6.  Relay modules assigned to purge operation for the suppression zone will activate and their relay contacts 

shall transfer causing the purge system components (i.e., fans, dampers, etc.) for the suppression zone to 
activate. 

7.  Upon activation of the relay modules assigned to purge operation (item 6), the relay module’s contacts will 

transfer sending a “Process” input to the panel via the modules feedback input. 

8.  An LED on a twenty-zone annunciator will illuminate to indicate the active state of the purge system 

component. 

Panel Programming  

The following example shows how to program the Cheetah Xi components to accomplish purge operation. For this 
example, the purge operation shall be configured for Zone 1. 

The first addressable relay module shall be utilized to initiate the “Purge

 

Soak” period for Zone 1. For this example, 

the module shall be assigned to Loop 1, Address 8. The relay module shall be programmed as follows (See Figures 2 
and 3). 

1. With 

the 

Common

 configuration tab for the relay module selected, assign the device trouble assignment to 

Zone 1. 

2.  In the Miscellaneous Option section, select “Independent Dry Contact” option. 

3.  Set the State option for the independent dry contact to “Process”. 

4.  Remaining configuration options, other than the custom message, should be left at default settings. 

 

Figure 2 - Relay Module Configured for “Purge Soak” Period 

 

 

Содержание Cheetah Xi

Страница 1: ...roller has been tested by Fike for compatibility and correct operation with both the Cheetah Xi including 50 point and SHP Pro panels The purge controller must be purchased directly from L E D and not from Fike Note This is the only option for performing purge with the SHP Pro panel Option 2 The second option is to utilize the following Cheetah Xi components to accomplish the purge functionality 2...

Страница 2: ...mple shows how to program the Cheetah Xi components to accomplish purge operation For this example the purge operation shall be configured for Zone 1 The first addressable relay module shall be utilized to initiate the Purge Soak period for Zone 1 For this example the module shall be assigned to Loop 1 Address 8 The relay module shall be programmed as follows See Figures 2 and 3 1 With the Common ...

Страница 3: ...nfiguration options should be left at default settings Figure 3 Relay Module Configured for Purge Soak Period One of the normally open relay contacts on the relay module must be wired to the feedback input on the module as shown in Figure 4 below Upon expiration of the relay s internal timer the modules relay contacts will transfer causing activation of the modules feedback input This will cause a...

Страница 4: ... start the purge function Activation of the purge key switch prior to expiration of the Purge Soak timer will only initiate a process input to the panel The second addressable relay module shall be utilized to activate the mechanical components associated with Zone 1 purge operation i e fans dampers etc Activation of this relay shall be triggered by the expiration of the Purge Soak relay timer and...

Страница 5: ... Row B to 4 Row two of the Output Control table should indicate Group P3 P4 9 Select priority Row 3 and set the Activation State option to Process Action Type option to Activate on Specific Device and Relay State option to OFF 10 Upon setting the relay action type to Activate on Specific Device loop and address selection fields will appear at the bottom of the configuration screen Set these fields...

Страница 6: ... same programming process Purge System Status Indication In order to provide visual indication of the status of the purge system operation Fike s 20 Zone remote LED annunciator can be used See Figure 8 For this example the annunciator shall be programmed as follows See Figures 9 and 10 1 Configure LED 01 for ON Zone Release for Zone 1 The yellow LED will turn on upon Zone 1 entering the release st...

Страница 7: ...clarification Design Note Where the system incorporates more than one suppression zone additional relay modules monitor modules and key switches must be added for each additional suppression zone The programming should follow the same general convention shown in this application guide Please feel free to contact Fike s electrical support at 1 800 979 3453 option 2 1 if you have any questions regar...

Страница 8: ...MPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A SPECFIC PURPOSE You should not act on any information products or services described herein before you have formed your own opinion through investigation and research as to the suitability of the information products or services for your specific application and circumstances Fike 704 SW 10 th Street P O Box 610 Blue Springs Missouri 64013 0610...

Отзывы: