FIK-5496 Manual —
P/N LS10253-001FK-E:A 03/02/2021
7
Section 2: Installation Requirements
2.1 Model FIK-5496
The Model FIK-5496 ships with the following hardware:
•
A cabinet with all hardware assembled.
•
Two keys for theFIK-5496 front door.
•
Ten 4.7K ohm end-of-line resistors
•
A battery wiring harness and jumper to wire batteries in series
2.2 Environmental Specifications
It is important to protect the FIK-5496 control panel from water. To prevent water damage, the following conditions should be AVOIDED
when installing the units:
•
Do not mount the panel directly on exterior walls, especially masonry walls (condensation).
•
Do not mount the panel directly on exterior walls below grade (condensation).
•
Protect the panel from plumbing leaks.
•
Protect the panel from the splash caused by sprinkler system inspection ports.
•
Do not mount the panel in areas with humidity-generating equipment (such as dryers, production machinery).
When you select a location to mount the FIK-5496, the unit should be mounted where it will NOT be exposed to temperatures outside the
range of 0°C-49°C (32°F-120°F) or humidity outside the range of 10%-93% at 30°C (86°F) non-condensing.
2.3 Preventing Water Damage
The water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits that are installed to enter
the top of the cabinet are most likely to cause water problems. The Installers should take reasonable precautions to prevent water from enter-
ing the cabinet. Water damage is not covered under the Warranty.
2.4 FIK-5496 Board and Terminal Strip Description
Figure 2.1 on page 7 illustrates the FIK-5496 circuit board showing the location of the terminals and the dipswitch for setting the module ID.
.
Figure 2.1 The FIK-5496 Board Layout
NOTE:
For UL installations, use the 4.7k
Ω
end-of-line resistor (ordered separately).
DIP switches for
Setting ID
To AC
Regulated
SBUS Module
Connections
Battery
Connections
Output Circuits
DIP switches for
Setting ID
Regulated
SBUS Module
Connections
Battery
Connections
Output Circuits
All Circuits Supervised
Power-limited, except
Battery and AC which are
supervised non-power
limited.