FIK-UV-IR-HD
User Manual
Doc. No. 06-935.02
For more information & Technical support: (800)-979-FIKE (3453)
15
5
Operation
The FIK-UV-IR-HD is a UV/IR flame detector that includes a built-in high-definition video camera module. The
video module automatically records video of alarm events, and can provide live video of the detection zone
to a screen in the control room.
The detector is ready for detecting fire approximately 30 seconds after power up. During this startup time the
LED flashes Yellow. If the startup is successful, the indication LED turns to green, the 0-20mA indicates 4mA
and the fault relay is closed. The video module starts operating approximately 2 minutes after power up.
Detector configuration settings can be changed as described in section 0.
To restart the detector, turn off and then turn on the power.
5.1
Output Signals
The detector has the following output signals:
•
Current output (0–20mA)
•
Relays (Fault and Alarm)
•
RS-485
•
Tri-color LED
Table 4- Output Signals
Startup
Fault
Dirty Window
Normal
Fire Alarm
0 – 20mA
1mA
1mA
2mA
4mA
20mA
Fault Relay (NO)
Open
Open
Open
Closed
Closed
Alarm Relay NO
Open
Open
Open
Open
Closed
LED
Flashing
Yellow
Flashing
Yellow
Yellow
Green
Red
5.2
Testing
The detector has a Built-In-Test (BIT) capability to ensure proper operation and to make sure that the window
is not dirty. The BIT process runs automatically at startup and periodically during the operation of the
detector. The BIT can also be initiated manually by short circuiting the “Manual BIT” terminal and the “24
VDC (-)“ terminal for one second (see Table 3) or by using the communicator software (connected through
RS-485).
Содержание FIK-UV-IR-F-HD Series
Страница 2: ......