit and

associated equipment may be damaged by removing and/or inserting cards,

modules, or interconnecting cables while the unit is energized.  Do not attempt to

install, service, or operate this unit until this manual is read and understood.

CAUTION - 

System Reacceptance Test after Software Changes:

     To ensure

proper system operation, this product must be tested in accordance with NFPA 72-

1993 Chapter 7 after any programming operation or change in site-specific software.

Reacceptance testing is required after any change, addition or deletion of system

components, or after any modification, repair or adjustment to system hardware or

wiring.

All components, circuits, system operations, or software functions known to be

affected by a change must be 100% tested.  In addition, to ensure that other

operations are not inadvertently affected, at least 10% of initiating devices that are

not directly affected by the change, up to a maximum of 50 devices, must also be

tested and proper system operation verified.

This system  

meets NFPA requirements for operation at 0-49

O

 C/32-120

O

 F

and at a relative humidity of 85% RH (non-condensing) at 30

C/86

O

 F.

However, the useful life of the system's standby batteries and the electronic

components may be adversely affected by extreme temperature ranges and

humidity.  Therefore, it is recommended that this system and its peripherals be

installed in an environment with a nominal room temperature of 15-27

O

 C/60-80

O

F.

Verify that wire sizes are adequate

 for all initiating and indicating device loops.

Most devices cannot tolerate more than a 10% I.R. drop from the specified device

voltage.

Like all solid state electronic devices,

 this system may operate erratically or can

be damaged when subjected to lightning induced transients.  Although no system is

completely immune from lightning transients and interferences, proper grounding will

reduce susceptibility.

 Overhead or outside aerial wiring is not recommended, due to

an increased susceptibility to nearby lightning strikes.

  Consult with the Technical

Services Department if any problems are anticipated or encountered.

Disconnect AC power and batteries

 prior to removing or inserting circuit boards.

Failure to do so can damage circuits.

Remove all electronic assemblies

 prior to any drilling, filing, reaming, or punching

of the enclosure. When possible, make all cable entries from the sides or rear.

Before making modifications, verify that they will not interfere with battery,

transformer, and printed circuit board location.

Do not tighten screw terminals

 more than 9 in-lbs.  Over tightening may damage

threads, resulting in reduced terminal contact pressure and difficulty with screw

terminal removal.

This system 

contains static-sensitive components.  Always ground yourself with a

proper wrist strap before handling any circuits so that static charges are removed

from the body.  Use static suppressive packaging to protect electronic assemblies

removed from the unit.

Follow the instructions

 in the installation, operating, and programming manuals.

These instructions must be followed to avoid damage to the control panel and

associated equipment. FACP operation and reliability depend upon proper

installation.

Fire Alarm System Limitations

While installing a fire alarm system may make lower insurance

rates possible, it is not a substitute for fire insurance!

An automatic fire alarm system

 - typically made up of smoke detectors, heat

detectors, manual pull stations, audible warning devices, and a fire alarm control

with remote notification capability can provide early warning of a developing fire.

Such a system, however, does not assure protection against property damage or

loss of life resulting from a fire.

Any fire alarm system

 may fail for a variety of reasons:

Smoke detectors

 may not sense fire where smoke cannot reach the detectors such

as in chimneys, in walls, or roofs, or on the other side of closed doors.  Smoke

detectors also may not sense a fire on another level or floor of a building.  A second

floor detector, for example, may not sense a first floor or basement fire.  Further-

more, all types of smoke detectors - both ionization and photoelectric types, have

sensing limitations.  No type of smoke detector can sense every kind of fire caused

by carelessness and safety hazards like smoking in bed, violent explosions,

escaping gas, improper storage of flammable materials, overloaded electrical

circuits, children playing with matches, or arson.

IMPORTANT! 

 Smoke detectors  

must be installed in the same room as the

control panel and in rooms used by the system for the connection of alarm

transmission wiring, communications, signaling, and/or power.

  If detectors are

not so located, a developing fire may damage the alarm system, crippling its

ability to report a fire.

Audible warning devices

 such as bells  may not alert people if these devices are

located on the other side of closed or partly open doors or are located on another

floor of a building.

A fire alarm system

 will not operate without any electrical power.  If AC power fails,

the system will operate from standby batteries only for a specified time.

Rate-of-Rise heat detectors

 may be subject to reduced sensitivity over time.  For

this reason, the rate-of-rise feature of each detector should be tested at least once

per year by a qualified fire protection specialist.

Equipment used in the system

 may not be technically compatible with the control.

It is essential to use only equipment listed for service with your control panel.

Telephone lines

 needed to transmit alarm signals from a premise to a central

monitoring station may be out of service or temporarily disabled.

The most common cause

 of fire alarm malfunctions, however, is inadequate

maintenance.  All devices and system wiring should be tested and maintained by

professional fire alarm installers following written procedures supplied with each

device.  System inspection and testing should be scheduled monthly or as required

by National and/or local fire codes. Adequate written records of all inspections should

be kept.

FCC Warning

Canadian Requirements

This digital apparatus does not exceed the Class A limits for radiation noise

emissions from digital apparatus set out in the Radio Interference Regulations of the

Canadian Department of Communications.

Le present appareil numerique n'emet pas de bruits radioelectriques depassant les

limites applicables aux appareils numeriques de la classe A prescrites dans le

Reglement sur le brouillage radioelectrique edicte par le ministere des Communica-

tions du Canada.

Technical Publishing

        Document PRECAULG.P65  12/31/96

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Содержание FCPS-24F

Страница 1: ...le Road Northford CT 06472 203 484 7161 FAX 203 484 7118 FCPS 24F FCPS 24FE Field Charger Power Supply Installation Operation and Application Manual P N 50079 D ECN 97 145 D Technical Manuals Online http www tech man com firealarmresources com ...

Страница 2: ...p before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the unit Follow the instructions in the installation operating and programming manuals These instructions must be followed to avoid damage to the control panel and associated equipment FACP operation and reliability depend upon proper instal...

Страница 3: ...Module 13 Chapter 4 Special Applications 14 Section 4 0 Specific Applications 14 Section 4 1 Controlling Four Outputs from One Input 14 Figure 4 1a Control Module Application Style Y 14 Figure 4 1b Control Module Application Style Z 15 Section 4 2 Controlling Four Outputs from Two NAC Inputs 16 Figure 4 2 Two Inputs Controlling Four Outputs 16 Section 4 3 Controlling Four Outputs from One NAC Inpu...

Страница 4: ... VDC power outputs Output power circuits may be configured as resettable or nonresettable 3 0 amps maximum current available for any one output circuit 4 0 amps total of continuous current available 6 0 amps maximum short term one hour maximum current can be provided Fully filtered power output Integral supervised battery charger Up to 7 0 AH batteries in remote power supply cabinet Fully supervis...

Страница 5: ...75 to make Output 2 nonresettable power Cut R176 to make Output 4 nonresettable power 1 4 Optional Device MPM 4F Description The MPM 4F is used for Monitoring battery charger voltage Voltmeter Monitoring charger current Ammeter The MPM 4F is most commonly required in military installations It consists of two analog edge meters a voltmeter and an ammeter which connects to the P3 Header The voltmete...

Страница 6: ...e Current 250 mA Maximum Battery Capacity 7 0 AH 1 6 Installation Standards and Codes The FCPS complies with the following standards NFPA 72 1993 National Fire Alarm Code Underwriters Laboratories UL 864 Standard for Control Units for Fire Alarm Systems UL 1481 Power Supplies for Fire Alarm Systems In addition the installer should be familiar with the following stan dards NEC Article 300 Wiring Me...

Страница 7: ...ttery Charger Trouble Output 1 Trouble Output 2 Trouble Output 3 Trouble Output 4 Trouble JP1 R27 Battery fuse 10A 3AG slow blow Earth AC Neutral AC Hot To Transformer 1 To Transformer 2 D31 R175 JP2 R76 R176 R63 R134 In In Out Trouble Contact Out Trouble Contact In In Control Input 1 from FACP Control Input 2 from FACP Auxiliary Output Specific Application Power 45 mA Short Circuit Common To MPM ...

Страница 8: ...om the main FACP NAC output s to the remote power supply Control Input circuits When these Control Input circuits activate due to reverse polarity of the NAC output the power supply will activate its corresponding outputs NAC Control Input 1 controls power supply output circuits 1 and 2 NAC Control Input 2 controls output circuits 3 and 4 refer to Figure 4 2 During the inactive state the remote po...

Страница 9: ...s in the corners of the board Two permanent standoffs support the board in the center Set the board aside in a safe clean place Avoid static discharge which may damage the board 2 Mark and predrill holes for the top two keyhole mounting bolts 3 Install two upper fasteners in the wall with the screw heads protruding approximately 1 4 4 Using the upper keyholes mount the backbox over the two screws ...

Страница 10: ...sions Bottom 1 125 Backbox 14 5 Door 15 218 Top Depth 3 562 0 75 10 625 2 875 2 7 9 1 Figure 2 2 MPM 4F Installation Diagram MPM 4F Meter Bracket Transformer Bottom Nut JP1 Meter Assembly Cable P3 Header Technical Manuals Online http www tech man com firealarmresources com ...

Страница 11: ...imited circuit wiring must enter and exit the cabinet through different conduits One such example of this is shown below Your specific application may require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional Figure 2 3 Power limited Wiring Example If input circuit wiring is nonpower limited the 24 VDC output on termi...

Страница 12: ...l condition at the power supply may be delayed depending on R134 c A battery fail condition at the power supply d Battery charger fail e Earth Fault condition Any power supply trouble will break the connection between the FACP and the ELR provided the FACP s NAC is not in alarm The FACP s ELR must be placed after the last NAC appliance connected to FCPS terminals 3 4 or if no appliances are connec...

Страница 13: ...iode D31 jumper JP2 and resistor R63 Monitor FCPS trouble contacts at terminals TB3 3 and TB3 5 Any trouble condition listed above will trigger the internal trouble contact regardless of voltage polarity on the input 1 An addressable monitor module or any FACP input circuit may be used to track the condition of the trouble contact refer to Figures 4 4 4 5 and 4 6 Figure 3 1 Wiring Diagram of Multi...

Страница 14: ... refer to Figures 4 4 and 4 5 The control module is shown to demonstrate the use of the power supply on a multiplexed system The control module could be replaced with any circuit capable of polarity reversal Note that Figure 4 1a shows Style Y configuration and Figure 4 1b shows Style Z configuration Optional Style Z Return Optional Style Z Return SLC Loop to Addressable FACP 47 K ELR for Control ...

Страница 15: ...required when Style Z return is wired Note All Notification Appliance Circuits are supervised Optional Style Z Return Optional Style Z Return Figure 4 1b Control Module Application Style Z Notes The following notes apply to Figure 4 1b 1 When the remote power supply is in an inactive state control module not active a trouble on the power supply will result in an open circuit condition on the contr...

Страница 16: ...l Style Z Return This circuit may be power limited or nonpower limited Continuation of Notification Appliance Circuit 1 from FACP This circuit must be power limited by the FACP Control Input 1 Control Input 2 Continuation of Notification Appliance Circuit 2 from FACP Fire Alarm Control Panel Notification Appliance Circuit 1 Notification Appliance Circuit 2 Notes 1 ELRs must be used on the Notifica...

Страница 17: ... terminals 1 and 2 on the FCPS 2 Jumper TB3 Terminal 3 to Terminal 6 and Terminal 4 to Terminal 7 This allows a single Control Input to control the four FCPS outputs Install the ELR across terminals 6 and 7 to supervise the Notification Appliance Circuit originating from the FACP as well as the jumpers Refer to the respective FACP installation manual for corresponding ELR value 3 If additional not...

Страница 18: ...erminals 3 and 4 or a separate power source can be used The auxiliary power output of the FCPS power supply TB3 Terminals 8 9 should not be used for this purpose 3 The specific ELR required to be installed on the FCPS trouble monitoring contacts at TB3 3 and TB3 5 is dependent on the particular model of monitor module employed to supervise the FCPS The Fire Lite model M300 and M301 require a 47K E...

Страница 19: ...model of monitor module employed to supervise the FCPS Fire Lite models M300 and M301 require a 47K ELR Fire Lite model M302 requires a 3 9K ELR 3 Do not loop wires under screw terminals Break wires to maintain proper supervision 4 If an addressable M302 Monitor Module is employed to monitor the trouble contacts of the remote power supply the module must be supplied with separate 24 VDC power This...

Страница 20: ...o Terminal 6 and Terminal 2 to Terminal 7 2 An ELR must be installed between Terminals 6 and 7 for control module wiring supervision the ELR value is dependent on the module employed 3 The specific ELR required to be installed on the FCPS trouble monitoring contacts at TB3 3 and TB3 5 is dependent on the particular model of monitor module employed to supervise the FCPS Fire Lite models M300 and M3...

Страница 21: ...rol input 2 Notes 1 During a normal condition nonalarm 24 VDC should be applied to TB3 1 and TB3 2 2 The normally closed alarm relay may consist of an actual relay in the Fire Alarm Control Panel or a control module If a control module is being used it may be mounted remotely or at the control panel 3 A monitor module may be used to monitor the trouble contacts of the FCPS 4 Nonresettable power mu...

Страница 22: ...otal standby current draw of all devices on each active output including end of line relays when used for supervision Table 5 1 Load in Standby 24VDC e p y T e c i v e D s e c i v e D f o t n e r r u C s p m A l a t o T t n e r r u C s p m A C A t u o h t i w d r a o B C P n i a M d e l b a n E y a l e D t r o p e R l i a F m u m i x a m 1 X 2 3 0 0 R O l i a F C A h t i w d r a o B C P n i a M d ...

Страница 23: ... 0 amps Maximum Current Use the following tables to determine the proper battery size 3 When Battery Amp Hour Requirements are for Greater than 7 0 AH Cut FCPS jumper JP1 to disable onboard battery charger and use an external battery charger Table 5 2 Load in Alarm 24VDC e p y T e c i v e D s e c i v e D f o t n e r r u C s p m A t n e r r u C l a t o T s p m A C A t u o h t i w d r a o B C P n i ...

Страница 24: ... Hours i e 5 min 0 084 hours _________ Add Standby and Alarm Load for Required Ampere Hours _________ Multiply by the Derating Factor of 1 2 _________ Total Ampere Hours AH Required _________ Notes 1 Battery size is limited to 7 0 AH using the internal FCPS battery charger 2 For battery sizes greater than 7 0 AH cut FCPS jumper JP1 to disable the internal battery charger and use an external batter...

Страница 25: ...Document 50079 Rev D 05 23 97 Page 25 NOTES Technical Manuals Online http www tech man com firealarmresources com ...

Страница 26: ...Document 50079 Rev D 05 23 97 Page 26 NOTES Technical Manuals Online http www tech man com firealarmresources com ...

Страница 27: ...Document 50079 Rev D 05 23 97 Page 27 NOTES Technical Manuals Online http www tech man com firealarmresources com ...

Страница 28: ...de by Fire Lite with respect to its products Fire Lite does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer acknowledges that Fire Lite is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience transportation damage misuse abuse ac...

Отзывы: