5.17.2 ALARMS
Any alarm condition is indicated by the flashing of the [9] led "Alarm" and the DMC20 activates a buzzer
tone in order to alert the operator. The operator can stop the buzzer by pressing any key. The cause of the
alarm will be displayed on the upper line of the LCD display.
Alarm Message
Cause
Intervention
Point
Intervention
Delay
Remarks
Protection Comp.
Thermal/electrical protection
of the compressor
-
No delay
The dryer is stopped
Protection Fan.
(Air-Cooled)
Thermal/electrical protection
of the fan
-
No delay
The dryer is stopped
STOP Compr.LP
PB Refrigerant low pressure
switch
R404A = 1.0 barg
No delay
The dryer is stopped
STOP Compr.HP
PA Refrigerant high
pressure switch
R404A = 32 barg
No delay
The dryer is stopped
Condens. HIGH
Condensation temperature
too high (probe T6)
50 - 70 °C
0.5-20
adjustable
The dryer is stopped
DewPoint LOW
DewPoint low (probe T1)
-10 - 0 °C
0.5-20
adjustable
The operator chooses
whether to stop dryer
DewPoint HIGH
DewPoint high (probe T1)
10 - 20 °C
0.5-30 min
adjustable
The operator chooses
whether to stop dryer
Probe Fault
One of the probes is faulty
-
No delay
The dryer does not stop
STORING ALARMS IN MEMORY
When the
“Automatic Start-Up” and “Reset ! Autom.”
functions are deactivated (customer selected
setting “no”), any alarm causing the dryer to stop and any anomaly with one or more probes (Probe Fault) is
stored in the memory of DMC20. To reset the alarm memory the dryer is to be switched OFF (keep the
button [15] "Dryer Stop" pressed for at least 2 seconds). The dryer is then to be switched ON again (keep
the button [14] "Dryer Start-up" pressed for at least 2 seconds); If the alarm is no longer in effect the dryer
will run correctly, otherwise the alarm message will appear again.
When the “
Automatic Start-Up” and “Reset ! Autom.”
functions are activated (customer selected setting
“yes”) any alarm which has caused the stop of the dryer and any anomaly with one or more probes (Probe
Fault) is automatically reset once nominal conditions return and the dryer will run again automatically.
Any alarm, which is not causing the stop of the dryer, is reset automatically when nominal working
conditions return.
5.17.3 SET-UP
The DMC20 is adjusted during the final test of the dryer. Where particular requirements concerning the
operation or the alarm management exist, the user can change the setting of the programmed parameters.
Set-up parameters are divided into two levels: anybody can access the level 1, while access to level 2 is
reserved to authorised personnel provided with the password.
To access to Set-up mode the [11] "Set-up access" button must be depressed for at least 2 seconds. Then
it will be possible to display the desired parameter using the [12] and [13] keys. To modify the displayed
parameter, use the [12] and [13] keys, while keeping the [11] key depressed.
During Set-up, the upper line of the display will display the selected parameter, while the lower line will show
the current value of the same parameter.
To exit Set-up mode, press simultaneously the [12] and [13] keys, or wait 20 seconds.
NOTE : The character “!” means “Alarm”
DESCRIPTION OF SET-UP PARAMETERS
LEVEL
1
•
Pass Code?
: The system asks for the password to access the level 2 of the programming parameters; If
the password is not modified or wrong, only the parameters of level 1 will be accessible;
NOTE :
The
password can be modified only when the dryer is in stand-by; therefore during operation, only the level 1
will be accessible.
•
Language
: It is possible to select the language for the alarm and dialogue messages.
Содержание RD 185-810
Страница 37: ...40069 Zola Predosa BO ITALY info finicompressors it 7 1 1 RD 185 350 AC 7 1 2 RD 410 AC 7 1 3 RD 480 620 AC ...
Страница 38: ...40069 Zola Predosa BO ITALY info finicompressors it 7 1 4 RD 810 AC 7 1 5 RD 185 350 WC 7 1 6 RD 410 WC ...
Страница 39: ...40069 Zola Predosa BO ITALY info finicompressors it 7 1 7 RD 480 620 WC 7 1 8 RD 810 WC ...
Страница 40: ...40069 Zola Predosa BO ITALY info finicompressors it 7 2 1 RD 185 410 ...
Страница 41: ...40069 Zola Predosa BO ITALY info finicompressors it 7 2 2 RD 480 810 ...
Страница 54: ...40069 Zola Predosa BO ITALY info finicompressors it The access code to the 2 level is 20 EN ...