background image

FS-8700-130 Notifier NCA2/NFS-3030 Manual 

 

 

 

 

Page 16 of 22 

FieldServer Technologies

 1991 Tarob Court Milpitas, California 95035 USA   

Web

: www.fieldserver.com 

Tel

: (408) 262-2299   

Fax

: (408) 262-2269   

Toll Free

: (888) 509-1970   

email

[email protected] 

System Trouble         

Address   

System Trouble         

Address 

ANALOG OUTPUT 1 TROUBLE                     

113 

 

LIB #2 SCB RECEIVE ERROR                    

367 

ANALOG OUTPUT 2 TROUBLE                     

114 

 

LIB #3 SCB RECEIVE ERROR                    

368 

ANALOG OUTPUT 3 TROUBLE                     

115 

 

LIB #4 SCB RECEIVE ERROR                    

369 

ANALOG OUTPUT 4 TROUBLE                     

116 

 

LIB #5 SCB RECEIVE ERROR                    

370 

AUXILIARY TROUBLE                           

117 

 

LIB #6 SCB RECEIVE ERROR                    

371 

UDACT TROUBLE                               

118 

 

LIB #7 SCB RECEIVE ERROR                    

372 

AVPS. TROUBLE                               

119 

 

LIB #8 SCB RECEIVE ERROR                    

373 

MASTER BOX TROUBLE                          

120 

 

LIB #9 SCB RECEIVE ERROR                    

374 

AUXIN TROUBLE                               

121 

 

LIB #10 SCB RECEIVE ERROR                   

375 

DIGIN TROUBLE                               

122 

 

LIB #1 SCB ACKNOWLEDGE ERROR                

376 

FFT TROUBLE                                 

123 

 

LIB #2 SCB ACKNOWLEDGE ERROR                

377 

REMOTE MIC TROUBLE                          

124 

 

LIB #4 SCB ACKNOWLEDGE ERROR                

378 

LOCAL MIC TROUBLE                           

125 

 

LIB #5 SCB ACKNOWLEDGE ERROR                

379 

LOCAL PHONE TROUBLE                         

126 

 

LIB #6 SCB ACKNOWLEDGE ERROR                

380 

POWER SUPPLY TROUBLE                        

127 

 

LIB #7 ACKNOWLEDGE ERROR                    

381 

FIM TROUBLE - FIELD INTERFACE MODULE        

128 

 

LIB #8 SCB ACKNOWLEDGE ERROR                

382 

LIM TROUBLE - LOOP INTERFACE MODULE         

129 

 

LIB #9 SCB ACKNOWLEDGE ERROR                

383 

NIM TROUBLE - NETWORK INTERFACE MODULE      130 

 

LIB #10 SCB ACKNOWLEDGE ERROR               

384 

SYSTEM TROUBLE DEFAULT MESSAGE              

131 

 

LIB #1 NIB COMMUNICATION ERROR              

385 

TROUBLE                                     

132 

 

LIB #2 NIB COMMUNICATION ERROR              

386 

ANNUN 1 NO ANSWER                           

133 

 

LIB #3 NIB COMMUNICATION ERROR              

387 

ANNUN 2 NO ANSWER                           

134 

 

LIB #4 NIB COMMUNICATION ERROR              

388 

ANNUN 3 NO ANSWER                           

135 

 

LIB #5 NIB COMMUNICATION ERROR              

389 

ANNUN 4 NO ANSWER                           

136 

 

LIB #6 NIB COMMUNICATION ERROR              

390 

ANNUN 5 NO ANSWER                           

137 

 

LIB #7 NIB COMMUNICATION ERROR              

391 

ANNUN 6 NO ANSWER                           

138 

 

LIB #8 NIB COMMUNICATION ERROR              

392 

ANNUN 7 NO ANSWER                           

139 

 

LIB #9 COMMUNICATION ERROR                  

393 

ANNUN 8 NO ANSWER                           

140 

 

LIB #10 NIB COMMUNICATION ERROR             

394 

ANNUN 9 NO ANSWER                           

141 

 

LIB #1 NIB M/S PROGRAMMING ERROR            

395 

ANNUN 10 NO ANSWER                          

142 

 

LIB #2 NIB M/S PROGRAMMING ERROR            

396 

ANNUN 11 NO ANSWER                          

143 

 

LIB #3 NIB M/S PROGRAMMING ERROR            

397 

ANNUN 12 NO ANSWER                          

144 

 

LIB #4 NIB M/S PROGRAMMING ERROR            

398 

ANNUN 13 NO ANSWER                          

145 

 

LIB #5 NIB M/S PROGRAMMING ERROR            

399 

ANNUN 14 NO ANSWER                          

146 

 

LIB #6 NIB M/S PROGRAMMING ERROR            

400 

ANNUN 15 NO ANSWER                          

147 

 

LIB #7 NIB M/S PROGRAMMING ERROR            

401 

ANNUN 16 NO ANSWER                          

148 

 

LIB #8 NIB M/S PROGRAMMING ERROR            

402 

ANNUN 17 NO ANSWER                          

149 

 

LIB #9 NIB M/S PROGRAMMING ERROR            

403 

ANNUN 18 NO ANSWER                          

150 

 

LIB #10 NIB M/S PROGRAMMING ERROR           

404 

ANNUN 19 NO ANSWER                          

151 

 

INTERNAL RAM ERROR                          

405 

ANNUN 20 NO ANSWER                          

152 

 

EXTERNAL RAM ERROR                          

406 

ANNUN 21 NO ANSWER                          

153 

 

CPU EXTERNAL RAM TEST ERROR                 

407 

ANNUN 22 NO ANSWER                          

154 

 

CATASTROPHIC CUP NONVOLATILE RAM            

408 

ANNUN 23 NO ANSWER                          

155 

 

DIB EXTERNAL RAM TEST ERROR                 

409 

ANNUN 24 NO ANSWER                          

156 

 

CATASTROPHIC DIA NONVOLATILE RAM            

410 

ANNUN 25 NO ANSWER                          

157 

 

EPROM ERROR                                 

411 

ANNUN 26 NO ANSWER                          

158 

 

PRINTER SUPERVISORY PATH IS INTERRUPTED     

412 

ANNUN 27 NO ANSWER                          

159 

 

PRINTER SUPERVISORY                         

413 

ANNUN 28 NO ANSWER                          

160 

 

PRINTER COVER OPEN                          

414 

ANNUN 29 NO ANSWER                          

161 

 

PRINTER PAPER OUT                           

415 

ANNUN 30 NO ANSWER                          

162 

 

PRINTER BUFFER FULL OR OUT OF PAPER         

416 

ANNUN 31 NO ANSWER                          

163 

 

AUX PRINTER BUFFER FULL OR OUT OF PAPER     

417 

ANNUN 32 NO ANSWER                          

164 

 

PRINTER OFF LINE                            

418 

REMOTE DISPLAY 1 NO ANSWER                  

165 

 

PRINT QUEUE FULL                            

419 

REMOTE DISPLAY 2 NO ANSWER                  

166 

 

FACP PRINT BUFFER FULL                      

420 

REMOTE DISPLAY 3 NO ANSWER                  

167 

 

CORRUPT LOGIC EQUAT                         

421 

REMOTE DISPLAY 4 NO ANSWER                  

168 

 

PROGRAM CORRUPTED                           

422 

REMOTE DISPLAY 5 NO ANSWER                  

169 

 

DATABASE CORRUPTED                          

423 

REMOTE DISPLAY 6 NO ANSWER                  

170 

 

AUDIO LIBRARY CORRUPTED                     

424 

REMOTE DISPLAY 7 NO ANSWER                  

171 

 

LCD80 SUPERVISORY                           

425 

Содержание NCA2-NFS2-3030

Страница 1: ...ITY EFFECTIVITY Effective for all systems manufactured after January 2009 Driver Manual Supplement to the FieldServer Instruction Manual FS 8700 130 Notifier NCA2 NFS2 3030 Driver Version 1 02 Document Revision 1 ...

Страница 2: ... 2 Data Arrays Descriptors 8 4 3 Client Side Connection Descriptions 9 4 4 Client Side Node Descriptors 9 4 5 Client Side Map Descriptors 10 4 5 1 FieldServer Related Map Descriptor Parameters 10 4 5 2 Driver Related Map Descriptor Parameters 10 4 5 3 Map Descriptor Example Standard example 11 5 Configuring the FieldServer as a Notifier NCA2 NFS2 3030 Server 12 Appendix A Advanced Topics 13 Append...

Страница 3: ...itored by third party tools Since the FieldServer does not actively poll for data the accuracy and timeliness of the stored data is limited to the frequency of update messages that the Notifier Fire Panel issues If a networked panel does not send the CLEARED message for latched points via the NCA2 it is not possible to detect cleared points unless a system reset is done It is possible to configure...

Страница 4: ...n drawing Configure the Notifier Panel according to manufacturer s instructions FieldServer FieldServer Part 8917 16 Pigtail for RJ45 Port RJ45 Connection to TB5 Printer Port Notifier NCA2 NFS2 3030 Connect to one of the RS 232 Ports on the FieldServer P1 CTX CRX REF PTX PRX REF TB5 Printer CRT Rx Brown Tx Orange White Com Blue White 1 8 Connector Pinouts TB5 CRT Function Receive Reference Transmi...

Страница 5: ...l 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com 3 1 Hardware Connection Tips Hints The FieldServer should preferably be connected to the TB5 Printer port It is theoretically possible to connect to the TB5 CRT port but this has not been fully tested The Panel s port must be enabled and set to 80 Columns Not Supervised ...

Страница 6: ...ing the text messages sent to the printer or CRT port Not all messages will be interpreted as many messages do not directly pertain to device status or are not currently supported The following subset of event messages is recognized Active Events FIRE ALARM SECURITY ALARM LIFE LIFE CRITICAL ALARM MEDICAL EMERGENCY SECURITY ALARM CRITICAL PROCESS SUPERVISORY TROUBLE FAULT DISABLED PREALARM ACTIVE O...

Страница 7: ...Active 1432 1590 ON OFF 1591 1749 Memory Type Detector_Trouble Module_Trouble Troubles Faults 1 159 Parameter Addresses For each Node Memory Type Node_Trouble Troubles Faults 1 508 Memory Type Panel Panel Maximum12 Boards and 8 Panel circuits per Board Hardware address memory address Board 1 panel 1 1 Board 1 panel 2 2 Board 2 panel 1 9 Board 12 panel 8 96 Fire Alarm 1 96 Security Life 97 192 Life...

Страница 8: ...ide Map Descriptors section Details on how to do this can be found below Note that in the tables indicates an optional parameter with the bold legal value being the default Section Title Data_Arrays Column Title Function Legal Values Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Array_Format Provide data format Each Data Array can only take on one format Bit Sin...

Страница 9: ...its Specify data bits 8 Vendor limitation Stop_Bits Specify stop bits 1 Vendor limitation Example Client Side Connections Connections Port Protocol Baud Stop_Bits Parity P8 nfs2 nca 9600 1 None 4 4 Client Side Node Descriptors Section Title Nodes Column Title Function Legal Values Node_Name Provide name for Node Up to 32 alphanumeric characters Node_ID Station address of any physical Node on netwo...

Страница 10: ...riptor Passive 4 5 2 Driver Related Map Descriptor Parameters Column Title Function Legal Values Node_Name Name of Node to fetch data from One of the Node names specified in Client Node Descriptor above Data_Type Specify memory area type Detector Module Detector_Trouble Module_Trouble Panel Panel_Trouble Bell_Trouble Node_Trouble Address Starting address of block As per Data_type Detector Module 1...

Страница 11: ...fset Function Node_Name Loop Data_Type Address Length Capture Node Events SMD_N2_Troubles DA_SYS_N2 0 Passive NODE2 Node_Trouble 1 508 SMD_N2_PANEL DA_N2_PANEL 0 Passive NODE2 Panel 1 1056 SMD_N2_PANEL_T DA_N2_PANEL_T 0 Passive NODE2 Panel_Trouble 1 96 SMD_N2_BELL_T DA_N2_BELL_T 0 Passive NODE2 Bell_Trouble 1 4 Capture Loop 1 events SMD_N2L01D DA_N2L01D 0 Passive NODE2 1 Detector 1 1749 SMD_N2L01D...

Страница 12: ...logies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com 5 CONFIGURING THE FIELDSERVER AS A NOTIFIER NCA2 NFS2 3030 SERVER This driver cannot be configured as a Server ...

Страница 13: ... states 1 0 SECURITY ALARM CLEARED SECURITY ALARM states 1 0 CRITICAL PROCESS CRITICAL PROCESS states 1 0 SUPERVISORY CLEARED SUPERVISORY states 1 0 TROUBLE FAULT CLEARED TROUBLE FAULT States counter DISABLED CLEARED DISABLED states 1 0 PREALARM CLEARED PREALARM states 1 0 ACTIVE CLEARED ACTIVE states 1 0 ON OFF OFF states 1 0 SYSTEM NORMAL Resets all addresses in all memory areas but only if data...

Страница 14: ...D 5 276 STYLE 6 NEG LOOP 10 23 COMM FAULT LOOP INTERFACE BOARD 6 277 STYLE 6 POS LOOP 1 24 COMM FAULT LOOP INTERFACE BOARD 7 278 STYLE 6 POS LOOP 2 25 COMM FAULT LOOP INTERFACE BOARD 8 279 STYLE 6 POS LOOP 3 26 COMM FAULT LOOP INTERFACE BOARD 9 280 STYLE 6 POS LOOP 4 27 COMM FAULT LOOP INTERFACE BOARD 10 281 STYLE 6 POS LOOP 5 28 CATASTROPHIC ISIB COMMUNICATIONS FAULT 282 STYLE 6 POS LOOP 6 29 MEM...

