6.  Switchbox components

TRIO-XX.X-TL-OUTD-S-US-480

TRIO-XX.X-TL-OUTD-S1B-US-480

TRIO-XX.X-TL-OUTD-S1-US-480

TRIO-XX.X-TL-OUTD-S1A-US-480

SWITCHBOX COMPONENTS

09

Communication card

17

AC terminal block

10

Service cable opening with plastic threaded plug, trade size 1/2“

18

AC board (behind 19 in -S1A and behind 20 in –S1B

11

DC cable openings with plastic threaded plug*, trade size 1”, 1 ½”

19

Class II AC surge protection (-S1A version)

13

DC terminal block (-S version)

20

Fused AC disconnect switch (-S1B version)

14

DC disconnect switch handle

22

DC fuse holders (-S1, -S1A, -S1B versions)

15

Class II DC surge protection (-S1, -S1A, -S1B versions)

27

Equipment ground conductor (EGC) busbar

16

AC cable opening, plastic threaded plug ,trade size 1”

28

AC ground (The DC EGC is common with the AC side and no 

other interconnecting jumpers are required.)

* If a 2” conduit is needed for DC cable, DC cable entries can be punched to ccommodate using a knockout hole punch in location of existing knockouts.

7. List of supplied components

TRIO version -S with AFD

Switchbox components with AFD

TRIO -S1, -S1A, -S1B with AFD

All -A versions include the arc fault 

 

detection board 29 and paralleling 

 

terminal block 30 mounted on rail in wiring box, in 

addition to components listed above.  

Unless specified, wiring instructions for versions 

with AFD are the same as versions without AFD, 

although 29 and 30 may not be shown.

Содержание TRIO-20.0-27.6-TL-OUTD-US

Страница 1: ... guide the safety and installation information provided in the product manual must be read and followed The technical documentation for the product is available at the website The device must be used in the manner described in the manual If this is not the case the safety devices guaranteed by the inverter might be ineffective ...

Страница 2: ... has been factory programmed to automatically disconnect from the utility distribution system in compliance with UL 1741 and IEEE 1547 specifications Default voltage and frequency trip limit and trip time settings to comply with these standards are shown in table below The Service menu can be used to adjust Voltage and Frequency Trip Limit and Trip Time Parameters according to Grid requirements of...

Страница 3: ...rovide enough conductor to allow for movement of wiring box in final stages Hook wiring box on bracket by inserting heads of rear screws in bracket slots Remove wiring box front cover 08 Loosen connector screws 07 to remove coupling cover 04 and store in pocket at left rear of wiring box Locate four bolts protruding from rear of inverter chassis use as mounting studs and insert into four associate...

Страница 4: ...DC surge protection S1 S1A S1B versions 27 Equipment ground conductor EGC busbar 16 AC cable opening plastic threaded plug trade size 1 28 AC ground The DC EGC is common with the AC side and no other interconnecting jumpers are required If a 2 conduit is needed for DC cable DC cable entries can be punched to ccommodate using a knockout hole punch in location of existing knockouts 7 List of supplie...

Страница 5: ...ghten to chassis to maintain NEMA 4X compliance Connect raceway to chassis pulling conductors through raceway and DC cable openings 11 Connect to DC terminal block 13 Acceptable conductor cross section ranges from 12 AWG to 2AWG copper conductors only Tighten with at least 53 in lbs 6Nm torque Connect any Equipment Grounding conductors in raceway to EGC busbar 27 Connection of inputs on the S2F S2...

Страница 6: ...le inverter activate termination resistance of communication line by moving switch a08 or a09 to ON position Address on inverter is set through user interface on display panel area b7 section 13 Default address is set at 2 ATTENTION A A removeable transparent cover prevents access to the communication card in the wiring box remove four screws in place and remove cover to connect wiring Refer to te...

Страница 7: ...han Vstart icon b11 remains off Waiting Sun is shown in display area b7 and voltage and current are present icons b12 and b13 3 Assoonas WaitingSun conditionsaremet theinvertershowstheAFDboardself testrunning Theresultsareshownindisplayareab7 If a problem on the AFD board is detected the self test will result in an error Refer to section 16 below 4 If there are no irregularities the grid connectio...

Страница 8: ...l Grid Frequency Hz 60 60 Adjustable Grid Frequency Range Hz 57 63 57 63 Maximum Current Iac max phase ARMS 27 0 36 0 Power Factor 0 995 0 995 Total Harmonic Distortion At Rated Power 3 3 Grid Wiring Termination Type Spring Tension Clamp Terminal Copper wiring only 6AWG 4AWG type B or C stranding 19 strand max per conductor Fault Current ARMS 35 0 46 0 Reverse Polarity Protection Yes Passive inver...

Отзывы: