![Fike FIK-5496 Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/fike/fik-5496/fik-5496_installation-and-operation-manual_2288392014.webp)
14
FIK-5496 Manual —
P/N LS10253-001FK-E:A 03/02/2021
Hardware Installation
Sounder Sync Power
3.5.5 Releasing Operations
Figure 3.1 on page 14 lists the Approved releasing solenoids
.
Do not mix the cross alarming zones with the smoke verification zones. There
must be at least two automatic detection devices in each protected space. The spacing must be reduced to 0.7 times the linear spacing in
accordance with NFPA 72.
3.5.6 Auxiliary Power Configuration
The Output circuits 1-4 on the control panel can be used as the auxiliary power circuits. The following list the three types of the auxiliary
power available. Refer to this Section for a description.
The auxiliary power circuits are power-limited. Each circuit can source up to 3A (the total current for all output circuits must not exceed 6.
A). To configure an output circuit as the auxiliary power, do the following.
1.
Wire the output circuit(s) that will be used for the auxiliary power. See Figure 3.7 on page 14 for the location of the output circuits.
2.
Use programming to configure the auxiliary power output for the Door Holder, Constant or Resettable power.
.
Figure 3.7 Output Circuits Used as Auxiliary Power
Door Holder Power
The Door Holder is intended for use with the Fire Door applications. When there are no alarms in the System and the panel has AC power,
the door holder circuits have 24-volt power present at their terminals. Any alarm will cause power to discontinue. The Power will be re-
applied when the System is reset. If the AC power is off for more than 15 seconds, the auxiliary door holder power will be discontinued to
conserve the battery backup power. When the AC power is restored, the power is immediately restored to the door holder circuits.
Constant Power
Use the Constant Power for the applications that require a constant auxiliary power source. The Power is always present at Constant circuits.
Resettable Power
The Resettable power is typically used to power beam detectors, flame detectors, and conventional 4-wire smoke detectors. For circuits
selected as Resettable, 24-volt power is always present at the terminals unless a System Reset occurs. If a System Reset occurs, the power is
removed from the terminals for 30 seconds, then re-applied.
3.6 Sounder Sync Power
The Sounder Sync Power continuously outputs the System Sensor synchronization pattern and is intended for use with B200S sounder bases.
Manufacturer
Part Number
Rating
Current
Freq
Asco
T8210A107
24 VDC
3A max
0 Hz
8210G207
24 VDC
3A max
0 Hz
Table 3.1 Approved Releasing Solenoids
•
Door Holder
•
Constant
•
Resettable
Power-Limited
Supervised when used with the
Power Supervision Relay (PN160150)