PM 1 Installation and Operating Manual v1.2
20
FilterSense © 2016
Grounding
Required for reliable operation and safety.
PM1-T: Earth ground connection is made
through the process mount. Grounding to the
enclosure ground studs is not required.
PM1-A: Earth ground connection should be
made to one of the three ground locations:
o
External enclosure ground screw.
o
Internal enclosure ground screw.
o
Electronics module earth ground
terminal.
Analog wiring cable shield should be
terminated to earth ground in PLC/DCS
cabinet or at panel meter (terminate at one
end only).
Ground wire should not impede service loop.
GROUNDING IN HAZARDOUS AREAS
For hazardous area applications, an external sensor earth ground cable is
required to maintain sensor grounding during installation and maintenance.
The ground cable must remain attached when the sensor is temporarily
removed from the process. Do not disconnect the ground cable.