FIK-UV-IR-HD
User Manual
Doc. No. 06-935.02
For more information & Technical support: (800)-979-FIKE (3453)
8
3
Configuration options
Some functions of the detector can be configured using an RS-485 modem connected to a computer
with the “communicator” software. These configuration options are listed in the following table
along with their factory default values.
Table 1 - Detector Configuration Options
Function
Options
Default Setting
Sensitivity
Low, Medium, High, Extreme
Medium
Ultra-fast detection
Disabled, Enabled
Disabled
Alarm delay
0, 5, 10, 20 or 30 seconds
0 seconds (no delay)
Alarm latch
Disabled, Enabled
Disabled
Window heater
Disabled, Enabled
Enabled
Video module
Disabled, Enabled
Enabled
Post alarm video recording duration
1, 2 or 3 minutes
1 minute
Video analog output
Disabled, NTSC, PAL
Disabled
Modbus address
1 – 247
1
Manual BIT – Alarm Output Test
Disabled, Enabled
Disabled
•
Note:
Medium sensitivity setting allows detection of a 1x1ft
2
(0.1m
2
) N-heptane pan fire at a
distance of 100ft (30m).
3.1
Sensitivity
The detector can be configured to one of four sensitivity levels: low, medium, high and extreme.
The following table lists for each sensitivity setting the maximum distance, in which a standard
fire
would be reliably detected.
1
A standard fire is defined as a 1x1
ft
2
(0.1 m
2
) N-heptane pan fire, with maximum wind speed of 6.5
ft/s (2 m/s).