40069 Zola Predosa (BO) - ITALY
- EN -
DATABASE
Below is a list of the parameter description, type and address of data on DMC20 :
Data
Description
Type
Register
Address
DewPoint
DewPoint temperature - T1 probe
Signed Integer
0000 - R
Air
→
O
Temperature of the incoming air - T2 probe
Signed Integer
0001 - R
Air
←
O
Temperature of the outgoing air - T3 probe
Signed Integer
0002 - R
Compr.LP
Suction temperature of the compressor (low pressure side) - T4 probe
Signed Integer
0003 - R
Compr.HP
Outlet temperature of the compressor (high pressure side) - T5 probe Signed Integer
0004 - R
Condens.
Condensing temperature - T6 probe
Signed Integer
0005 - R
Water
→
O
Inlet temperature of the cooling water (Water-Cooled) - T8 probe
Signed Integer
0006 - R
Ambient
Ambient temperature - T7 probe
Signed Integer
0007 - R
Language
1)
Selection of the language for dialogue and alarm messages
Signed Integer 0200 - R/W
DewPoint Set
Not Used
Signed Integer 0201 - R/W
Diff. DewPoint Not Used
Signed Integer 0202 - R/W
E Drain Time
Not Used
Signed Integer 0203 - R/W
E Drain Pause Not Used
Signed Integer 0204 - R/W
S Drain Time
Discharge time of the condensate separator
Signed Integer 0205 - R/W
S Drain Pause Pause between two condensate separator discharges
Signed Integer 0206 - R/W
Display Contrast. Adjustment of the Display contrast
Signed Integer 0207 - R/W
Min DewPoint
Not Used
Signed Integer 0208 - R/W
Max DewPoint Not Used
Signed Integer 0209 - R/W
Low DewPoint Temperature of interv. for the too low DewPoint alarm
Signed Integer 0210 - R/W
Low DP Diff.!
Differential temperature for the too low DewPoint alarm
Signed Integer 0211 - R/W
Low DP Delay! Delay time for the too low DewPoint alarm
Signed Integer 0212 - R/W
High DewPoint ! Temperature of interv. for the too high DewPoint alarm
Signed Integer 0213 - R/W
High DP Diff.!
Differential temperature for the too high DewPoint alarm
Signed Integer 0214 - R/W
High DP Delay! Delay time for the too high DewPoint alarm
Signed Integer 0215 - R/W
Condensation ! Temperature of intervention for the too high DewPoint alarm
Signed Integer 0216 - R/W
Condens.Diff.! Differential temperature for the too high DewPoint alarm
Signed Integer 0217 - R/W
Condens.Delay! Delay time for the too high DewPoint alarm
Signed Integer 0218 - R/W
Peripheral No
Unit address for serial communication
Signed Integer 0219 - R/W
Working
Operating time of the dryer in hours
Signed Integer 0246 - R/W
Alarm STOP
Presence of an alarm that has stopped the dryer
bit - 1=Yes 0100.0 - R
Alarm Status
Presence of an alarm
bit - 1=Yes 0100.1 - R
Cond. Fan Switch Status of the condenser fan control pressure switch
bit - 1=ON
0101.3 - R
Remote ON/OFF
Switch
Status of the Remote ON/OFF switch
bit - 0=Local
1=Remote
0101.6 - R
DewPoint LOW Low DewPoint alarm ON
bit - 1=Yes 0102.0 - R
DewPoint HIGH High DewPoint alarm ON
bit - 1=Yes 0102.1 - R
Condens. HIGH High Condensation temperature alarm ON
bit - 1=Yes 0102.2 - R
STOP Compr.LP Cooler low pressure switch (P
B
) alarm ON
bit - 1=Yes 0102.4 - R
STOP Compr.HP Cooler high pressure switch (P
A
) alarm ON
bit - 1=Yes 0102.5 - R
Protection Fan. Fan thermal/electrical protections alarm ON (Air-Cooled)
bit - 1=Yes 0102.6 - R
Protection Comp. Compressor thermal/electrical protections alarm ON
bit - 1=Yes 0102.7 - R
Probe Fault
Probe faulty alarm ON
bit - 1=Yes 0102.8 - R
Stop ! Low DP STOP enabled in case the DewPoint of the dryer is too low
bit - 1=Yes 0220.0 - R/W
Stop ! High DP STOP enabled in case the DewPoint of the dryer is too high
bit - 1=Yes 0220.1 - R/W
Automatic
Start-up
Machine enabled to restore its operation after a power black out
bit - 1=Yes 0220.2 - R/W
Recovery After !
Autom.
Automatic alarms reset
bit - 1=Yes 0220.3 - R/W
ON/OFF DMC20 Status of DMC20 - ON or OFF (Stand-by)
bit-1=Stand-by
0220.15 - R/W
NOTE :
1)
Language selection : 00=Italian - 01=English - 02=German - 03=French
R=Read - W=Write
Содержание RD 185-810
Страница 37: ...40069 Zola Predosa BO ITALY info finicompressors it 7 1 1 RD 185 350 AC 7 1 2 RD 410 AC 7 1 3 RD 480 620 AC ...
Страница 38: ...40069 Zola Predosa BO ITALY info finicompressors it 7 1 4 RD 810 AC 7 1 5 RD 185 350 WC 7 1 6 RD 410 WC ...
Страница 39: ...40069 Zola Predosa BO ITALY info finicompressors it 7 1 7 RD 480 620 WC 7 1 8 RD 810 WC ...
Страница 40: ...40069 Zola Predosa BO ITALY info finicompressors it 7 2 1 RD 185 410 ...
Страница 41: ...40069 Zola Predosa BO ITALY info finicompressors it 7 2 2 RD 480 810 ...
Страница 54: ...40069 Zola Predosa BO ITALY info finicompressors it The access code to the 2 level is 20 EN ...