SET-UP PARAMETERS TABLE
Parameter
Description
Adjustment
Range
Std
Value
Pass Code ? Password to access level 2
0 - 255
0
Language
Selection of the language for dialogue and alarm messages
Italian - English
German - French
DewPoint Set Not Used
N.A.
-5 ºC
DewPoint Diff. Not Used
N.A.
0.2 ºK
E Drain Time Not Used
0 - 50 sec
3 sec
E Drain Pause Not Used
0.5 - 10 min
4.0 min
S Drain Time Discharge time of the condensate separator
0 - 50 sec
4 sec
S Drain Pause Pause between two condensate separator discharges
0.5 - 10 min
1.0 min
Display Contrast. Adjustment of the Display contrast
0 - 100
50
Min DewPoint Not Used
N.A.
-10 ºC
Max DewPoint Not Used
N.A.
0 ºC
Low ! DewPoint Temperature of interv. for the too low DewPoint alarm
-10.0 - 0.0 ºC -5 ºC
Low DP ! Diff. Differential temperature for the too low DewPoint alarm
1.0 - 10.0 ºK
6 ºK
Low DP ! Delay Delay time for the too low DewPoint alarm
0.5 - 20 min
10 min
Low DP ! Stop STOP enabled in case the DewPoint of the dryer is too low
YES/NO
NO
High DewPoint ! Temperature of interv. for the too high DewPoint alarm
10.0 - 20.0 ºC 15 ºC
High DP ! Diff. Differential temperature for the too high DewPoint alarm
-1.0 - -10.0 ºK -5 ºK
High DP ! Delay Delay time for the too high DewPoint alarm
0.5 - 30 min
20 min
High DP ! Stop STOP enabled in case the DewPoint of the dryer is too high
YES/NO
NO
Condensation ! Temp. of intervention for the too high condensation
temperature alarm
50.0 - 70.0 ºC 60.0 ºC
Condens ! Diff. Differential temp. for the too high condensation
temperature alarm
-1.0 - -10.0 ºK -5 ºK
Condens. ! Delay Delay time for the too high condensation temp. alarm
0.5 - 20 min
10 min
Start at
Power Up
Machine enabled to restore its operation after a power
black out
YES/NO
NO
Recovery After ! Automatic alarms reset
YES/NO
NO
Peripheral No. Unit address for serial communication
01 - 255
01
5.17.4 REMOTE COMMAND
It is possible to remotely switch the dryer ON and OFF by means of a simple switch connected with two
wires to the DMC20 (see terminal 20 and 21 on the electric diagram). Closing the contact of the command
switch, on the display appears the message "Stand-by Remote", and no functions will be selectable on the
local panel; as soon as the contact is opened, the dryer returns to the previous condition (Stand-by if it was
in Stand-by condition, ON if it was ON).
I
F INSTALLED
,
THE REMOTE CONTROL HAS PRIORITY ON THE FRONTAL COMMANDS OF THE
DMC20.
THE
USER WILL BE RESPONSIBLE FOR THE INSTALLATION OF PROPER PROTECTIONS FOR POSSIBLE SUDDEN
POWER RESTORATION TO THE DRYER
.
L
E
V
E
L
1
L
E
V
E
L
2
Содержание RD 185-810
Страница 37: ...40069 Zola Predosa BO ITALY info finicompressors it 7 1 1 RD 185 350 AC 7 1 2 RD 410 AC 7 1 3 RD 480 620 AC ...
Страница 38: ...40069 Zola Predosa BO ITALY info finicompressors it 7 1 4 RD 810 AC 7 1 5 RD 185 350 WC 7 1 6 RD 410 WC ...
Страница 39: ...40069 Zola Predosa BO ITALY info finicompressors it 7 1 7 RD 480 620 WC 7 1 8 RD 810 WC ...
Страница 40: ...40069 Zola Predosa BO ITALY info finicompressors it 7 2 1 RD 185 410 ...
Страница 41: ...40069 Zola Predosa BO ITALY info finicompressors it 7 2 2 RD 480 810 ...
Страница 54: ...40069 Zola Predosa BO ITALY info finicompressors it The access code to the 2 level is 20 EN ...