Triangle Tube’s ProtoNode Startup Guide
Page 39 of 40
ProtoCessor
1991 Tarob Court Milpitas, California 95035 USA
Web
Appendix E.1.1.
Compliance with UL Regulations
ProtoNode FPC-N34
ProtoNode FPC-N35
Electrical
Connections
One 6-pin Phoenix connector, one RS-485
+/- ground port, power +/- frame ground
port
One 3-pin RS-485 Phoenix connector, one
RS-485 +/- ground port
One Ethernet-10/100 Ethernet port
One 6-pin Phoenix connector, one RS-485
+/- ground port, power +/- frame ground
port
One Ethernet 10/100 BaseT port
One FTT-10 LonWorks port
Approvals:
Pending CE (EN55022;EN55024; EN60950), UL916, Pending FCC Class A Part 15, DNP3
Conformance Tested, OPC Self-tested for Compliance, RoHS Compliant, CSA 205 Approved
BTL Marked
LonMark Certified
Power
Requirements
Multi-mode power adapter: 9 - 30VDC or 12 - 24VAC
Physical
Dimensions
11.5 cm L x 8.3 cm W x 4.1 cm H (4.5 x 3.2 x 1.6 in.)
Weight:
0.2 kg (0.4 lbs)
Operating
Temperature:
-40°C to 75°C (-40°F to167°F)
Surge Suppression
EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT
Humidity:
5 - 90% RH (non-condensing)
(Specifications subject to change without notice)
Figure 27: Specifications
For UL compliance, the following instructions must be met when operating ProtoNode.
•
The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating
temperature range.
•
The interconnecting power connector and power cable shall:
•
Comply with local electrical code.
•
Be suited to the expected operating temperature range.
•
Meet the current and voltage rating for ProtoNode/Net
•
Furthermore, the interconnecting power cable shall:
•
Be of length not exceeding 3.05m (118.3”)
•
Be constructed of materials rated VW-1 or FT-1 or better
•
If the unit is to be installed in an operating environment with a temperature above 65 °C, it should be
installed in a Restricted Access Area requiring a key or a special tool to gain access
•
This device must not be connected to a LAN segment with outdoor wiring.
Appendix E.1. Specifications
Appendix E.
Reference