background image

Form No. 06-795, Rev. 0 (02/16) 

 

Page 5 of 8 

 

 

Figure 6 - Relay Module Configured for “Purge” Operation 

5. Select 

the 

Output

 

Control

 configuration tab (See Figure 7). 

6.  Select priority Row 1 and set the Activation State option to “No State”; Action Type option to “No Action”; and 

Relay State option to “OFF”. This priority row is unused and a placeholder for future use, if desired. The 
programmer can move all rows up one row and program the change accordingly. 

7.  Select priority Row 2 and set the Activation State option to “No State; Action Type option to “Activate on 

Multiple Priority Rows Active”; and Relay State option to “ON”.  

8.  Upon setting the relay action type to “Activate on Multiple Priority Rows Active”, priority row selection fields 

will appear at the bottom of the configuration screen. Set Priority Row A to 3 and Priority Row B to 4. Row two 
of the Output Control table should indicate Group P3, P4. 

9.  Select priority Row 3 and set the Activation State option to “Process”; Action Type option to “Activate on 

Specific Device”; and Relay State option to “OFF. 

10. Upon setting the relay action type to “Activate on Specific Device”, loop and address selection fields will 

appear at the bottom of the configuration screen. Set these fields to match the loop and address of the relay 
module used for the “Agent Soak” timer (i.e., loop 1, address 8). 

11. Select priority row 4 and set the Activation State option to “Process”; Activation Type option to “Activate on 

Specific Device”; and Relay State option to “OFF”. 

12.  Upon setting the relay action type to “Activate on Specific Device”, loop and address selection fields will 

appear at the bottom of the configuration screen. Set these fields to match the loop and address of the 
monitor module used for the “PURGE” key-switch (i.e., loop 1, address 34). 

13.  Remaining configuration options should be left at default settings. 

 

 

Содержание Cheetah Xi

Страница 1: ...roller has been tested by Fike for compatibility and correct operation with both the Cheetah Xi including 50 point and SHP Pro panels The purge controller must be purchased directly from L E D and not from Fike Note This is the only option for performing purge with the SHP Pro panel Option 2 The second option is to utilize the following Cheetah Xi components to accomplish the purge functionality 2...

Страница 2: ...mple shows how to program the Cheetah Xi components to accomplish purge operation For this example the purge operation shall be configured for Zone 1 The first addressable relay module shall be utilized to initiate the Purge Soak period for Zone 1 For this example the module shall be assigned to Loop 1 Address 8 The relay module shall be programmed as follows See Figures 2 and 3 1 With the Common ...

Страница 3: ...nfiguration options should be left at default settings Figure 3 Relay Module Configured for Purge Soak Period One of the normally open relay contacts on the relay module must be wired to the feedback input on the module as shown in Figure 4 below Upon expiration of the relay s internal timer the modules relay contacts will transfer causing activation of the modules feedback input This will cause a...

Страница 4: ... start the purge function Activation of the purge key switch prior to expiration of the Purge Soak timer will only initiate a process input to the panel The second addressable relay module shall be utilized to activate the mechanical components associated with Zone 1 purge operation i e fans dampers etc Activation of this relay shall be triggered by the expiration of the Purge Soak relay timer and...

Страница 5: ... Row B to 4 Row two of the Output Control table should indicate Group P3 P4 9 Select priority Row 3 and set the Activation State option to Process Action Type option to Activate on Specific Device and Relay State option to OFF 10 Upon setting the relay action type to Activate on Specific Device loop and address selection fields will appear at the bottom of the configuration screen Set these fields...

Страница 6: ... same programming process Purge System Status Indication In order to provide visual indication of the status of the purge system operation Fike s 20 Zone remote LED annunciator can be used See Figure 8 For this example the annunciator shall be programmed as follows See Figures 9 and 10 1 Configure LED 01 for ON Zone Release for Zone 1 The yellow LED will turn on upon Zone 1 entering the release st...

Страница 7: ...clarification Design Note Where the system incorporates more than one suppression zone additional relay modules monitor modules and key switches must be added for each additional suppression zone The programming should follow the same general convention shown in this application guide Please feel free to contact Fike s electrical support at 1 800 979 3453 option 2 1 if you have any questions regar...

Страница 8: ...MPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A SPECFIC PURPOSE You should not act on any information products or services described herein before you have formed your own opinion through investigation and research as to the suitability of the information products or services for your specific application and circumstances Fike 704 SW 10 th Street P O Box 610 Blue Springs Missouri 64013 0610...

Отзывы: