background image

Document # 50079    Rev. D      05/23/97

Page 

 19

4.5 Remote Power Supply - Resettable and Nonresettable

The FCPS may be used as a remote stand-alone power supply to provide up to an
additional 4.0 amps of power to any devices that require filtered, regulated, resettable
or nonresettable power.  A monitor module may be used to monitor the trouble contact
of the FCPS.  If the FCPS enters a trouble condition the normally closed contact will
open.  A resettable output is created by tying the resettable output from the FACP to one
or both of the power supply inputs.  A nonresettable output is created by cutting an on
board resistor (R175 for Output 2, R176 for Output 4). For addressable panel
applications, use a monitor module to sense the trouble status of the remote power
supply via the trouble relay contact. Cut JP2, R63 and D31 for this application.

Fire Alarm

Control Panel

Resettable

24VDC Output

Control Input #1

SLC

Control
Input #2

Trouble

ELR

Note 2

+

-

Resettable

Power Output

Circuit #1

-

+

Resettable

Power Output

Circuit #3

-

Notes:
1) Outputs 2 and 4 are also resettable 24 VDC power in this example.  To make Output 2

nonresettable power, cut R175.  To make Output 4 nonresettable, cut R176.

2) The specific ELR required to be installed on the FCPS trouble monitoring contacts at TB3-

3 and TB3-5 is dependent on the particular model of monitor module employed to supervise
the FCPS.   Fire-Lite models M300 and M301 require a 47K ELR.  Fire-Lite model M302
requires a 3.9K ELR.

3) Do not loop wires under screw terminals.  Break wires to maintain proper supervision.
4) If an addressable M302 Monitor Module is employed to monitor the trouble contacts of the

remote power supply, the module must be supplied with separate 24 VDC power.  This power
is required so that the module may supervise the connection to the trouble contacts of the
power supply.

5) One of the FCPS nonresettable power outputs (TB4) can be used to supply 24 VDC to M302

terminals 3 and 4 or a separate power source can be used.  

The auxiliary power output of

the FCPS power supply (TB3 Terminals 8 & 9) should not be used for this purpose.

6) For a list of compatible devices, refer to Fire-Lite Device Compatibility Document.
7) It may be necessary to use an EOL relay on outputs that are normally activated for proper

supervision.

Figure 4-5: One NAC Input - Resettable & Nonresettable Outputs

Note 1

+

-

Power Output

Circuit #4

+

Power Output

Circuit #2

Resettable outputs deliver a negative polarity
voltage of up to -5 VDC during reset.  In the unlikely
case that this negative voltage causes a problem
resetting certain models of 4-wire smoke detectors,
use TB-4 terminals 3 (+) and 2 (-) for Output #1 and
terminals 9 (+) and 8 (-) for Output #3.

Monitor

Module

Notes 4 & 5

Refer to Section 1.1 for current ratings.

  1    2    3    4    5    6    7    8    9   10   11  12

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Содержание FCPS-24F

Страница 1: ...le Road Northford CT 06472 203 484 7161 FAX 203 484 7118 FCPS 24F FCPS 24FE Field Charger Power Supply Installation Operation and Application Manual P N 50079 D ECN 97 145 D Technical Manuals Online http www tech man com firealarmresources com ...

Страница 2: ...p before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the unit Follow the instructions in the installation operating and programming manuals These instructions must be followed to avoid damage to the control panel and associated equipment FACP operation and reliability depend upon proper instal...

Страница 3: ...Module 13 Chapter 4 Special Applications 14 Section 4 0 Specific Applications 14 Section 4 1 Controlling Four Outputs from One Input 14 Figure 4 1a Control Module Application Style Y 14 Figure 4 1b Control Module Application Style Z 15 Section 4 2 Controlling Four Outputs from Two NAC Inputs 16 Figure 4 2 Two Inputs Controlling Four Outputs 16 Section 4 3 Controlling Four Outputs from One NAC Inpu...

Страница 4: ... VDC power outputs Output power circuits may be configured as resettable or nonresettable 3 0 amps maximum current available for any one output circuit 4 0 amps total of continuous current available 6 0 amps maximum short term one hour maximum current can be provided Fully filtered power output Integral supervised battery charger Up to 7 0 AH batteries in remote power supply cabinet Fully supervis...

Страница 5: ...75 to make Output 2 nonresettable power Cut R176 to make Output 4 nonresettable power 1 4 Optional Device MPM 4F Description The MPM 4F is used for Monitoring battery charger voltage Voltmeter Monitoring charger current Ammeter The MPM 4F is most commonly required in military installations It consists of two analog edge meters a voltmeter and an ammeter which connects to the P3 Header The voltmete...

Страница 6: ...e Current 250 mA Maximum Battery Capacity 7 0 AH 1 6 Installation Standards and Codes The FCPS complies with the following standards NFPA 72 1993 National Fire Alarm Code Underwriters Laboratories UL 864 Standard for Control Units for Fire Alarm Systems UL 1481 Power Supplies for Fire Alarm Systems In addition the installer should be familiar with the following stan dards NEC Article 300 Wiring Me...

Страница 7: ...ttery Charger Trouble Output 1 Trouble Output 2 Trouble Output 3 Trouble Output 4 Trouble JP1 R27 Battery fuse 10A 3AG slow blow Earth AC Neutral AC Hot To Transformer 1 To Transformer 2 D31 R175 JP2 R76 R176 R63 R134 In In Out Trouble Contact Out Trouble Contact In In Control Input 1 from FACP Control Input 2 from FACP Auxiliary Output Specific Application Power 45 mA Short Circuit Common To MPM ...

Страница 8: ...om the main FACP NAC output s to the remote power supply Control Input circuits When these Control Input circuits activate due to reverse polarity of the NAC output the power supply will activate its corresponding outputs NAC Control Input 1 controls power supply output circuits 1 and 2 NAC Control Input 2 controls output circuits 3 and 4 refer to Figure 4 2 During the inactive state the remote po...

Страница 9: ...s in the corners of the board Two permanent standoffs support the board in the center Set the board aside in a safe clean place Avoid static discharge which may damage the board 2 Mark and predrill holes for the top two keyhole mounting bolts 3 Install two upper fasteners in the wall with the screw heads protruding approximately 1 4 4 Using the upper keyholes mount the backbox over the two screws ...

Страница 10: ...sions Bottom 1 125 Backbox 14 5 Door 15 218 Top Depth 3 562 0 75 10 625 2 875 2 7 9 1 Figure 2 2 MPM 4F Installation Diagram MPM 4F Meter Bracket Transformer Bottom Nut JP1 Meter Assembly Cable P3 Header Technical Manuals Online http www tech man com firealarmresources com ...

Страница 11: ...imited circuit wiring must enter and exit the cabinet through different conduits One such example of this is shown below Your specific application may require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional Figure 2 3 Power limited Wiring Example If input circuit wiring is nonpower limited the 24 VDC output on termi...

Страница 12: ...l condition at the power supply may be delayed depending on R134 c A battery fail condition at the power supply d Battery charger fail e Earth Fault condition Any power supply trouble will break the connection between the FACP and the ELR provided the FACP s NAC is not in alarm The FACP s ELR must be placed after the last NAC appliance connected to FCPS terminals 3 4 or if no appliances are connec...

Страница 13: ...iode D31 jumper JP2 and resistor R63 Monitor FCPS trouble contacts at terminals TB3 3 and TB3 5 Any trouble condition listed above will trigger the internal trouble contact regardless of voltage polarity on the input 1 An addressable monitor module or any FACP input circuit may be used to track the condition of the trouble contact refer to Figures 4 4 4 5 and 4 6 Figure 3 1 Wiring Diagram of Multi...

Страница 14: ... refer to Figures 4 4 and 4 5 The control module is shown to demonstrate the use of the power supply on a multiplexed system The control module could be replaced with any circuit capable of polarity reversal Note that Figure 4 1a shows Style Y configuration and Figure 4 1b shows Style Z configuration Optional Style Z Return Optional Style Z Return SLC Loop to Addressable FACP 47 K ELR for Control ...

Страница 15: ...required when Style Z return is wired Note All Notification Appliance Circuits are supervised Optional Style Z Return Optional Style Z Return Figure 4 1b Control Module Application Style Z Notes The following notes apply to Figure 4 1b 1 When the remote power supply is in an inactive state control module not active a trouble on the power supply will result in an open circuit condition on the contr...

Страница 16: ...l Style Z Return This circuit may be power limited or nonpower limited Continuation of Notification Appliance Circuit 1 from FACP This circuit must be power limited by the FACP Control Input 1 Control Input 2 Continuation of Notification Appliance Circuit 2 from FACP Fire Alarm Control Panel Notification Appliance Circuit 1 Notification Appliance Circuit 2 Notes 1 ELRs must be used on the Notifica...

Страница 17: ... terminals 1 and 2 on the FCPS 2 Jumper TB3 Terminal 3 to Terminal 6 and Terminal 4 to Terminal 7 This allows a single Control Input to control the four FCPS outputs Install the ELR across terminals 6 and 7 to supervise the Notification Appliance Circuit originating from the FACP as well as the jumpers Refer to the respective FACP installation manual for corresponding ELR value 3 If additional not...

Страница 18: ...erminals 3 and 4 or a separate power source can be used The auxiliary power output of the FCPS power supply TB3 Terminals 8 9 should not be used for this purpose 3 The specific ELR required to be installed on the FCPS trouble monitoring contacts at TB3 3 and TB3 5 is dependent on the particular model of monitor module employed to supervise the FCPS The Fire Lite model M300 and M301 require a 47K E...

Страница 19: ...model of monitor module employed to supervise the FCPS Fire Lite models M300 and M301 require a 47K ELR Fire Lite model M302 requires a 3 9K ELR 3 Do not loop wires under screw terminals Break wires to maintain proper supervision 4 If an addressable M302 Monitor Module is employed to monitor the trouble contacts of the remote power supply the module must be supplied with separate 24 VDC power This...

Страница 20: ...o Terminal 6 and Terminal 2 to Terminal 7 2 An ELR must be installed between Terminals 6 and 7 for control module wiring supervision the ELR value is dependent on the module employed 3 The specific ELR required to be installed on the FCPS trouble monitoring contacts at TB3 3 and TB3 5 is dependent on the particular model of monitor module employed to supervise the FCPS Fire Lite models M300 and M3...

Страница 21: ...rol input 2 Notes 1 During a normal condition nonalarm 24 VDC should be applied to TB3 1 and TB3 2 2 The normally closed alarm relay may consist of an actual relay in the Fire Alarm Control Panel or a control module If a control module is being used it may be mounted remotely or at the control panel 3 A monitor module may be used to monitor the trouble contacts of the FCPS 4 Nonresettable power mu...

Страница 22: ...otal standby current draw of all devices on each active output including end of line relays when used for supervision Table 5 1 Load in Standby 24VDC e p y T e c i v e D s e c i v e D f o t n e r r u C s p m A l a t o T t n e r r u C s p m A C A t u o h t i w d r a o B C P n i a M d e l b a n E y a l e D t r o p e R l i a F m u m i x a m 1 X 2 3 0 0 R O l i a F C A h t i w d r a o B C P n i a M d ...

Страница 23: ... 0 amps Maximum Current Use the following tables to determine the proper battery size 3 When Battery Amp Hour Requirements are for Greater than 7 0 AH Cut FCPS jumper JP1 to disable onboard battery charger and use an external battery charger Table 5 2 Load in Alarm 24VDC e p y T e c i v e D s e c i v e D f o t n e r r u C s p m A t n e r r u C l a t o T s p m A C A t u o h t i w d r a o B C P n i ...

Страница 24: ... Hours i e 5 min 0 084 hours _________ Add Standby and Alarm Load for Required Ampere Hours _________ Multiply by the Derating Factor of 1 2 _________ Total Ampere Hours AH Required _________ Notes 1 Battery size is limited to 7 0 AH using the internal FCPS battery charger 2 For battery sizes greater than 7 0 AH cut FCPS jumper JP1 to disable the internal battery charger and use an external batter...

Страница 25: ...Document 50079 Rev D 05 23 97 Page 25 NOTES Technical Manuals Online http www tech man com firealarmresources com ...

Страница 26: ...Document 50079 Rev D 05 23 97 Page 26 NOTES Technical Manuals Online http www tech man com firealarmresources com ...

Страница 27: ...Document 50079 Rev D 05 23 97 Page 27 NOTES Technical Manuals Online http www tech man com firealarmresources com ...

Страница 28: ...de by Fire Lite with respect to its products Fire Lite does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer acknowledges that Fire Lite is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience transportation damage misuse abuse ac...

Отзывы: