Triangle Tube’s ProtoNode Startup Guide
Page 9 of 40
ProtoCessor
1991 Tarob Court Milpitas, California 95035 USA
Web
2.3.1 Selecting Configuration Files for Devices: “S” bank DIP Switches S0 – S3
S0 S1 S2 S3
S0 – S3 DIP Switches
S Bank DIP Switch Location
Figure 3: S Bank DIP Switches
2.3.1.1 BACnet MS/TP and BACnet IP DIP Switch Settings
•
The S bank of DIP switches (S0 - S3) are used to select and load a configuration file from a group of
pretested/preloaded configuration files which are stored in the ProtoNode FPC-N34 (BACnet MS/TP,
BACnet/IP, Modbus TCP, Metasys N2) and the ProtoNode FPC-N35 (LonWorks).
The following chart describes S0 - S3 DIP Switch configuration settings for 1 through 8 device applications to
support
BACnet MS/TP and BACnet/IP
on a ProtoNode FPC-N34
Cover doesn’t need to be Removed
ProtoCarrier DIP Switches
Profile -
FPC-N34-0822
S0
S1
S2
S3
1 Prestige to BACnet IP/BACnet MSTP
Off Off Off Off
2 Prestige to BACnet IP/BACnet MSTP
On Off Off Off
3 Prestige to BACnet IP/BACnet MSTP
Off On Off Off
4 Prestige to BACnet IP/BACnet MSTP
On On Off Off
5 Prestige to BACnet IP/BACnet MSTP
Off Off On Off
6 Prestige to BACnet IP/BACnet MSTP
On Off On Off
7 Prestige to BACnet IP/BACnet MSTP
Off On On Off
8 Prestige to BACnet IP/BACnet MSTP
On On On Off
1 Keystone to BACnet IP/BACnet MSTP
Off Off Off On
2 Keystone to BACnet IP/BACnet MSTP
On Off Off On
3 Keystone to BACnet IP/BACnet MSTP
Off On Off On
4 Keystone to BACnet IP/BACnet MSTP
On On Off On
5 Keystone to BACnet IP/BACnet MSTP
Off Off On On
6 Keystone to BACnet IP/BACnet MSTP
On Off On On
7 Keystone to BACnet IP/BACnet MSTP
Off On On On
8 Keystone to BACnet IP/BACnet MSTP
On On On On
See Appendix B.1 for the Configuration DIP switch settings for - 1 through 8 Prestige and Keystone to Metasys N2
and Modbus TCP.
NOTE:
When setting DIP Switches, please ensure that power to the board is OFF.
2.3 Selecting Stored Configurations, Setting the Mac Address, Node_ID, and Baud Rate