27
Diagnostics
3.5
Echo curve
Simulation
Sensor status
Trigger Default
Trigger Default
0 1 0 0
+0.000
…
+9999
3.5.1
Trigger Default
(3.5) menu is to set the minimum level for setting the echo signal.
Diagnostics
3.6
Simulation
Sensor status
Trigger Default
Blind Distance
Blind Distance
0 0 2 0 0
+0.0000
…
+6400.0
3.6.1
mm
Blind distance(3.6) menu is to set the distance from the bottom of flange t
hat can’t be
measured ( 200mm by default).
9.2.4 Additional Settings Menu
Additional Set
4.1
HART Mode
D.C. Value
Reset
Probe Type
HART Mode
4.1.1
HART Variables
HART Address
HART Variables
HART variable (PV)
Distance
HART variable (SV)
Distance Percent
HART Address
0 1
0
……
16
HART Mode(4.1.1) menu, the first layer is divided into HART Variable and HART Address.
HART Variable submenu allows you to query the data of 4 HART variables, while HART
Address submenu is to set the communication ID.
Additional Set
4.2
HART Mode
D.C. Value
Reset
Probe Type
D.C. Value
4.2.1
Auto calculate D.C. value?
YES
NO
D.C. Value
0 1 . 5 7
+1.500
…
.+10.00
D.C. Value(4.2) menu is to set the dielectric constant of the media. It is used for the bottom
tracking probe mode.
Additional Set
4.3
HART Mode
D.C. Value
Reset
Probe Type
Reset
4.3.1
NO
YES
Reset (4.3) menu is to restore to the factory settings. After Yes is pressed, all parameters
will be reset.