6
Specifications
6.1
Fire Detection
•
Detection time and distance:
•
5ms
-
for fast fire burst or explosion
•
1.5s
-
for 1ft
(0.1m
2
) N-heptane pan fire at 100 ft (30m)
•
4s
-
for 1ft
2
(0.1m
2
) N-heptane pan fire at 230 ft (70m)
•
Field of view: 90° Horizontal, 75° Vertical
•
Time Delay: 0-30 seconds (adjustable)
•
Built-in test: Automatic and Manual
6.2
Video functionality
•
HD Video allowing clear imaging of fire and people at 100ft. (30m) distance.
•
Video recording of alarm events 1 minute before and up to 3 minutes after the flame is
detected.
•
System integration protocol: ONVIF (Open Network Video Interface Forum) Profile S
6.3
Electrical Specifications
•
Operating Voltage: 24 VDC nominal (18-32 VDC)
•
Current Consumption:
•
Standby
180mA
•
Maximum
250mA all systems in operation (including window heater)
•
Cable Entries: 2x conduit entries 3/4” 14NPT or M25x1.5
•
Wiring: 12-20AWG (2.5-0.35mm
2
)
6.4
Outputs
•
Relays: Volt-free contacts rated 2A at 30 VDC
•
Alarm: Normally open
•
Fault
2
: Normally open energized
•
0-20mA (stepped) current output: 3 wire and 4 wire configurations (sink and source).
The 0-20 mA output at different detectors status are define at the below table.
The max load of 0-20 is max 500 ohm at 18-32 VDC. The 0-20 mA is sink isolated and can be
configured as source.
2
The FAULT relay will normally be energized and the contact will be closed during normal operation of the
detector. The contact will be open at fault condition or low voltage.