13.  Configure display settings

Before commissioning, it may be necessary to set inverter configurations prior to grid connection by accessing the SETTINGS menu from the display.

 ATTENTION – 

A

The man adjustable parameters and instructions for accessing the SETTINGS menu are explained below 

With only array connected, set DC disconnect switch to ON. GREEN POWER LED will flash and YELLOW ALARM LED will be steady. LCD will read 

"Missing Grid". Press ESC to open menus. Use DOWN key to scroll to Settings, and press ENTER. SETTINGS menu requires an access password.

Default password is 0000, pressing ENTER four times loads four zeroes on the display and opens the submenu.

•  Area b7 has two visible text lines and the UP and DOWN keys are used to scroll through the menu items. 

•  Arrow (>) on the left side of the display highlights the current selection. 

•  Press UP or DOWN keys to move the arrow to the desired selection and press ENTER to open the associated submenu. 

•  To return to the preceding menu, press the ESC key.

Address

:

  the RS485 address may need to be changed or assigned; DEFAULT address is 

set at 2 for a single inverter.

•  Scroll to 

Address

 and press ENTER to open submenu. Address values are assigned 

manually using any value in the range [2 to 63]. Scroll DOWN to number (2) and press ENTER.

•  Press UP and DOWN keys to scroll through numbers and press ENTER to select, ESC 

to cancel.

Vstart

: Vstart Parameter may need to be adjusted when short strings are used in PV array. 

Change activation voltage only if necessary.

•  Scroll DOWN to Vstart and press ENTER; Voltage range can be 250V to 500V ; (Default setting is 360V.)

•  If more than one input, select Vstart 1 or 2

•  Use DOWN key to move arrow to desired selection and press ENTER. 

•  Second display screen will open; press ENTER to confirm or ESC to cancel.

14.  Commissioning

The inverter commissioning procedure is as follows:

1. Turn the DC disconnect switch in the ON position. If there are two separate external disconnect switches (one for DC and the other for AC), first close 

the AC disconnect switch and then the DC disconnect switch.

2. Once powered, icon b11 comes on to indicate that the voltage from the PV array has reached the Vstart threshold. 

For input voltages lower than Vstart, icon b11 remains off,  “Waiting Sun” is shown in display area b7 and voltage  

and current are present (icons b12 and b13).

3. As soon as “Waiting Sun” conditions are met, the inverter shows the AFD board self-test running.  The results are shown in display area b7.   

If a problem on the AFD board is detected, the self-test will result in an error.  Refer to section 16 below.

4. If there are no irregularities, the grid connection sequence starts. Once all the checks are 

completed, icon b19 comes on. During these checks, icon b19 is flashing. 

5. Icon b14 flashes to indicate the start-up phase; at the same time icon b15 will come on.

6. 

Immediately following the grid connection will start. Icon b18 will be displayed in steps until the connection is complete. After the inverter is connected, 

the icon b18 will stay “plugged in”.

If there is not sufficient sunlight to connect to the grid, the unit will repeat the procedure until all the parameters controlling connection to the grid (grid 

voltage and frequency, confirmation of no ground fault) are within range. During this procedure, the green LED flashes ON and OFF.

15.  Arc fault detection

For –A models only, the AFD performs a self-test when the system is started. The inverter display shows the results of the self-test in area b7.

•  If the self-test results are OK, the inverter will continue to AC grid connection.

•  If a potential problem on the AFD board is detected, the self-test will result in error E053.

Refer to the technical manual online for possible solutions to clear the error.

During normal operation the input current is continually measured and analyzed.

•  If a DC arc fault is detected during operation, the inverter is disconnected from AC grid and error E050 will be shown on display.

•  Press and hold the ESC key for three seconds to clear the E050 error which will start the self-test.

•  If self-test results are OK, the inverter will reconnect to the AC grid; if the DC arc fault is still present, the self-test will result in error E053. Refer to the 

technical manual online for solutions.  The AFD self-test can be manually started anytime using the following procedure: 

1. Turn off the inverter (switching off both DC and AC switches), 

2. Turn on both the DC and AC switches and wait for display communication of the self-test result.

Waiting Sun . . . .

   

Test Arc Sensor

OK

Arc Self Test

E053

Arc Fault

E050

  0***

>Address

  Display settings

  Address

>2

>Vstart1

   Vstart2

  Language

>Vstart

Содержание TRIO-20.0-27.6-TL-OUTD-US

Страница 1: ... guide the safety and installation information provided in the product manual must be read and followed The technical documentation for the product is available at the website The device must be used in the manner described in the manual If this is not the case the safety devices guaranteed by the inverter might be ineffective ...

Страница 2: ... has been factory programmed to automatically disconnect from the utility distribution system in compliance with UL 1741 and IEEE 1547 specifications Default voltage and frequency trip limit and trip time settings to comply with these standards are shown in table below The Service menu can be used to adjust Voltage and Frequency Trip Limit and Trip Time Parameters according to Grid requirements of...

Страница 3: ...rovide enough conductor to allow for movement of wiring box in final stages Hook wiring box on bracket by inserting heads of rear screws in bracket slots Remove wiring box front cover 08 Loosen connector screws 07 to remove coupling cover 04 and store in pocket at left rear of wiring box Locate four bolts protruding from rear of inverter chassis use as mounting studs and insert into four associate...

Страница 4: ...DC surge protection S1 S1A S1B versions 27 Equipment ground conductor EGC busbar 16 AC cable opening plastic threaded plug trade size 1 28 AC ground The DC EGC is common with the AC side and no other interconnecting jumpers are required If a 2 conduit is needed for DC cable DC cable entries can be punched to ccommodate using a knockout hole punch in location of existing knockouts 7 List of supplie...

Страница 5: ...ghten to chassis to maintain NEMA 4X compliance Connect raceway to chassis pulling conductors through raceway and DC cable openings 11 Connect to DC terminal block 13 Acceptable conductor cross section ranges from 12 AWG to 2AWG copper conductors only Tighten with at least 53 in lbs 6Nm torque Connect any Equipment Grounding conductors in raceway to EGC busbar 27 Connection of inputs on the S2F S2...

Страница 6: ...le inverter activate termination resistance of communication line by moving switch a08 or a09 to ON position Address on inverter is set through user interface on display panel area b7 section 13 Default address is set at 2 ATTENTION A A removeable transparent cover prevents access to the communication card in the wiring box remove four screws in place and remove cover to connect wiring Refer to te...

Страница 7: ...han Vstart icon b11 remains off Waiting Sun is shown in display area b7 and voltage and current are present icons b12 and b13 3 Assoonas WaitingSun conditionsaremet theinvertershowstheAFDboardself testrunning Theresultsareshownindisplayareab7 If a problem on the AFD board is detected the self test will result in an error Refer to section 16 below 4 If there are no irregularities the grid connectio...

Страница 8: ...l Grid Frequency Hz 60 60 Adjustable Grid Frequency Range Hz 57 63 57 63 Maximum Current Iac max phase ARMS 27 0 36 0 Power Factor 0 995 0 995 Total Harmonic Distortion At Rated Power 3 3 Grid Wiring Termination Type Spring Tension Clamp Terminal Copper wiring only 6AWG 4AWG type B or C stranding 19 strand max per conductor Fault Current ARMS 35 0 46 0 Reverse Polarity Protection Yes Passive inver...

Отзывы: