23
Setting
1.3
Unit Type
Application
Probe Length
Adjustment L.V.
Application
1.3.1
Type of Medium
Application Mode
Medium/D.C.
Type of Medium
Solids
Liquids
Media Type
Solvent and Oil/<3
Aqueous Media />10
Chemical Mixture/3...10
Application (1.3) menu provides settings based on application media and condition,
including the following parameters:
Media Type(1.3.1): It is to set solid or liquid media based on the measured media.
Media/ Dielectric Constant (1.3.2): For solid media, it is to set the media as [Dust, Wood
Chips/<1.5, Particles, Cement
/1.5…3, Object, Powder />3]
;
For liquid media, it is to set the
media as [Solvent and Oil /<3, Chemical Mixture
/3…10
,
Aqueous Media />10]
。
Setting
1.4
Unit Type
Diagnostics
Display
Additional Set
Adjustment L.V.
1.4.1
Min. Adjustment
Offset Adjustment
Max. Adjustment
Offset Adjustment
1st Offset
2nd Offset
1st Offset
- 0 0 0 0 0
-6400.0
…
+6400.0
mm
2nd Offset
- 0 0 0 0 0
-6400.0
…
+6400.0
mm
Material Level Adjustment (1.4) menu can be divided into High Level Adjustment (1.4.1)
and Low Level Adjustment (1.4.2) used to set the upper/lower limit(0/100%) shown on the
LCM display and upper/lower limit(4/20mA) of analog output.
Deviation Adjustment (1.4.3) refers to the difference between the measured signal and the
actual material height. You may set this value to change the measured value.
Note!
The parameter settings of High/Low Level Adjustment require inputting the distance from
the bottom of flange.