FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 18 of 22
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262-2299
Fax
: (408) 262-2269
Toll Free
: (888) 509-1970
System Trouble
Address
System Trouble
Address
LOOP CONTINUITY TEST FAIL LOOP 3
231
WALK TEST - FIRE PROTECTION IS LIMITED
485
LOOP CONTINUITY TEST FAIL LOOP 4
232
REMOTE PROG MODE ACCESSED
486
LOOP CONTINUITY TEST FAIL LOOP 5
233
DIA PROG. CHANGE DET. SERVICE REQUIRED
487
LOOP CONTINUITY TEST FAIL LOOP 6
234
ISIB DATA MESSAGE RECEIVED ERROR
488
LOOP CONTINUITY TEST FAIL LOOP 7
235
ISIB EXECUTIVE ROUTINE RE-ENTERED
489
LOOP CONTINUITY TEST FAIL LOOP 8
236
DIB TO SIB CABLE BAD OR MISSING
490
LOOP CONTINUITY TEST FAIL LOOP 9
237
UPLOAD/DOWNLOAD MESSAGE RECEIVED
491
LOOP CONTINUITY TEST FAIL LOOP 10
238
GLOBAL DATABASE MISMATCH
492
AMP FAIL
239
SIB PROG. CHANGE DET. SERVICE REQUIRED
493
AC FAIL
240
HS-NCM SNIFFER MODE ACTIVE
494
SCB ASSEM. COM. VERIFIED FAILED
241
EXCEEDED CONNECTION LIMIT
495
8255 PORT CHIP CONTROL WORD CHECK FAILE 242
NAM CCBE. PROG LOST
496
NETWORK COMMUNICATION LINK FAIL PORT A 243
MEMORY LOSS
497
NETWORK COMMUNICATION LINK FAIL PORT B 244
DVC COMM LOSS
498
STYLE 4 SHORT A L1
245
A.C. POWER LOSS. BACK UP ACTIVATED
499
STYLE 4 SHORT B L1
246
BUZZER OFF-LINE
500
STYLE 4 SHORT A L2
247
PANEL DOOR OPEN
501
STYLE 4 SHORT B L2
248
OFF NETWORK
502
STYLE 4 SHORT A L3
249
INSTALL. ERROR
503
STYLE 4 SHORT B L3
250
OR AUDIO/TELEPHON
504
STYLE 4 SHORT A L4
251
EXPANDER MODULES
505
STYLE 4 SHORT B L4
252
MANUAL CONTROL
506
STYLE 4 SHORT A L5
253
CAT. COMM. FAULT
507
STYLE 4 SHORT B L5
254
UNKNOWN
508
Appendix A.3.
Node Status
•
Data for any particular Node is valid while that Node is online and the system is synchronized. Integrity of
data for any Node will be lost if the Node goes offline or if synchronism between the FieldServer and the
NCA2 Panel is lost.
•
Node status offline/online (1/0) is stored in the 502
nd
address. It is important to read the Node status
before reading any information about the Node.
•
Node status data integrity itself depends upon system synchronization.
Appendix A.4.
FieldServer Synchronization
There is currently no method of auto-synchronizing the FieldServer's Data Arrays with the Notifier NCA2/NFS2-
3030 panel because there is no method for polling the panel through the printer or CRT port. Synchronization of
the two devices can be achieved manually pressing the “System Reset” button on the panel while the FieldServer is
connected and running. All current events will be re-sent to the FieldServer..