Fimer TRIO-20.0-27.6-TL-OUTD-US Скачать руководство пользователя страница 2

2

1.  Labels and Symbols

The labels on the TRIO inverter carry the markings, main technical data and identification of the equipment and manufacturer.  The technical data shown 

in this quick installation guide does not replace that shown on the labels attached to the equipment.

•  PV source conductors must be Listed PV wire rated 1000V minimum per NEC 690.35. 

•  PV output conductors shall consist of sheathed (jacketed) multi-conductor cables or be installed in an approved raceway and must be isolated from 

enclosure and system grounding, as required by NEC 690.35 and is responsibility of the installer. 

•  The TRIO is designed without an isolation transformer and intended to be installed per NFPA 70, 690.35 with an ungrounded PV array and can be used 

only with PV modules that do not require one of the terminals to be grounded.

•  All PV source and output circuit conductors must have disconnects complying with NEC, Section 690, Part III.

•  To reduce risk of fire, connect only to circuit provided with 40A for 20kW and 50A for 27.6kW maximum branch circuit overcurrent protection in 

accordance with NEC (ANSI/NFPA 70). See Maximum AC OCPD requirement in Technical Data table, Section 17. 

•  For models that do not include AC output overcurrent protection, the end user is responsible for providing protection for AC output circuit.

•  Output circuits must be isolated from enclosure and system grounding, required by Articles 690.40 and 690.42 of NEC, ANSI/NFPA 70, and are the 

responsibility of the installer.

In the manual and/or in some cases on the equipment, the danger or hazard zones are indicated with signs, labels, symbols or icons.

UL 1741; CSA-C22.2 No. 107.1-01

Grounding (earth)

General warning - Important safety information

System earth conductor 

 

(main grounding protective earth, PE)

Hazardous voltage

ø

Phase

Hot surfaces

Direct and alternating currents, respectively

2.  Frequency disconnect

This inverter has been factory programmed to automatically disconnect from the utility distribution system in compliance with UL 1741 and IEEE 1547 

specifications. Default voltage and frequency trip limit and trip time settings to comply with these standards are shown in table below.  The Service menu 

can be used to adjust Voltage and Frequency Trip Limit and Trip Time Parameters according to Grid requirements of installation locale. Refer to technical 

manual for instructions to use the Service menu.

Cond.

      Simulated Utility Source  

Max.time (sec) @60Hz before 

cessation of current to simulated 

utility

Voltage (V) 

Frequency (Hz)

A

< 0.50 Vnom (Fixed)

Rated (60 Hz)

0.16 (Fixed)

B

 0.50 Vnom ≤ V < 0.88 Vnom (Adj. Set Points 55% to 88%)

Rated (60 Hz)

2 (Default)(Adj. Set Points 0.16 to 5 sec)

C

1.10 Vnom < V < 1.20 Vnom(*) (Adj. Set Points 110% to 115%)

Rated (60 Hz)

1 (Default)(Adj. Set Points 0.16 to 5 sec)

D

(*)1.20 Vnom ≤ V(Fixed)

Rated (60 Hz)

0.16 (Fixed)

E

Rated

f>60.5Hz (Default)(Adj. 60.2 to 63.0 Hz) 0.16 (Default) (Adj. 0.16 to 300 sec)

F

Rated

f<59.3 Hz (Default)(Adj. 59.8 to 57.0 Hz)

0.16 (Default) (Adj. 0.16 to 300 sec)

G

Rated

f < 57.0 Hz

0.16 (Fixed)

H

Rated

f > 63.0 Hz

0.16 (Fixed)

3. List of components

Components available for all models

Quantity

3 pin connector for 

configurable relay

2

9 pin connector for 

communication and control 

signals

4

L-key, TORX TX20

1

Jumpers for parallel input 

mode

2

Components available for all models

Quantity

Jumper cables for parallel 

input, (-S1, -S1A, -S1B models)1+1

Bracket for wall mounting

1

4.  Select installation location

Installation position - 

•  Install on a wall or strong structure capable of bearing weight.

•  Install vertically with a maximum incline of +/- 5°.

•  Maintain minimum clearance measurements shown.

•  Ensure sufficient working area in front of inverter for wiring box access.

•  Choose a location that allows unobstructed airflow around inverter.

•  Position multiple inverters side-by-side, maintaining minimum clearances. Multiple inverters can also be placed in 

staggered arrangement.

•  Minimum clearances for staggered arrangements include width of inverter plus additional allowances for inverters 

arranged above or below.

Содержание TRIO-20.0-27.6-TL-OUTD-US

Страница 1: ... guide the safety and installation information provided in the product manual must be read and followed The technical documentation for the product is available at the website The device must be used in the manner described in the manual If this is not the case the safety devices guaranteed by the inverter might be ineffective ...

Страница 2: ... has been factory programmed to automatically disconnect from the utility distribution system in compliance with UL 1741 and IEEE 1547 specifications Default voltage and frequency trip limit and trip time settings to comply with these standards are shown in table below The Service menu can be used to adjust Voltage and Frequency Trip Limit and Trip Time Parameters according to Grid requirements of...

Страница 3: ...rovide enough conductor to allow for movement of wiring box in final stages Hook wiring box on bracket by inserting heads of rear screws in bracket slots Remove wiring box front cover 08 Loosen connector screws 07 to remove coupling cover 04 and store in pocket at left rear of wiring box Locate four bolts protruding from rear of inverter chassis use as mounting studs and insert into four associate...

Страница 4: ...DC surge protection S1 S1A S1B versions 27 Equipment ground conductor EGC busbar 16 AC cable opening plastic threaded plug trade size 1 28 AC ground The DC EGC is common with the AC side and no other interconnecting jumpers are required If a 2 conduit is needed for DC cable DC cable entries can be punched to ccommodate using a knockout hole punch in location of existing knockouts 7 List of supplie...

Страница 5: ...ghten to chassis to maintain NEMA 4X compliance Connect raceway to chassis pulling conductors through raceway and DC cable openings 11 Connect to DC terminal block 13 Acceptable conductor cross section ranges from 12 AWG to 2AWG copper conductors only Tighten with at least 53 in lbs 6Nm torque Connect any Equipment Grounding conductors in raceway to EGC busbar 27 Connection of inputs on the S2F S2...

Страница 6: ...le inverter activate termination resistance of communication line by moving switch a08 or a09 to ON position Address on inverter is set through user interface on display panel area b7 section 13 Default address is set at 2 ATTENTION A A removeable transparent cover prevents access to the communication card in the wiring box remove four screws in place and remove cover to connect wiring Refer to te...

Страница 7: ...han Vstart icon b11 remains off Waiting Sun is shown in display area b7 and voltage and current are present icons b12 and b13 3 Assoonas WaitingSun conditionsaremet theinvertershowstheAFDboardself testrunning Theresultsareshownindisplayareab7 If a problem on the AFD board is detected the self test will result in an error Refer to section 16 below 4 If there are no irregularities the grid connectio...

Страница 8: ...l Grid Frequency Hz 60 60 Adjustable Grid Frequency Range Hz 57 63 57 63 Maximum Current Iac max phase ARMS 27 0 36 0 Power Factor 0 995 0 995 Total Harmonic Distortion At Rated Power 3 3 Grid Wiring Termination Type Spring Tension Clamp Terminal Copper wiring only 6AWG 4AWG type B or C stranding 19 strand max per conductor Fault Current ARMS 35 0 46 0 Reverse Polarity Protection Yes Passive inver...

Отзывы: