46
This active control will allow the engineer to view or change the time of
day at which the weekly test will be indicated. Use the alphanumeric
keypad to enter a new time. To confirm the changes press
ENTER.
This active control will allow the engineer to view or change the
number of weeks between routine services. Use the alphanumeric
keypad to enter a time interval up to 99 weeks. To confirm the changes
press
ENTER.
When the routine service is indicated, the user must
enter the
engineer code
and reset the panel to clear.
Please Note: set week to 00 to switch timer off
This active control will allow the engineer to view or change the
operation of programmable input 1. Use the UP and
DOWN arrow keys
to toggle through the following options. To confirm the changes press
ENTER.
1. CONTROL EVENT –
Operation of I/P 1 will operate a
control function on the panel.
2. REMOTE FIRE EVENT–
Operation of I/P 1 will signal a remote
fire input at the control panel. Panel
outputs will be triggered and fire
indication will be shown at the control
panel.
3. TECHNICAL EVENT –
Operation of I/P 1 will signal a
technical event at the control panel.
Panel outputs will be triggered but the
control panel will read technical alarm
and no fire indication will be given.
4. DISABLEMENTS –
Operation of I/P 1 will activate a
disablement on the control panel.
5. DAY-NIGHT MODE –
Operation of I/P 1 will activate the day
mode on the control panel
(TWINFLEX
®
Multipoint devices will
be disabled; TWINFLEX
®
ASD
devices will be disabled for smoke
only but not for heat).
6. PROGRAM I/P 1 OFF –
I/P 1 will not be active.
9. Panel Details
5. Timers
2. Service Timer
01/09/09 20:13 ENGR
WEEKLY TEST TIMER
TIME= 10:00 (HH:MM)
Press Enter Key
9. Panel Details
5. Timers
1. Weekly Test Timer
3. Weekly Test Time
01/09/09 20:13 ENGR
WEEKLY TEST TIMER
TIME= 10:00 (HH:MM)
Press Enter Key
01/09/09 20:13 ENGR
WEEKLY TEST TIMER
TIME= 10:00 (HH:MM)
Press Enter Key
01/09/09 20:13 ENGR
SERVICE TIMER
TIME= 06(0-99) WEEKS
Press Enter Key
10. Panel I/O
1. Programmable I/P 1
1. Input Type
01/09/09 20:13 ENGR
1.CONTROL EVENT
2.REMOTE FIRE EVENT
Press Enter Key