Section 2: Installation Requirements

2.1  Model FIK-5496

The Model FIK-5496 ships with the following hardware:

A cabinet with all hardware assembled.

Two keys for theFIK-5496 front door.

Ten 4.7K ohm end-of-line resistors

A battery wiring harness and jumper to wire batteries in series

2.2  Environmental Specifications

It is important to protect the FIK-5496 control panel from water. To prevent water damage, the following conditions should be AVOIDED 

when installing the units:

Do not mount the panel directly on exterior walls, especially masonry walls (condensation).

Do not mount the panel directly on exterior walls below grade (condensation).

Protect the panel from plumbing leaks.

Protect the panel from the splash caused by sprinkler system inspection ports.

Do not mount the panel in areas with humidity-generating equipment (such as dryers, production machinery).

When you select a location to mount the FIK-5496, the unit should be mounted where it will NOT be exposed to temperatures outside the 
range of 0°C-49°C (32°F-120°F) or humidity outside the range of 10%-93% at 30°C (86°F) non-condensing.

2.3  Preventing Water Damage

The water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits that are installed to enter 
the top of the cabinet are most likely to cause water problems. The Installers should take reasonable precautions to prevent water from enter-
ing the cabinet. Water damage is not covered under the Warranty.

2.4  FIK-5496 Board and Terminal Strip Description

Figure 2.1 on page 7 illustrates the FIK-5496 circuit board showing the location of the terminals and the dipswitch for setting the module ID.

.

Figure 2.1  The FIK-5496 Board Layout

NOTE:

For UL installations, use the 4.7k

Ω

 end-of-line resistor (ordered separately).

DIP switches for

Setting ID

To AC

Regulated

SBUS Module

Connections

Battery

Connections

Output Circuits

DIP switches for

Setting ID

Regulated

SBUS Module

Connections

Battery

Connections

Output Circuits

All Circuits Supervised 
Power-limited, except 
Battery and AC which are 
supervised non-power 
limited.

Содержание FIK-5496

Страница 1: ...A P N LS10253 001FK E A ECN 151526 Document LS10253 001FK E 03 02 2021 Distributed Power Module FIK 5496 Installation Operation Manual ...

Страница 2: ...ches a predetermined level Rate of rise heat detectors may be subject to reduced sensitivity over time For this reason the rate of rise feature of each detector should be tested at least once per year by a qualified fire protection specialist Heat detectors are designed to protect property not life IMPORTANT Smoke detectors must be installed in the same room as the control panel and in rooms used ...

Страница 3: ...ior to any drilling filing ream ing or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage threads resulting in reduced terminal contact pressure and difficulty with ...

Страница 4: ... questions about software and the appropriate version for a specific application Documentation Feedback Your feedback helps us keep our documentation up to date and accurate If you have any comments or suggestions about our online Help or printed manuals you can email us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title...

Страница 5: ...rrent Draw and the Standby Battery 8 2 6 1 Worksheet Requirements 8 2 6 2 Current Draw Worksheet 9 2 6 3 Wire Routing 10 Section 3 Hardware Installation 11 3 1 AC Power 11 3 2 Battery Connection 11 3 3 Connecting the FIK 5496 to the FACP 12 3 4 Setting the Device ID 12 3 5 Notification Appliance Wiring 13 3 5 1 Class A Supervised Wiring 13 3 5 2 Class A Output Notification Circuits 13 3 5 3 Class ...

Страница 6: ...circuits Outputs are rated 3 0 A 6 0 A total for each FIK 5496 The FIK 5496 is optically isolated providing ground loop isolation and transient protection The FIK 5496 provides the configuration options that eliminate the need for sychronization modules when you use the AMSECO Faraday Gentex System Sensor or Wheelock synchronization appliances 1 2 Agency Requirements TheFIK 5496 has the same requi...

Страница 7: ... unit should be mounted where it will NOT be exposed to temperatures outside the range of 0 C 49 C 32 F 120 F or humidity outside the range of 10 93 at 30 C 86 F non condensing 2 3 Preventing Water Damage The water damage to the fire system can be caused by moisture entering the cabinet through the conduits Conduits that are installed to enter the top of the cabinet are most likely to cause water ...

Страница 8: ...n the manual refer to the device manual for the current ratings 4 Make sure that the total alarm current you calculated including the current for the panel itself does not exceed 6 0 A This is the maximum alarm current allowable 5 Complete the remaining instructions in Table 2 4 to determine battery size requirements Terminal and Label Description Rating Voltage Current B AC input hot 120 VAC 60 H...

Страница 9: ...ator Transmitter DACT Table 2 3 Maximum Battery Standby Load NOTE Use the 33 maximum battery size for the FM Factory Mutual installations Device Number of Devices Current per Device Standby Current Alarm Current For each device use this formula This column X This column Current per number of devices FIK 5496 Intelligent Power Module Current draw from battery 1 Standby 40 mA 40 mA Alarm 160 mA 160 ...

Страница 10: ...Routing You must follow the power limited wiring standards These standards require you to do the following Maintain one quarter inch spacing between the power limited and the non power limited circuits Separate the high and the low voltage circuits Figure 2 2 Wire Routing Example FIK 5496 Board To AC Power To Battery To SBUS Terminals To NACs ...

Страница 11: ... be necessary for a professional electrician to make this connection The AC terminals are rated as 120 VAC 50 or 60 Hz 2 5 A Figure 3 1 AC Power Connection 3 2 Battery Connection The following list the battery connection requirements The FIK 5496 battery charge capacity is 7 0 AH not to exceed 35 0 AH Use 12V batteries of the same AH rating It is recommended that you replace the batteries every fi...

Страница 12: ... following Fike addressable FACP Installation Manuals that are located on the on Fike s website at www fike com Figure 3 3 Class B FIK 5496 Connection to FACP 3 4 Setting the Device ID All SBUS modules in the System must have a unique number 1 31 to identify them to the FACP Use the DIP switch on the FIK 5496 board to set the module ID number Figure 2 1 on page 2 shows the location of the dipswitc...

Страница 13: ...Supervised Input Output Connections 3 5 3 Class B Supervised Wiring Figure 3 6 on page 13 shows how to wire for the Class B output supervision Use the In Out wiring methods for the proper supervision To identify which notification appliances to be used with the FIK 5496 refer to Appendix A 3 5 4 Class B Output Notification Circuits Figure 3 6 on page 13 shows four 1 5 amp devices wired as Class B ...

Страница 14: ...e with the Fire Door applications When there are no alarms in the System and the panel has AC power the door holder circuits have 24 volt power present at their terminals Any alarm will cause power to discontinue The Power will be re applied when the System is reset If the AC power is off for more than 15 seconds the auxiliary door holder power will be discontinued to conserve the battery backup p...

Страница 15: ...sor or Wheelock synchronization appliances A 2 Agency Requirements TheFIK 5496 has the same requirements as the main control panel These requirements are listed in the Fike addressable FACP Installation Manuals For additional information refer to the Fike s website at www fike com A 3 Reference Documentation This manual describes the installation of the FIK 5496 hardware The software configuration...

Страница 16: ...FIKE CORPORATION 704 SW 10th Street Blue Springs MO 64015 Telephone 1 816 229 3405 www fike com ...

Отзывы: