FS-8700-19_Metasys_N2 Driver Manual
Page 37 of 51
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
:www.fieldserver.com
Tel
: (408) 262-2299
Fax
: (408) 262-2296
Toll_Free
: 888-509-1970
PAGE 0
Item
DEC
Item
HEX
Signal Condition Read/Write
Johnson
Tag
Description
180 B4
Byte
Write
TYPE8
Controller type
181 B5
FP
Write
LS8
Local setpoint
182 B6
FP
Write
PB8
Proportional band
183 B7
FP
Write
TI8
Reset action
184 B8
FP
Write
TD8
Rate action
185 B9
FP
Write
HL8
Upper limit of the control output
186 BA
FP
Write
LL8
Lower limit of the control output
187 BB
FP
Write
BS8
Change of setpoint during STAND-BY
188 BC
FP
Write
BO8
Change of setpoint during OFF
189 BD
FP
Write
AD8
Deviation alarm
190 BE
Byte
Write
IR1
Range analog input 1
191 BF
FP
Write
HA1
High alarm input 1
192 C0
FP
Write
LA1
Low alarm input 1
193 C1
FP
Write
FI1
Filter time input 1
194 C2
Byte
Write
IR2
Range analog input 2
195 C3
FP
Write
HA2
High alarm input 2
196 C4
FP
Write
LA2
Low alarm input 2
197 C5
FP
Write
FI2
Filter time input 2
198 C6
Byte
Write
IR3
Range analog input 3
199 C7
FP
Write
HA3
High alarm input 3
200 C8
FP
Write
LA3
Low alarm input 3
201 C9
FP
Write
FI3
Filter time input 3
202 CA
Byte
Write
IR4
Range analog input 4
203 CB
FP
Write
HA4
High alarm input 4
204 CC
FP
Write
LA4
Low alarm input 4
205 CD
FP
Write
FI4
Filter time input 4
206 CE
Byte
Write
IR5
Range analog input 5
207 CF
FP
Write
HA5
High alarm input 5
208 D0
FP
Write
LA5
Low alarm input 5
209 D1
FP
Write
FI5
Filter time input 5
210 D2
Byte
Write
IR6
Range analog input 6
211 D3
FP
Write
HA6
High alarm input 6
212 D4
FP
Write
LA6
Low alarm input 6
213 D5
FP
Write
FI6
Filter time input 6
214 D6
Byte
Write
IR7
Range analog input 7
215 D7
FP
Write
HA7
High alarm input 7
216 D8
FP
Write
LA7
Low alarm input 7
217 D9
FP
Write
FI7
Filter time input 7
218 DA
Byte
Write
IR8
Range analog input 8
219 DB
FP
Write
HA8
High alarm input 8
220 DC
FP
Write
LA8
Low alarm input 8
221 DD
FP
Write
FI8
Filter time input 8
222 DE
FP
Write
OH1
Output 1 high range
223 DF
FP
Write
OL1
Output1 low range
224 E0
Byte
Write
OMS1
Source of analog output module 1
225 E1
FP
Write
OH2
Output 2 high range
226 E2
FP
Write
OL2
Output 2 low range
227 E3
Byte
Write
OMS2
Source of analog output module 2
228 E4
FP
Write
OH3
Output OUTA1 high range
229 E5
FP
Write
OL3
Output OUTA1 low range
230 E6
Byte
Write
OMS3
Source of logic output module OUTA