8
For the best draw,
the chimney
termination should
be at least 2 feet
above the highest
portion of the roof
that is within a 10
foot radius of the
chimney.
The termination cap
should be designed
to inhibit down-
drafting without
restricing the
exhaust discharge.
When using a brick chimney, you must line the entire chimney
with stainless steel liner. The liner must be a 6 inch liner.
The diameter of the chimney stack should be consistent
throughout the length of the chimney.
The chimney stack should have a built in airtight clean out.
WARNING: Do not operate with clean out uncapped.
USE LISTED UL 103 TYPE
HT 2100 CHIMNEY ONLY.
The chimney size should be at least as large as the exhaust stack on
the furnace, but not more than twice its size.