26
9.2.3 Diagnostics
Diagnostics
3.1
Peak distance
Echo curve
Simulation
Sensor status
Diagnosis
(3) menu provides 6 parameters for setting, with the function as introduced below:
Peak distance (3.1): It is to query and reset the measured peak value.
。
Echo curve (3.2): It is to view the echo curve of the measured signal.
Simulation (3.3): It is to simulate the height of the measured media.
Sensor Status (3.4): It is to view the sensor status.
Trigger Default (3.5): It is the minimum level of echo signal.
。
Blind Distance (3.6): It is the distance from the bottom of flange th
at can’t be measured.
Diagnostics
3.1
Peak distance
Echo curve
Simulation
Sensor status
Peak Distance
3.1.1
MAX: 597 mm
MIN: 581 mm
Return
Clear
Peak distance
(3.1) menu records the measured peak value after startup, which can be queried
and reset in this menu.
Echo Curve
(3.2) menu shows the echo curve that is measured currently.
Diagnostics
3.3
Peak distance
Echo curve
Simulation
Sensor status
Simulation
3.3.1
1st simulation
2nd simulation
1st Simulation
YES
NO
Activate Simulation?
Simulation (3.3) menu provides settings in two phases. The first phase is to select whether
to start the simulation function. The second phase is to input the target distance value to
be simulated.
Diagnostics
3.4
Peak distance
Echo curve
Simulation
Sensor status
Sensor Status
3.4.1
No error occurred
Sensor Status (3.4) menu allows you to query the current instrument status. Under normal
status, it shows No Error. After self-diagnosis, it shows error code in case of error.