Страница 15: ...BOVE LIMIT ON LOOP 10 335 REMOTE DISPLAY 2 TROUBLE 82 TOO MANY DEVICES ON LOOP 1 336 REMOTE DISPLAY 3 TROUBLE 83 TOO MANY DEVICES ON LOOP 2 337 REMOTE DISPLAY 4 TROUBLE 84 TOO MANY DEVICES ON LOOP 3 338 REMOTE DISPLAY 5 TROUBLE 85 TOO MANY DEVICES ON LOOP 4 339 REMOTE DISPLAY 6 TROUBLE 86 TOO MANY DEVICES ON LOOP 5 340 REMOTE DISPLAY 7 TROUBLE 87 TOO MANY DEVICES ON LOOP 6 341 REMOTE DISPLAY 8 TRO...

Страница 16: ...NNUN 6 NO ANSWER 138 LIB 8 NIB COMMUNICATION ERROR 392 ANNUN 7 NO ANSWER 139 LIB 9 COMMUNICATION ERROR 393 ANNUN 8 NO ANSWER 140 LIB 10 NIB COMMUNICATION ERROR 394 ANNUN 9 NO ANSWER 141 LIB 1 NIB M S PROGRAMMING ERROR 395 ANNUN 10 NO ANSWER 142 LIB 2 NIB M S PROGRAMMING ERROR 396 ANNUN 11 NO ANSWER 143 LIB 3 NIB M S PROGRAMMING ERROR 397 ANNUN 12 NO ANSWER 144 LIB 4 NIB M S PROGRAMMING ERROR 398 A...

Страница 17: ...R SECONDARY STATUS 450 UDACT NO ANSWER 197 LINK PROTECTOR PRIMARY NOT PRESENT 451 MASTER BOX NO ANSWER 198 EVENT BUFFER 80 FULL 452 DAA NO ANSWER 199 EBI STATUS 453 NO ANSWER 200 SOFTWARE MISMATCH 454 NETWORK FAILURE 201 NO POWER SUPPLY INST 455 WORKSTATION FAN FAILURE 202 TEST PROGRAM UPDATE 456 UPS FAILURE 203 HISTORY 80 FULL 457 NCM COMM FAILURE 204 FLASH IMAGE ERROR 458 NODE COMMUNICATIONS FAI...

Страница 18: ...L PORT B 244 DVC COMM LOSS 498 STYLE 4 SHORT A L1 245 A C POWER LOSS BACK UP ACTIVATED 499 STYLE 4 SHORT B L1 246 BUZZER OFF LINE 500 STYLE 4 SHORT A L2 247 PANEL DOOR OPEN 501 STYLE 4 SHORT B L2 248 OFF NETWORK 502 STYLE 4 SHORT A L3 249 INSTALL ERROR 503 STYLE 4 SHORT B L3 250 OR AUDIO TELEPHON 504 STYLE 4 SHORT A L4 251 EXPANDER MODULES 505 STYLE 4 SHORT B L4 252 MANUAL CONTROL 506 STYLE 4 SHOR...

Страница 19: ...NCA 2 EIA 232 Protocol Data Formats 53219 Rev A 1 3 2008 Any changes or additions by Notifier will not be reflected in this driver unless specifically revised This driver will not record information about zone status that is incorporated with point status messages There can only be one panel connected to any given FieldServer port This driver records data as presented to the printer CRT port by th...

Страница 20: ...e ground potential problems Appendix B 2 Networking Tips By default FieldServer does not take any action on receiving a SYSTEM RESET Normally when a Node initiates SYSTEM RESET by pressing the RESET button on the Panel the panel sends an individual CLEAR message for every point it clears in its memory area The FieldServer therefore waits for the CLEAR message to clear a specific bit in its memory ...

Страница 21: ... d Node u Loop d Data_Type s Address d The FieldServer got a recognized message on this particular port Node loop Address_Type and Address but did not find a defined Map Descriptor To capture this data add a new Map Descriptor with the required parameters 2 Err Reset Normal queue d full on MD s This driver keeps track of all non zero memory locations per Map Descriptor When the track queue is full...

Страница 22: ...n 0 This occurs due to poor synchronization between the FieldServer and the Notifier panel or because a problem existed before connection 3 It will rectify itself upon System Normal message Check the configuration file to identify the address and memory area type mapped to this offset and the Data Array which is causing the error 3 All Data Arrays on the FieldServer are initialized to zero on rebo...

Отзывы: